Plan Review Details - Permit 02040253
Plan Review Stops For Permit 02040253
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2002-04-13 Cont ID  
Sent By dlauderm Date 2002-04-13 Time 11:40 Rev Time 1.00
Received By dlauderm Date 2002-04-13 Time 11:22 Sent To  
Notes
2002-04-13 00:00:00APPROVED AS NOTED:
 1.WRAPID SEAL ONLY REQUIRED ON REHABED
 MANHOLES, NOT NEW.
 2.NO FRAME AND COVER DETAIL SHOWN FOR
 NEW MANHOLE. MUST BE "CITY DETAIL" WITH
 OUT CITY NAME ON IT (REVIEW DETAIL)
 3.AS-BUILTS MUST BE SUPPLIED TO THE
 ENGINEERING SERVICES DIVISION OF THE
 CITY, MYLAR, PAPER AND ELECTRONIC COPY.
 4. CERTIFYING ENGINEER MUST WITNESS THE
 WORK AND CERTIFY IT TO THE CITY
 ENGINEERING SERVICES DIVISION AS WELL AS
 THE CONSTRUCTION SERVICES DEPARTMENT.
 5.WARNING: PLAN DOES NOT SHOW EXISTING
 UTILITIES.THERE IS A 6 OR 8" FIRE LINE
 AS WELL AS DRINKING WATER LINES.
 CONTACT THE PALM BEACH COUNTY FACILITIES
 DEPARTMENT TO SEE IF THEY HAVE ANY
 RECORDS BEFORE DIGGING. YOU ARE DEALING
 WITH A HOSPITAL SITUATION WITH UNDER-
 GROUND GAS LINES AS WELL.
 6. IT IS THE ENGINEER OF RECORDS
 RESPONSIBILITY TO CHECK WITH DEP TO SEE
 IT A PERMIT IS REQUIRED FOR THIS WORK.
 7. AS-BUILT DATA WILL NEED TO BE
 SURVEYED AND BASED ON STATE PLAIN
 COORDIANTES. THE EASTERN MANHOLE IS NOT
 SHOWN IN THE ACTUAL LOCATION. ALL
 EXISTING UTILITIES THAT CROSS THIS MAIN
 NEED TO BE SHOWN ON THE AS-BUILT.
 8. DEAN LAUDERMILK, UTILITIES PROJECT
 COODINATOR CAN BE CONTACTED AT 561-
 659-8040 CONCERNING THESE COMMENTS.
 9. HOW WILL EXISTING SANITARY SERVICE
 BE MAINTAINED WHILE NEW LINE IS INSTALL-
 ED?WILL IT BE BYPASSED PUNPED TO
 MANHOLE IN AUSTRALIAN? IF SO A CITY AND
 COUNTY ROW PERMIT WILL BE REQUIRED.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved