Plan Review Details - Permit 02040434
Plan Review Stops For Permit 02040434
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-07-24 Cont ID  
Sent By rmcdouga Date 2002-07-24 Time 12:45 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-24 00:00:00BUILDING PROVISO
  
 1) PROVIDE (2) CURRENT COPIES OF
 PRODUCT APPROVALS FOR AWNING WINDOWS.
 THE ONES SUBMITTED WERE EXPIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-06-21 Cont ID  
Sent By pkrauss Date 2002-06-21 Time 16:25 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-21 00:00:00BUILDING DENIED
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALC. FORM. AN ADDITIONAL
 COPY IS REQUIRED.
  
 2) PROVIDE DETAILS FOR THE ATTACHMENT OF
 THE WINDOW AND DOOR BUCKS TO THE
 STRUCTURE. INDICATE THE FASTENER TYPE,
 SIZE, SPACING AND EMBEDMENT. PER FBC
 SEC. 1707.4.4.2
  
 3) INDICATE ON THE PLANS THAT TERMITE
 PROTECTION WILL BE PROVIDED PER FBC
 SEC. 1816.
  
 4) THE WOOD USED FOR THE SCREENED PORCH
 SHALL BE APPROVED PRESERVATIVE TREATED
 WOOD SUITABLE FOR GROUND CONTACT. SEE
 FBC SECTION 2304. PLEASE INDCATE ON THE
 PLANS.
  
 5) THE STRUCTURAL ENGINEER WHOSE TITLE
 BLOCK IS ON SHEET 3 IS REQUIRED TO SIGN
 AND SEAL THE STRUCTURAL PAGES OF THE
 PLANS.
  
 6) PLEASE CLARIFY NOTE # 8 ON SHEET 3.
 THE INTERNAL PRESSURE COEFFICIENTS,GCPI
 FOR AN ENCLOSED BUILDING USING THE
 SIMPLIFIED METHOD IS + 0.18 AND - 0.18.
  
 7) NOTE #9 ON SHEET 3, STATES THAT THE
 OPENINGS ARE TO BE IMPACT RESISTANT.
 PLEASE CLARIFY. THE PRODUCT APPROVALS
 SUBMITTED INDICATE NON-IMPACT RESISTANT
 GLAZING AND STORM PANELS.
  
 8) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS (2 COPIES)
  
 9)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - SINGLE HUNG WINDOW
 - EXTERIOR INSWING DOOR AT UTILITY ROOM
  
 10) THE POSITIVE OPENING PRESSURE LISTED
 ON THE PLANS EXCEEDS THE POSITIVE DESIGN
 PRESSURE IN THE PRODUCT APPROVAL FOR THE
 AWNING WINDOWS. (PLAN HAS +38.3 AND THE
 PRODUCT APPROVAL IS RATED FOR +36.7)
  
 11) THE GLASS BLOCK OPENINGS WHICH ARE
 BOTH IN HAZARDOUS LOCATIONS ARE REQUIRED
 TO HAVE A MINIMUM FACE THICKNESS OF 0.25
 INCH.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-26 Cont ID  
Sent By btrobaug Date 2002-06-20 Time 13:01 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-04-26 00:00:00BUILDING DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE 2001 FBC SECTION 1606.1.7
 REQUIRES THE FOLLOWING INFORMATION TO BE
 SHOWN ON THE CONSTRUCTION DRAWINGS:
 - BASIC WIND SPEED, MPH.
 - WIND IMPORTANCE FACTOR(1) AND BUILDING
 CATEGORY.
 - WIND EXPOSURE- IF MORE THAN ONE WIND
 EXPOSURE IS USED THE WIND EXPOSURE AND
 APPLICABLE WIND DIRECTION SHALL BE
 INDICATED.
 - THE APPLICABLE INTERNAL PRESSURE
 COEFFICIENT
 - COMPONENTS AND CLADDING. THE DESIGN
 WIND PRESSURES IN TERMS OF PSF, TO BE
 USED FOR THE DESIGN OF EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 4) INDICATE THE NEGATIVE AND POSITIVE
 PRESSURES FOR EXTERIOR WINDOW AND DOOR
 OPENINGS ON THE PLANS.
  
 5) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 1997 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR DOORS
 - AWNING WINDOWS
 - GLASS BLOCK
  
 7) PROVIDE PRODUCT APPROVALS FOR ROOFING
 MATERIALS UNDER A SEPARATE PERMIT.
  
 8) PROVIDE EMERGENCY EGRESS WINDOW IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24INCHES,NET CLEAR
 OPENING WIDTH OF 20 INCHES AND NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 INCHES ABOVE
 THE FLOOR. 2001 FBC 1005.4
  
 9) PLEASE REVIEW PLACEMENT OF VERTICAL
 REINFORCEMENT.
  
