Plan Review Details - Permit 02040248
| Plan Review Stops For Permit 02040248 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-04-30 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-04-30 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-04-30 |
Time |
16:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-04-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-08 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-04-09 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2002-04-09 00:00:00 | A) NO PRODUCT APPROVALS SUBMITTED FOR | | | TWO HOUR FIREWRAP SHOWN ON THE | | | DRAWINGS. | | | B) EXHAUST OUTLETS ARE TO BE AT LEAST | | | TEN FEET FROM OTHER BUILDINGS OR | | | PROPERTY LINES. | | | C) ADDITIONAL PERMIT REQUIRED FOR | | | REQUIRED FIRE SUPPRESSION SYSTEM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-04-30 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-04-30 |
Time |
13:28 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2002-04-30 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2002-04-30 00:00:00 | 1) EXHAUST OUTLETS TO BE MINIMUM 10' | | | FROM ADJACENT BUILDINGS,PROPERTY LINES | | | OR PARKING LOTS | | | 2) ADDITIONAL PERMIT REQUIRED FOR | | | SUPPRESSION SYSTEM |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-04-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-08 |
Time |
10:24 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-04-08 |
Time |
10:24 |
Sent To |
FIRE |
|
| Notes |
| 2002-04-08 00:00:00 | 2001 FLORIDA BUILDING CODE, MECHANICAL | | | NFPA 96 | | | | | | 1.PROVIDE MANUFACTURER SUBMITTAL DATA | | | & INSTALLATION INSTRUCTIONS FOR THE | | | 2 HR FIRE BLANKET. | | | | | | 2.SHOW COMPLIANCE WITH 2001 FBC, MECH | | | 508.1.1. | | | | | | 3.EXHAUST OUTLETS SHALL BE LOCATED NOT | | | LESS THAN 10 FT FROM PARTS OF THE | | | SAME OR CONTIGUOUS BUILDINGS, | | | ADJACENT PROPERTY LINES & AIR INTAKE | | | | | | 4.ADDITIONAL PERMIT REQUIRED FOR FIRE | | | SUPRESSION. | | | | | | 5.PROVIDE SUBMITTAL FOR THE DISHWASHER | | | HOOD. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|