Plan Review Details - Permit 02040245
Plan Review Stops For Permit 02040245
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-07 Cont ID  
Sent By btrobaug Date 2002-06-07 Time 08:31 Rev Time 0.00
Received By btrobaug Date 2002-06-07 Time 08:24 Sent To Z
Notes
2002-06-07 00:00:00PROVISO
 ~~~~~~~
 1} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.(ON PANEL SCHED.)
  
 2} THE #6 EQUIPMENT GROUND SHOWN BETWEEN
 THE METER AND THE FIRST MEANS OF
 DISCONNECT WOULD CAUSE A PARALLEL PATH
 TO GROUND WITH THE GROUNDED CONDUCTOR
 (NEUTRAL).DO NOT INSTALL AND REMOVE
 FROM AS BUILTS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-17 Cont ID  
Sent By btrobaug Date 2002-04-17 Time 15:00 Rev Time 0.00
Received By btrobaug Date 2002-04-09 Time 07:50 Sent To P
Notes
2002-04-09 00:00:00****************** UNSAT! **************
  
 PLEASE NOTE THE FOLLOWING AND RESUBMIT
 FOR REVIEW ;
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE REDRAW THE SERVICE GROUNDING
 SYSTEM TO COMPLY WITH 250-50.
  
 3} THE GFI IN "HIS" BATH IS NOT
 SHOWN.PLEASE INCLUDE PER 210-52(D) &
 210-11(3).
  
 4} NOTE;BEDROOMS TO COMPLY WITH 210-12.
  
 5} PLEASE RECHECK THE LOAD CALCULATIONS
 AND MAKE ANY CHANGES NECESSARY.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-11-14 Cont ID  
Sent By hmoser Date 2002-11-14 Time 17:23 Rev Time 0.50
Received By hmoser Date 2002-11-14 Time 17:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-13 Cont ID  
Sent By hmoser Date 2002-04-13 Time 08:47 Rev Time 0.50
Received By hmoser Date 2002-04-13 Time 08:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-16 Cont ID  
Sent By kstevens Date 2003-01-16 Time 09:13 Rev Time 0.50
Received By kstevens Date 2003-01-16 Time 09:12 Sent To  
Notes
2003-01-16 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-11 Cont ID  
Sent By btrobaug Date 2002-04-17 Time 15:00 Rev Time 0.33
Received By jleech Date 2002-04-11 Time 14:16 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-06-12 Cont ID  
Sent By rmcdouga Date 2002-06-12 Time 15:41 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-12 00:00:00************BUILDING PROVISO************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) A SEPARATE PERMIT WITH ADDITIONAL
 FEES WILL BE REQUIRED FOR THE STORM
 PANELS. TWO COPIES OF PRODUCT APPROVALS,
 INSTALLATION SCHEDULE AND KEY PLAN WILL
 BE REQUIRED WITH APPLICATION.
  
 3) PROVIDE ENGINEERED CUT SHEETS FROM
 THE TRUSS MANUFACTURER FOR THE CHIMNEY
 SHOWN ON DETAIL 1 ON SHEET A9 PRIOR TO
 INSTALLATION. INDICATE THE APPROPRIATE
 CONNECTORS TO RESIST WINDLOADS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-04-23 Cont ID  
Sent By btrobaug Date 2002-06-07 Time 08:32 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-04-23 00:00:00*************BUILDING UNSAT*************
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE SOIL TEST PER SEC. 1804.2.2
 OF CITY AMENDMENTS TO THE 2001 FBC.
  
 3) PLEASE SPECIFY THE AMOUNT OF EMBED
 REQUIRED FOR THE 5/8" DIA. BOLTS AT THE
 C11 STEEL COLUMN BASES. SEE SCHEDULE ON
 A2.
  
 4) SAFETY GLAZING IS REQUIRED WITHIN 3'
 OF TUB/SHOWER ENCLOSURES PER 2001 FBC
 SECTION 2405.2.1(2). PLEASE INDICATE ON
 PLANS THAT THE BUTT GLASS AT HER BATH
 AND THE 2040 SH WINDOW IN HIS BATH WILL
 BE TEMPERED.
  
 5)THE ENGINEER WHOSE TITLE BLOCK APPEARS
 ON SHEETS A2,A3,A4,A5,A6 AND A7 IS
 REQUIRED TO SIGN, SEAL AND DATE THESE
 SHEETS.
