Plan Review Details - Permit 02040516
Plan Review Stops For Permit 02040516
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-01 Cont ID  
Sent By dpalmer Date 2002-05-01 Time 06:57 Rev Time 0.00
Received By dpalmer Date 2002-05-01 Time 06:57 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-26 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 06:13 Rev Time 0.00
Received By dpalmer Date 2002-04-26 Time 06:13 Sent To P
Notes
2002-04-26 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT CODE ARTS ARE
 FROM 96 NEC, PLEASE CORRELATE TO THE
 99 NEC.
  
 2)NOTE: PLEASE NOTE MIS PRINT FOR AIC
 RATING. SHOWN AS 22.00? SHOULD SHOW
 22,000.
  
 3 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 4 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS IN NOTES OR
 ON PANEL SCHEDULE. PER 210-12
  
 PLEASE SUBMIT TTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-06 Cont ID  
Sent By pkrauss Date 2002-12-06 Time 10:42 Rev Time 0.25
Received By pkrauss Date 2002-12-06 Time 10:21 Sent To  
Notes
2002-12-06 00:00:00MECH REV PERMIT 02040565

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-22 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 08:15 Rev Time 0.45
Received By pkrauss Date   Time   Sent To  
Notes
2002-06-22 00:00:00PASSED PER H. MOSER 6/22/02

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-24 Cont ID  
Sent By hmoser Date 2002-04-24 Time 19:35 Rev Time 0.33
Received By hmoser Date 2002-04-24 Time 19:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-27 Cont ID  
Sent By dpalmer Date 2002-04-26 Time 06:13 Rev Time 0.33
Received By jleech Date 2002-04-27 Time 12:02 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-07-30 Cont ID  
Sent By rmcdouga Date 2002-07-30 Time 15:42 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-30 00:00:00************BUILDING PROVISO************
  
 1) RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 SUBMIT SOIL BEARING TEST PRIOR TO
 POURING THE FOUNDATION.
  
 4) SUBMIT (2) STORM PANEL INSTALLATION
 SCHEDULES LISTING ALL OF THE OPENINGS
 THAT ARE BEING SHUTTERED. THE ONES THAT
 WERE SUBMITTED ONLY LISTED 7 OF 10
 OPENINGS.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 EVALUATIONS FOR GLASS BLOCK. ONLY PART
 OF THE REPORT WAS SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-06-24 Cont ID  
Sent By rmcdouga Date 2002-06-24 Time 17:01 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-24 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 3) PROVIDE SOIL BEARING TEST REPORT PER
 FBC SEC. 1804.2.2.
  
 4) PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND TESTING INFORMATION FOR ONE HOUR
 FIRE RATED GLASS BLOCK.
  
 5) PROVIDE AN INSTALLATION SCHEDULE FOR
 STORM PANELS OR APPLY UNDER A SEPARATE
 PERMIT AND PAY ADDITIONAL PERMIT FEES.
  
 6) PROVIDE ADDITIONAL COPIES OF PRODUCT
 APPROVALS FOR THE FRONT DOOR AND GLASS
 BLOCK. TWO COPIES OF EACH ARE REQUIRED.
  
 7) PROVIDE A DETAIL OF THE GABLE END ON
 THE ZERO LOT LINE. IT IS REQUIRED TO
 HAVE A ONE HOUR FIRE RATING BASED ON
 BOTH INTERIOR AND EXTERIOR EXPOSURE TO
 FIRE. SEE 2001 FBC TABLE 600 AND NOTE I.
  
 8) PLEASE CHANGE THE CALL SIZE OF THE
 EGRESS WINDOW (I) IN THE WINDOW SCHEDULE
 TO 24-5 SH WHICH CORRESPONDS WITH THE
 REVISED DIMENSION THAT IS GIVEN.
  
