Plan Review Details - Permit 02040494
Plan Review Stops For Permit 02040494
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-07-31 Cont ID  
Sent By lmartine Date 2002-07-31 Time 07:34 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-07-12 Cont ID  
Sent By lmartine Date 2002-07-12 Time 13:58 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-07-12 00:00:00 
 NOT APPROVED
  
 1]
 THE WRONG BUILDING CODE IS NOTED UNDER
 THE WIND CRITERIA.
  
 2]
 PLEASE SPECIFY WHICH ROOF COVER WILL BE
 USED, PLAN CALLS FOR TWO DIFFERENT
 KINDS.
  
 3]
 ROOF FRAMING, 2X4 RAFTERS MAXIMUM SPAN
 IS 7'5", PLAN NOT IN COMPLIANCE.
  
 4]
 CLARIFY RIDGE BEAM, 2X6 OR 2X8.
  
 5]
 DESIGNER SHALL NOTE ON PLAN THAT THE
 COVERED TERRACE WILL NOT BE ATTACHED TO
 EXISTING STRUCURES.
  
  
 LUIS MARTINEZ
 659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-23 Cont ID  
Sent By lsmith Date 2002-04-23 Time 11:22 Rev Time 0.75
Received By lmartine Date   Time   Sent To  
Notes
2002-04-23 00:00:00***************PROVISO*****************
  
 1. NEED PRODUCT APPROVALS FOR ROOF MATER
 IALS
  
 2. 2/12 SLOPE REQUIRES 2 LAYERS UNDERLAY
 MENT PER FBC 2001 SEC. 1507.3.8
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394
 3]
 RE-ENGINEER 2X4 STRUCTURAL ROOF FRAMING
 TO INCLUDE RIDGE BEAM, 2X RAFTERS, 2X
 COLLAR TIES, AND 2X PERIMETER BEAM
 INCLUDE SIZE OF WOOD, NAILING. ROOF
 DECK TO BE SOLID SHEATHING 5/8 CDX
 MINIMUM.
 4]
 ZONING REQUIRES A MINIMUM OF 5' SEBACK
 SIDE AND REAR FOR ALL STRUCTURES.
 5]
 COMPLETE ELECTRICAL INFORMATION IS
 REQUIRED FOR SEPERATE PERMIT
 6]
 PROVIDE DETAILS FOR FOUNDATION.
  
 L. MARTINEZ
 659-8096
 #8456