Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-01 Cont ID  
Sent By dpalmer Date 2002-05-01 Time 06:46 Rev Time 0.00
Received By dpalmer Date 2002-05-01 Time 06:46 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-26 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 07:21 Rev Time 0.00
Received By dpalmer Date 2002-04-26 Time 07:21 Sent To P
Notes
2002-04-26 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE NOTE PLANS STILL SHOWING
 96 NEC CODE ARTS. PLEASE CORRELATE
 W/ 99 NEC.
  
 2)NOTE: PLEASE NOTE MISPRINT FOR AIC
 RATING, SHOWN AS 22.00, INSTEAD OF
 22,000.
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4))NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE/NOTES. PER 210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-05 Cont ID  
Sent By pkrauss Date 2002-12-05 Time 15:37 Rev Time 0.25
Received By pkrauss Date 2002-12-04 Time 15:26 Sent To  
Notes
2002-12-05 00:00:00MECHANICAL PERMIT 02040552

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-20 Cont ID  
Sent By hmoser Date 2002-06-20 Time 20:02 Rev Time 0.50
Received By hmoser Date 2002-06-20 Time 20:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-25 Cont ID  
Sent By hmoser Date 2002-04-25 Time 17:23 Rev Time 0.33
Received By hmoser Date 2002-04-25 Time 17:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-27 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 07:21 Rev Time 0.33
Received By jleech Date 2002-04-27 Time 13:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-07-31 Cont ID  
Sent By rmcdouga Date 2002-07-31 Time 10:25 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-31 00:00:00************BUILDING PROVISO************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SUBMIT SOIL BEARING TEST REPORTS PRIOR
 TO POURING FOUNDATION.
  
 4) SUBMIT (2) STORM PANEL INSTALLATION
 SCHEDULES LISTING ALL THE OPENINGS THAT
 ARE BEING SHUTTERED. THE ONES THAT WERE
 SUBMITTED ONLY LISTED 7 OF 10 OPENINGS.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 EVALUATIONS FOR THE GLASS BLOCK. ONLY
 PORTIONS OF THE METRO-DADE PRODUCT
 APPROVAL WAS SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-06-26 Cont ID  
Sent By rmcdouga Date 2002-06-26 Time 18:16 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-26 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN 'A8'
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 3) PROVIDE SOIL BEARING TEST REPORT PER
 CITY OF WPB AMENDMENTS TO 2001 FBC SEC.
 1804.2.2.
  
 4) PROVIDE ADDITIONAL COPIES OF PRODUCT
 APPROVALS FOR THE FRONT DOOR AND GLASS
 BLOCK. TWO COPIES ARE REQUIRED.
  
 5) PROVIDE TESTING INFORMATION WHICH
 INDICATES THAT THE GLASS BLOCK TO BE
 INSTALLED ON THE ZERO LOT LINE HAS A ONE
 HOUR FIRE RATING.
  
 6) PROVIDE (2) COPIES OF INSTALLATION
 SCHEDULE FOR STORM PANELS. THESE ITEMS
 ARE REQUIRED AT TIME OF PERMIT OR YOU
 WILL BE REQUIRED TO PULL A SEPARATE
 PERMIT AND PAY ADDITIONAL FEES.
  
 7) PLEASE CHANGE THE CALL SIZE OF THE
 EGRESS WINDOW (I) IN THE WINDOW SCHEDULE
 TO 24-5 SH WHICH CORRESPONDS TO THE
 REVISED DIMENSIONS GIVEN.
  
 8) PLEASE CHANGE NOTE #6 UNDER GENERAL
 NOTES ON A2 TO REFERENCE THE 2001
 FLORIDA PLUMBING CODE.
  
 9) PROVIDE A DETAIL INDICATING ONE HOUR
 FIRE RATING BASED ON BOTH INTERIOR AND
 EXTERIOR FIRE EXPOSURE FOR THE GABLE END
 ON THE ZERO LOT LINE.
  
