Plan Review Details - Permit 02040506
Plan Review Stops For Permit 02040506
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-10-21 Cont ID  
Sent By lmartine Date 2004-10-21 Time 15:25 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-08-30 Cont ID  
Sent By lmartine Date 2002-08-30 Time 15:47 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-07-16 Cont ID  
Sent By btrobaug Date 2002-08-21 Time 11:30 Rev Time 0.00
Received By jgomez Date 2002-07-15 Time 17:23 Sent To  
Notes
2002-07-15 00:00:00SECOND CHECKLIST:
 1-PROVIDE COMPLETE DETAILS AND SPECS FOR
 STAIRS, RAILINGS AND GUARDRAILS. SEE
 SECTIONS 1007, 1015 & 1608.2 FBC 2001.
 **NOTE : INCLUDE RAILING AT SUNDECK.
 2-SPIRAL STAIRS SHEET TO BE SIGNED,
 SEALED AND DATED BY THE ENGINEER OF
 HEDJ ENGINEERING WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES.
 3-PROVIDE ON PLANS THE MIN. STRUCTURAL
 INFORMATION REQUIRED BY SECTION
 1606.1.7 FBC 2001.
 4-CLARIFY EGRESS WINDOW #3 AT MASTER
 BEDROOM. EXTERIOR ELEVATION SHOWS A
 VERTICAL MULLION IN THE MIDDLE OF THE
 WINDOW. IF SO, THEN CLEAR OPENING DOES
 NOT COMPLY WITH SEC. 1005.4.4 FBC 2001
 5-DRAWINGS AND SPECIFICATIONS REFERENCE
 ARCHITECT AND ENGINEER THROUGHOUT.
 NEED ARCHITECT AND ENGINEER TO SIGN,
 SEAL, DATE AND PROVIDE ALL HIS/HER
 INFORMATION AS REQUIRED BY CHAPTER 471
 FL. STATUTES WHEN SUBMITTING INFO.
 FOR PUBLIC RECORDS.
 6-AREA CALCULATIONS ARE WRONG. REVISE.
 7-PROVIDE COMPLETE SECTIONS, DETAILS &
 SPECIFICATIONS AT SUNDECK. SEE
 COMMENTS ON PLANS.
 8-CLEARLY SPECIFY ATTIC VENTILATION AS
 REQUIRED BY SEC. 2309.6 FBC 2001.
 **NOTE: THERE IS A CONFLICT WITH THE
 BLOCKING SPECIFIED AND VENTILATION.
 SEE DETAIL 6 OF S-1.
 9-IF GETTING CREDIT ON THE ENERGY CALCS
 FOR CEILING FANS, THEN, SPECIFIED SIZE
 AND NUMBER OF FANS REQUIRED BY TABLE
 6-6 CHAPTER 13 FBC 2001.
 10-PROVIDE PRODUCT APPROVAL FOR STORM
 SHUTTERS AND COMPLETE KEY PLAN AND
 INSTALLATION SCHEDULE. SEE CITY SAMPLE
 11-PROVIDE COMPLETE FRAMING DETAILS FOR
 SKYLIGHT. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 12-PROVIDE SOIL TEST REPORT SIGNED AND
 SEALED BY THE RESPECTIVE ENGINEER.
 13-DRAW GUARDRAIL DETAIL TO SCALE.
 RAILING DETAIL ON SHEET A-9 WON'T
 WORK FOR THE 4" MAX. SPHERE TO PASS
 THRU AS REQUIRED BY SEC. 1015 FBC 2001

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-17 Cont ID  
Sent By jgomez Date 2002-05-17 Time 14:24 Rev Time 4.00
Received By jgomez Date 2002-05-17 Time 14:24 Sent To  
Notes
2002-05-17 00:00:00CHECKLIST:
 1-A)ARCHITECT TO SIGN, SEAL AND DATE
 ALL DWGS & PROVIDE ALL HIS INFORMATION
 (EG: LIC #, ETC) AS REQUIRED BY FL.
 STATUTES CHAPTER 481. NOTE: SPECS TOO
 B)ENGINEER TO SIGN, SEAL AND DATE ALL
 DWGS & PROVIDE ALL HIS INFORMATION AS
 REQ'D FL ST CHAPTER 471. (SPECS TOO)
 2-AFTER CORRECTIONS ARE DONE TO ALL
 ORIGINAL DRAWINGS TAKE THEM TO PALM
 BEACH COUNTY TO PAY THE IMPACT FEES.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
 3-AREA CALCULATIONS ON DWG A-2 ARE WRONG
 SEE FLOOR PLANS AND REVISE AS REQUIRED
 TO PROPERLY ASSESS THE IMPACT, RADON
 AND VALUE FEES.
 4-PROVIDE COMPLETE DETAILS AND SPECS FOR
 STAIRS, RAILINGS AND GUARDRAILS. SEE
 SECTIONS 1007, 1015 & 1608.2 FBC 2001.
 **NOTE: INCLUDES RAILING AT SUNDECK.
 5-SPECIFY COMPLETE SIZE AND SPECS FOR
 SPIRAL STAIRS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 6-CLEARLY SPECIFY WINDOWS TO BE REPLACED
 AND SPECIFY TYPE AND SIZE IN ORDER TO
 VERIFY FOR COMPLIANCE WITH EGRESS
 REQUIREMENTS SEC. 1OO5.4 FBC 2001.
 WINDOW SCHEDULE DON'T MATCH PLANS.
 7-PROVIDE ALL INFORMATION ON DRAWINGS AS
 REQUIRED ON SECTION 1606.1.7.
 8-NEW SUNDECK WAS THE ROOF ABOVE GARAGE.
 ENGINEER TO CERTIFY IF EXISTING FRAM'G
 WILL BE ABLE TO SUPPORT THE NEW LOADS
 OR IF REINFORCEMENT IS NECESSARY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 9-PROVIDE ATTIC ACCESS AT 2ND FL. ROOF.
 SECTION 2309.6 FBC 2001.
 10-DRAW ALL EXTERIOR ELEVATIONS. SEE
 SEC. 104.3.1.1 CITY AMENDMENTS TO FBC.
 11-SPECIFY ATTIC VENTILATION. SEC 2309.7
 FBC 2001.
 **NOTE: SEE DETAIL 6 OF S-1 REGARDING
 THE BLOCKING TO AVOID A CONFLICT.
 12-UPDATE WINDOW AND DOOR BUCK DETAIL
 AND SPECS TO COMPLY WITH SECTION
 1707.4.4.2 FBC 2001.
 13-IF GETTING CREDIT ON THE ENERGY CALCS
 FOR CEILING FANS, THEN, SPECIFY SIZES
 AND LOCATIONS. SEE TABLE 6-6 CHAPTER
 13 FBC 2001.
 14-PROVIDE PRODUCT APPROVAL FOR:
 A)CASEMENT WINDOW PRODUCT APPROVAL DWGS
 ARE NOT LEGIBLE.
 B)STORM SHUTTERS WITH COMPLETE KEY PLAN
 AND INSTALLATION SCHEDULE SHOWING
 ANCHOR TYPE AND SPACING TO BE USED.
 C)SKYLIGHTS
 D)OCTAGONAL WINDOW
 E)GARAGE DOOR IF IT WILL BE REPLACED.
 F)PROVIDE SPECS/SHOP DRAWINGS FOR SPIRAL
 STAIRS.
 15-PROVIDE COMPLETE FRAMING DETAILS FOR
 ROOF SKYLIGHTS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 16-SEE COMMENTS ON REVIEWED PLAN AND
 PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS AND SPECS TO EXPEDITE THE
 REVIEW PROCESS.
 17-PROVIDE COMPLETE SECTION DETAIL AND
 SPECS FOR NEW SUNDECK.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-08-21 Cont ID  
Sent By btrobaug Date 2002-08-21 Time 11:30 Rev Time 0.00
Received By btrobaug Date 2002-08-21 Time 10:59 Sent To B
Notes
2002-08-21 00:00:00GAVE PLANS TO LUIS./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-06-28 Cont ID  
Sent By btrobaug Date 2002-06-28 Time 08:36 Rev Time 0.00
Received By btrobaug Date 2002-06-28 Time 06:44 Sent To P
Notes
2002-06-28 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS,AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE LOAD CALCULATIONS FOR ALL
 ADDITIONAL LOADS PER 220-3(C) NEC.
  
 2} NOTE:BATH,WET BAR,AND OUSIDE
 RECEPTACLES TO BE GFI PER
 210-8(A)(1),(3),&(7).PLEASE INDICATE
 SAME ON PLANS.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PLAN PER
 210-12
  
 4} CLOSET IN THE MASTER BEDROOM SHOWS AN
 A/C UNIT,THE DISCONNECT MUST COMPLY
 WITH 110-26,PLEASE SHOW LOCATION ON
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-04-25 Cont ID  
Sent By dpalmer Date 2002-04-25 Time 07:28 Rev Time 0.00
Received By dpalmer Date 2002-04-25 Time 07:27 Sent To  
Notes
2002-04-25 00:00:00NO ELECTRICAL ON PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-07-06 Cont ID  
Sent By hmoser Date 2002-07-06 Time 08:46 Rev Time 0.50
Received By hmoser Date 2002-07-06 Time 08:45 Sent To  
Notes
2002-07-06 00:00:00MECHANICAL CONTRACTOR NEEDS TO SUBMIT
 PLANS,ENERGY CALCS,MANUAL J FOR PERMIT.
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-06 Cont ID  
Sent By jleech Date 2002-07-06 Time 09:51 Rev Time 0.25
Received By jleech Date 2002-07-06 Time 09:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-07-02 Cont ID  
Sent By btrobaug Date 2002-06-28 Time 09:04 Rev Time 0.25
Received By jleech Date 2002-07-02 Time 18:43 Sent To  
Notes
2002-07-02 00:00:00NO RISER DIAGRAM SHOWN FOR 2ND FLOOR
 ADDITION.

Review Stop Z ZONING
Rev No 2 Status P Date 2002-04-24 Cont ID  
Sent By sgraham Date 2002-04-24 Time 16:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-04-18 Cont ID  
Sent By sgraham Date 2002-04-18 Time 10:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-04-18 00:00:00NEED SURVERY