Plan Review Details - Permit 02040189
| Plan Review Stops For Permit 02040189 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-05-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-01 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-01 |
Time |
15:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-04-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-04-25 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-04-25 |
Time |
15:37 |
Sent To |
P |
|
| Notes |
| 2002-04-25 00:00:00 | ****************** UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE THAT THE PLANS ARE | | | SHOWING THE 96 NEC CODE ARTS. PLEASE | | | CORRELATE WITH THE 99 NEC. | | | | | | 2)NOTE: PLEASE NOTE THAT PLANS ARE SHOW- | | | ING AIC RATING AT 22.00? MISPRINT? | | | SHOULD SHOW 22,000 | | | | | | 3 )NOTE: PLEASE CLARIFY EQUIPMENT | | | GROUNDING METHOD BETWEEN FIRST MEANS | | | OF DISCONNECT AND PANELS. PLEASE SIZE | | | CONDUCTORS PER 250-122. | | | | | | 4 )NOTE: PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS. PER 210-12 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-11-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-25 |
Time |
12:52 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-11-25 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2002-11-25 00:00:00 | MECH REVISION PERMIT 02040200 | | | REVISED PLANS SUBMITTED ARE "REVERSE" | | | OF APPROVED SET.PLAN INDICATES A 4 TON | | | UNIT WHILE ENERGY & MANUCAL J CALCS | | | REFLECT A 5 TON. PLEASE SUBMIT REVISED | | | CALCS TO COINCIDE WITH PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-04-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2002-04-24 |
Time |
19:14 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2002-04-24 |
Time |
19:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-04-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-04-25 |
Time |
15:40 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2002-04-27 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2002-05-13 |
|
|
Cont ID |
|
| Sent By |
lhatten |
Date |
2002-05-13 |
Time |
18:02 |
Rev Time |
2.50 |
| Received By |
lhatten |
Date |
2002-05-12 |
Time |
18:01 |
Sent To |
|
|
| Notes |
| 2002-05-13 00:00:00 | REVIEW & STAMPED PLANS 05/12/2002 | | | CALC. FEES & PRINT CARDS 05/13/2002 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-04-05 |
|
|
Cont ID |
|
| Sent By |
lhatten |
Date |
2002-04-05 |
Time |
18:03 |
Rev Time |
0.25 |
| Received By |
lhatten |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-13 00:00:00 | OKED PER SHIRLEY GRAHAM 04/05/2002 |
|
|
|