 9) PLEASE CHANGE NOTE #6 UNDER GENERAL
 NOTES ON A2 TO REFERENCE THE 2001
 FLORIDA PLUMBING CODE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-05-16 Cont ID  
Sent By rmcdouga Date 2002-05-16 Time 10:11 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-05-16 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) INDICATE THE APPLICABLE INTERNAL
 PRESSURE COEFFICIENT ON THE PLANS AS
 REQUIRED BY 2001 FBC 1606.1.7.
  
 3) THE STRUCTURE IS LOCATED IN AN "A8"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 4) THE ENERGY CALCULATIONS ARE REQUIRED
 TO BE SIGNED BY THE OWNER/AGENT.
  
 5) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE SOIL BEARING TEST REPORT.
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - FRONT DOOR (THE ONE SUBMITTED IS FOR A
 DOOR WITH SIDELITES ONLY AS STATED IN
 THE LIMITATIONS)
 - GLASS BLOCK (INFO SUBMITTED IS NOT
 ACCEPTABLE)
  
 7) THE GLASS BLOCK LOCATED IN THE WALL
 ON THE ZERO LOT LINE IS REQUIRED TO
 HAVE A ONE HOUR FIRE RATING.
  
 8)PROVIDE A KEY PLAN AND AN INSTALLATION
 SCHEDULE FOR STORM PANELS. INDICATE THE
 TYPE OF FASTENERS THAT WILL BE USED.
  
 9) ON SHEET A2 SEVERAL REFERENCES ARE
 MADE TO CODES WHICH HAVE BEEN REPLACED
 BY THE 2001 FLORIDA BUILDING CODE.
 PLEASE CORRECT.
  
 10) THE SH24 WINDOW IN THE SECOND FLOOR
 MASTER SUITE WILL NOT PROVIDE A 24" NET
 CLEAR OPENING HEIGHT REQUIRED FOR EGRESS
 PER 1005.4.4. THE SH34 WINDOWS USED FOR
 EGRESS MUST BE SIZED AS INDICATED IN THE
 WINDOW SCHEDULE IN ORDER TO COMPLY.
  
 11) PLEASE INDICATE THAT THE ANCHORS FOR
 THE WINDOWS AND SLIDING GLASS DOORS ARE
 REQUIRED TO FASTEN THROUGH THE 1X BUCKS
 INTO THE STRUCTURAL SUBSTRATE MATERIAL.
 SEE BUCK DETAILS ON A5.
  
 12) THE ONE HOUR FIRE RATING OF THE
 EXTERIOR WALL ON THE ZERO LOT LINE MUST
 BE MAINTAINED WHERE THE FLOOR GIRDER
 TRUSS ENTERS THE WALL AS INDICATED ON
 SHEET S1. IF THIS TRUSS DOES NOT
 PENETRATE INTO THE WALL, INDICATE AN
 APPROPRIATE HANGER.
  
 13)THE FOUNDATION PLAN ON S1 INCORRECTLY
 STATES THAT TERMITE TREATMENT IS PER
 97SBC. PLEASE CORRECT. SEE 2001FBC 1816.
  
 14) PLEASE INDICATE THE CONNECTORS THAT
 WILL BE USED TO ANCHOR THE KING HIP
 TRUSSES AT THE BUILDING CORNERS ON S1.
  
 15) PLEASE CLARIFY IF THE COMMON TRUSSES
 ON S1 WILL BE ANCHORED AT EACH END WITH
 TC-5 CONNECTORS.
  
 16) ON SHEET S2 ITEM #3 UNDER "CODE"
 STATES THAT UPLIFT IS DESIGNED IN
 ACCORDANCE WITH SBC CODE 1997 ED. THE
 2001 FBC REQUIRES DESIGN BASED ON
 ASCE 7-98 OR SECTION 1606.2 OF THE 2001
 FBC. PLEASE REVISE.
  
 PLEASE MAKE CORRECTIONS TO UPDATE THE
 MASTER CAD DRAWING SO THAT FUTURE PLANS
 SUBMITTED FOR PERMIT WILL BE CORRECT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-09 Cont ID  
Sent By sgraham Date 2002-04-09 Time 11:49 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***