Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-09 Cont ID  
Sent By pkrauss Date 2002-04-08 Time 09:56 Rev Time 0.35
Received By pkrauss Date   Time   Sent To  
Notes
2002-04-08 00:00:002001 FLORIDA BUILDING CODE, MECHANICAL
  
 PROVISO:
  
 INDICATE ROOF ACCESS FOR EQUIPMENT. AS
 PER 2001 FBC, MECHANICAL 306.5, WHERE
 EQUIPMENT REQUIRING ACCESS ARE
 INSTALLED ON ROOFS AT A HEIGHT
 EXCEEDING 16 FT, SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS
 OF ACCESS.SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRUASS AT 659-8096
 EXT. 8388.