 10) THE PLANS SUBMITTED INDICATE AN
 EXISTING CARPORT WITH EXISTING COLUMNS.
 HOWEVEVER, IT IS NOT SPECIFIED THAT THE
 COLUMNS ARE CONCRETE OR IF THEIR IS AN
 EXISTING CONCRETE TIE BEAM OR WOOD
 GIRDERS SUPPORTING THE EXISTING ROOF
 SYSTEM. PLEASE CLARIFY.
  
 11) PLEASE REVIEW THE SPACING OF THE
 VERTICAL REINFORCEMENT IN THE NEW BLOCK
 WALLS. THERE ARE NONE AT EACH SIDE OF
 THE WINDOW AND DOOR OPENINGS FOR BUCK
 ATTACHMENT. PLEASE INDICATE THE SPACING
 BETWEEN THE VERTICAL REINFORCEMENTS ON
 THE PLANS.
  
 12) PROVIDE FASTENING DETAILS FOR DOOR
 AND WINDOW BUCKS.
  
 13)PLEASE PROVIDE ADDITIONAL INFORMATION
 INDICATING THE CONSTRUCTION OF THE
 EXISTING COVERED PORCH. INDICATE HOW THE
 CONTINOUS LOAD PATH FROM FOUNDATION TO
 THE ROOF IS ACHIEVED.
  
 14) PROVIDE A ROOF FRAMING LAYOUT PLAN
 FOR THE AREA THAT DOES NOT HAVE AN EXIST
 ING ROOF.
  
 15) PROVIDE ELEVATION DIMENSIONS ON THE
 PLANS INDICATING BEAM HEIGHTS, CEILING
 HEIGHTS, FLOOR ELEVATION ABOVE GRADE,
 ETC.
  
 16) INDICATE ON PLANS THAT SOIL IS TO BE
 TREATED FOR TERMITES.
  
 17)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS. MISSLE
 IMPACT PROTECTION IS REQUIRED FOR ALL
 NEW EXTERIOR GLAZED OPENINGS.
  
 18) INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES AT ALL EXTERIOR OPENINGS ON
 THE PLANS.
  
 19) THE ENCLOSED AREA AND ADDITION CAN
 NOT PREVENT THE REQUIRED EMERGENCY
 EGRESS TO THE EXTERIOR FROM A ROOM USED
 FOR SLEEPING OR ENCLOSE A BATHROOM
 WINDOW WHEN IT IS REQUIRED FOR
 VENTILATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-20 Cont ID  
Sent By btrobaug Date 2002-06-20 Time 13:01 Rev Time 0.00
Received By btrobaug Date 2002-06-20 Time 12:01 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-10 Cont ID  
Sent By btrobaug Date 2002-04-10 Time 15:22 Rev Time 0.00
Received By btrobaug Date 2002-04-10 Time 15:18 Sent To B
Notes
2002-04-10 00:00:00**************** UNSAT!*****************
  
 1} PLEASE PROVIDE LOAD CALCULATIONS PER
 ARTICLE 220-3(C)(1).
  
 2} SMOKE DETECTORS ARE REQUIRED PER
 NFPA-72.INSIDE AND OUT OF GARAGE
 ENCLOSURE.
  
 3} PLEASE INDICATE THE SIZE OF THE NEW
 JUNCTION BOX SHOWN ON THE OUTSIDE OF
 THE GARAGE AND THE SIZE & NUMBER OF
 CONDUCTORS IT CONTAINS.
  
 4} SHOW TYPE & SIZE OF CONDUIT TO THE
 PANEL FROM THE JUNCTION BOX,AND TYPE &
 SIZE OF WIRING IT CONTAINS,ALONG WITH
 THE NUMBER OF CONDUCTORS.
  
 5} PLEASE SUBMIT A DRAWING SHOWING THE
 NEW PANEL WITH IT'S AMPERAGE
 RATING,MEANS OF DISCONNECT,AND
 RISER,INCLUDING SIZE AND TYPE OF
 SERVICE CONDUCTORS AND ASSOCIATED
 FEEDERS.ALSO THE GROUNDING SYSTEM BEING
 USED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-10-17 Cont ID  
Sent By pkrauss Date 2002-10-17 Time 15:56 Rev Time 0.00
Received By pkrauss Date 2002-10-17 Time 15:56 Sent To  
Notes
2002-10-17 00:00:00MECH PERMIT 02090876 - R/A REQUIRED FROM
 BEDROOM

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-21 Cont ID  
Sent By pkrauss Date 2002-06-21 Time 16:24 Rev Time 0.35
Received By pkrauss Date 2002-06-21 Time 16:24 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-04-21 Cont ID  
Sent By lmartine Date 2002-04-21 Time 12:09 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-04-21 00:00:00NO INFORMATION PROVIDED

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-04-21 Cont ID  
Sent By lmartine Date 2002-04-21 Time 12:08 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-04-21 00:00:00NO INFORMATION PROVIDED

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-08 Cont ID  
Sent By sgraham Date 2002-04-08 Time 12:43 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***