 10) PLEASE INSERT REVISED PAGES INTO THE
 PLANS AND REMOVE OLD SHEETS. SUBMIT THE
 OLD SHEETS WITH THE NEW PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-05-29 Cont ID  
Sent By rmcdouga Date 2002-05-29 Time 11:03 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-05-29 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) INDICATE THE APPLICABLE INTERNAL
 PRESSURE COEFFICIENT ON THE PLANS AS
 REQUIRED BY 2001 FBC SEC. 1606.1.7.
  
 3) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 4) THE ENERGY CALCULATIONS ARE REQUIRED
 TO BE SIGNED BY THE OWNER/AGENT.
  
 5) PROVIDE SOIL BEARING TEST REPORT PER
 CITY OF WPB AMENDMENTS TO 2001 FBC SEC.
 1804.2.2.
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FRONT DOOR (THE ONE SUBMITTED IS
 LIMITED TO DOORS WITH SIDELITES)
 - STRUCTURAL WINDOW MULLIONS
 - GLASS BLOCK ( NEED SBCCI OR METRO-DADE
 APPROVALS OR SITE SPECIFIC ENGINEERING )
  
 7) THE GLASS BLOCK LOCATED IN THE WALL
 ON THE ZERO LOT LINE IS REQUIRED TO HAVE
 A ONE HOUR FIRE RATING.
  
 8)PROVIDE A KEY PLAN AND AN INSTALLATION
 SCHEDULE FOR THE STORM PANELS. INDICATE
 THE TYPE OF FASTENERS THAT WILL BE USED.
  
 9) SHEET A2 MAKES REFERENCES TO SEVERAL
 CODES THAT WERE REPLACED BY THE FLORIDA
 BUILDING CODE 2001 EDITION. PLEASE
 UPDATE THESE REFERENCES.
  
 10) THE SH24 WINDOW IN THE SECOND FLOOR
 MASTER SUITE WILL NOT PROVIDE THE 24"
 NET CLEAR OPENING HEIGHT REQUIRED FOR
 EGRESS BY 1005.4.4 OF THE FBC.
  
 11) THE ONE HOUR FIRE RATING OF THE
 EXTERIOR WALL ON THE ZERO LOT LINE MUST
 BE MAINTAINED WHERE THE FLOOR GIRDER
 TRUSS ENTERS THE WALL AS INDICATED ON
 SHEET S1. IF THIS TRUSS DOES NOT
 PENETRATE THE WALL, INDICATE AN
 APPROPRIATE HANGER.
  
 12)THE FOUNDATION PLAN ON S1 INCORRECTLY
 STATES THAT TERMITE TREATMENT IS PER 97
 SBC. PLEASE CORRECT TO 2001 FBC SEC.1816
  
 13) NOTE # 14 ON A5 INDICATES 3"X 24"
 ATTIC VENTS AND THE CALCULATIONS USE
 6"X 24" ATTIC VENTS. PLEASE CORRECT.
  
 14) PLEASE INDICATE THE CONNECTORS THAT
 WILL BE USED TO ANCHOR THE KING HIP
 TRUSSES AT THE BUILDING CORNERS ON SHEET
 S1.
  
 15) PLEASE CLARIFY IF THE COMMON TRUSSES
 ON S1 WILL BE ANCHORED AT EACH END WITH
 TC-5 CONNECTORS.
  
 16) ON SHEET S2 ITEM #3 UNDER "CODE"
 STATES THAT UPLIFT IS DESIGNED IN
 ACCORDANCE WITH SBC CODE 1997 ED. THE
 2001 FBC REQUIRES DESIGN BASED ON
 ASCE 7-98 OR SECTION 1606.2 OF THE 2001
 FBC. PLEASE REVISE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-09 Cont ID  
Sent By sgraham Date 2002-04-09 Time 11:51 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved