| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-04-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-04-03 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-04-03 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2002-04-03 00:00:00 | ***************** UNSAT! *************** | | | | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATIONAND RESUBMIT FOR REVIEW: | | | | | | 1} PANEL LOCATION TO COMPLY WITH | | | ARTICLE 110-26.ARE THERE TO BE CABINETS | | | IN THE KNEEWALL? PLEASE REDRAW TO | | | CLARIFY. | | | | | | 2} IS THE RELOCATED PANEL MAIN LUG OR | | | MAIN BREAKER? WHERE IS THE MAIN LOCATED? | | | | | | 3} WHAT IS THE RATING OF THE PANEL? | | | | | | 4} PROVIDE CONDUIT AND WIRE SIZE OF THE | | | PANEL FEEDERS,AND INDICATE HOW IT WILL | | | BE REROUTED IF USING EXISTING. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|
|
|