  
 6) PROVIDE EMERGENCY EGRESS WINDOW IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24INCHES,NET CLEAR
 OPENING WIDTH OF 20 INCHES AND NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 INCHES ABOVE
 THE FLOOR. 2001 FBC 1005.4
 PLEASE NOTE THAT THE 2650 CASEMENT
 WINDOWS IN BEDROOMS #2 AND #3 DO NOT
 COMPLY. THE LIBRARY WHICH COULD BE USED
 AS A SLEEPING ROOM MUST HAVE EGRESS
 WINDOWS OR IT MUST BE PERMANENTLY NOTED
 ON THE PLANS THAT THIS ROOM IS NOT TO BE
 USED FOR SLEEPING PURPOSES.
  
 8) PLEASE NOTE THE SIZE OF THE T-NAILS
 USED TO FASTEN THE 1X4 P.T. WINDOW AND
 SLIDING GLASS DOOR BUCKS.
  
 9) PLEASE CLARIFY THE B AND D MARKS ON
 A3 WHICH APPEAR TO BE POSITIVE AND
 NEGATIVE PRESSURES. HOWEVER,THEY DO NOT
 COINCIDE WITH THE WIND PRESSURES
 ASSIGNED TO B AND D ON A5.
  
 10)PROVIDE MANUFACTURER'S SPECIFICATIONS
 AND UL LISTING FOR BBQ ON THE COVERED
 PORCH AND THE PREFAB FIREPLACE AND
 FLUE PIPE.
  
 11) DETAILS 21 & 22 ON A8 FOR THE STEEL
 COLUMN BASES DO NOT CORRESPOND WITH THE
 STEEL COLUMNS LISTED IN THE COLUMN
 SCHEDULE ON A2. PLEASE REVISE.
  
 12) PROVIDE ENGINEERED CUT SHEETS FROM
 THE TRUSS MANUFACTURER FOR THE CHIMNEY
 SHOWN ON DETAIL 1 SHEET A9 PRIOR TO
 INSTALLING. INDICATE APPROPRIATE
 CONNECTORS TO RESIST WINDLOADS.
  
 13) THE TOTAL THICKNESS OF THE STUCCO ON
 THE EXTERIOR OF THE CHIMNEY IS REQUIRED
 TO BE 7/8" THICK PER 2001 FBC SECTION
 2504.2.1 AND ASTM C 926. PLEASE CORRECT
 DETAIL 1 ON A9.
  
 14) THE CONNECTORS SPECIFIED FOR K & L
 IN THE TRUSS ANCHOR SCHEDULE ON A7 AS
 UCS SHOULD BE USC. PLEASE CORRECT.
  
 15) ITEM (I) IN THE WIND LOAD CHART ON
 A7 STATES THAT ALL DOORS, WINDOWS AND
 SKYLIGHTS ARE IMPACT RESISTANT. HOWEVER,
 SOME OF THE PRODUCT APPROVALS DO NOT
 INDICATE IMPACT RESISTANT GLAZING.
 PLEASE CORRECT.
  
 16) ITEM (C) IN THE CHART ON A7 APPEARS
 TO HAVE A TYPO AT MPH. PLEASE CORRECT.
  
 17) PROVIDE (2) COPIES OF KEY PLANS AND
 INSTALLATION SCHEDULES FOR THE STORM
 PANELS. INDICATETHE SPECIFIC ANCHORS
 THAT WILL BE USED FOR STORM PANELS ON
 THE PRODUCT APPROVALS.
  
 18) THE SITE SPECIFIC ENGINEERING FOR
 THE FIXED GLASS, BUTT GLASS AND
 STRUCTURAL MULLIONS ARE REQUIRED TO BE
 REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD FOR THE STRUCTURE. USE THE CITY
 OF WPB PRODUCT APPROVAL FORM TWO COPIES
 FOR EACH ITEM. FORM IS REQUIRED TO BE
 SIGNED AND SEALED BY BOTH THE ENGINEER
 CERTIFYING THE PRODUCT AND THE DESIGNER
 OF RECORD. A LETTER OF APPROVAL SIGNED,
 SEALED AND DATED BY THE DESIGNER OF
 RECORD IS ALSO ACCEPTABLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 2 Status P Date 2002-06-10 Cont ID  
Sent By sgraham Date 2002-06-10 Time 08:14 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-23 Cont ID  
Sent By btrobaug Date 2002-06-07 Time 09:28 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***