| Plan Review Stops For Permit 02040154 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2005-04-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-06-28 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-04-07 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2005-04-07 00:00:00 | REVISION TO CHANGE STORM PANELS IS OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2003-03-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2003-03-28 |
Time |
11:08 |
Rev Time |
4.00 |
| Received By |
rmcdouga |
Date |
2003-03-28 |
Time |
11:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2003-03-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-03-27 |
Time |
06:31 |
Rev Time |
3.00 |
| Received By |
rmcdouga |
Date |
2003-03-03 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2003-03-03 00:00:00 | BUILDING DENIED | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3) A SEPARATE PERMIT WILL BE REQUIRED | | | FOR THE POOL AND CBS WALL. NOTE: FOOTING | | | FOR WALL CAN NOT EXTEND OVER PROPERTY | | | LINE. | | | | | | 4) SOME OF THE DRAWINGS ARE NOT SIGNED | | | AND SEALED BY THE ENGINEER. | | | | | | 5) THE ENGINEER IS REQUIRED TO DATE THE | | | PLANS AS WELL AS SIGN AND SEAL THEM. | | | | | | 6) THE NEW PLANS DO NOT HAVE SHEETS G1 | | | AND G2. | | | | | | 7) SHEET A1 IS INCORRECTLY DATE 3-18-03. | | | THE OTHERS ARE DATED 3-18-02. | | | | | | 8) PLEASE PUT TOGETHER TWO COMPLETE SETS | | | OF PLANS WITH PRODUCT APPROVALS AND ALL | | | OTHER REQUIRED SUBMITTALS. IF YOU ARE | | | GOING TO SUBMIT THE OLD PLANS AS WELL, | | | THEY NEED TO BE MARKED "OLD PLANS". | | | | | | 9) THE ENERGY CALCULATIONS HAVE | | | INCORRECT INFORMATION LISTED FOR THE | | | EXTERIOR CONCRETE WALL. PLEASE CORRECT. | | | | | | 10) THE DRAWINGS FOR THE OPAQUE STEEL | | | DOORS DO NOT HAVE THE RENEWAL STAMP WITH | | | THE NEW ACCEPTANCE NUMBER. PLEASE SUBMIT | | | THE NEW DRAWINGS. | | | | | | 11) PLEASE SUBMIT SBCCI OR METRO-DADE | | | PRODUCT APPROVALS FOR THE STORM PANELS. | | | THE INFORMATION SUBMITTED IS NOT | | | ACCEPTABLE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-06-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-01 |
Time |
06:52 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-06-20 00:00:00 | BUILDING DENIED | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - STRUCTURAL MULLIONS (THE ONES THAT | | | WERE SUBMITTED WERE EXPIRED) | | | - EXTERIOR SIDE SWING METAL DOOR AT THE | | | GARAGE. | | | | | | 4) INDICATE ON THE PLANS THAT THE GLASS | | | BLOCK IN THE MASTER BATH IS ONE HOUR | | | FIRE RATED. | | | | | | 5) PROVIDE FIRE RATING INFORMATION FROM | | | GLASS BLOCK MANUFACTURER. | | | | | | 6) THE 24SH WINDOWS LABELED EGRESS AT | | | THE MASTER BEDROOM SITTING AREA DO NOT | | | COMPLY WITH THE MINIMUM NET CLEAR | | | OPENING REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE SECTION 1005.4. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-05-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-15 |
Time |
11:57 |
Rev Time |
4.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-09 00:00:00 | BUILDING DENIED | | | | | | 1)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3) PROVIDE STORM PANEL INFORMATION WITH | | | INSTALLATION SCHEDULE AND KEY PLAN WITH | | | SPECIFIC ANCHORS AND MOUNTING TO BE USED | | | FOR ALL NON-IMPACT GLAZING. | | | FBC 1606.1.4. | | | | | | 4) STUCCO THICKNESS ON VERTICAL METAL | | | LATHE IS REQUIRED TO BE 7/8" PER ASTM | | | C 926 AND 2504.2.1 FBC. PLEASE CORRECT | | | WALL SECTIONS B&C ON A10. | | | | | | 5) A CLEARANCE OF 6" IS REQUIRED BETWEEN | | | EXTERIOR WALL COVERINGS AND FINAL GRADE | | | FOR INSPECTION FOR TERMITE INFESTION. | | | 1403.1.6 FBC PLEASE INDICATE ON WALL | | | SECTIONS B&C ON A10. | | | | | | 6) PROVIDE EMERGENCY EGRESS WINDOW IN | | | SLEEPING ROOMS WITH A MINIMUM NET CLEAR | | | OPENING HEIGHT OF 24INCHES,NET CLEAR | | | OPENING WIDTH OF 20 INCHES AND NET CLEAR | | | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR | | | OPENINGS ARE PERMITTED TO HAVE A NET | | | CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT | | | SHALL NOT BE MORE THAN 44 INCHES ABOVE | | | THE FLOOR. 1005.4 FBC & CITY AMENDMENTS | | | THE 24SH WINDOWS IN BR #2 TYPICALLY DO | | | NOT PROVIDE THE REQUIRED OPENING HEIGHT. | | | THE EXISTING WINDOW IN BR #3 MUST COMPLY | | | OR BE REPLACED WITH A WINDOW THAT DOES. | | | | | | 7) INDICATE ATTIC ACCESS IN HOUSE AND | | | DETACHED GARAGE TO COMPLY WITH 2309.6FBC | | | | | | 8) INDICATE THE SIZE OF THE ATTIC VENTS | | | ON A10 AND PROVIDE CALCULATIONS WHICH | | | INDICATE THE TOTAL NET FREE VENTILATING | | | AREA TO CEILING AREA AS REQUIRED BY | | | 2309.7 FBC. | | | | | | 9) INDICATE ON THE PLANS THAT THE WELDED | | | WIRE MESH LISTED IN THE FOUNDATION NOTES | | | ON G1 SHALL BE SUPPORTED IN A MANNER | | | THAT COMPLIES WITH 1909.3 FBC. | | | | | | 10) THE ROOF SHEATHING NAILING DIAGRAM | | | ON A7 SHOULD INDICATE 5'(INCLUDING OVER- | | | HANG) AT THE GABLE END (ZONE 3). CITY | | | AMENDMENTS 2306.1 | | | | | | 11) INDICATE THE POSITIVE AND NEGATIVE | | | PRESSURES ON THE ELEVATIONS FOR ALL NEW | | | WINDOW AND DOOR OPENINGS. | | | | | | 12) THE REAR ELEVATION EXCEEDS TABLE 600 | | | FBC FOR THE PERCENTAGE OF OPENINGS | | | ALLOWED. WALLS WITHIN 3'-10' OF THE | | | PROPERTY LINE ARE ALLOWED TO HAVE 20 % | | | OF THE WALL AREA AS OPENINGS, WHICH IS | | | 52 SQFT. IN THIS CASE. WITH 1 HOUR FIRE | | | RATED GLASS BLOCK IN THE BATHROOM THE | | | REMAINING WINDOW AREA IS 55.3 SQFT. | | | | | | 13) THE OWNER/AGENT IS REQUIRED TO SIGN | | | THE ENERGY CALCULATION FORM. | | | | | | 14) PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - STRUCTURAL MULLIONS | | | - GLASS BLOCK | | | | | | 15) SECTION 1707.4.4.2 OF FBC REQUIRES | | | THAT TAPERED BUCKS EXTEND BEYOND THE | | | INTERIOR FACE OF THE WINDOW OR DOOR | | | FRAME. WHERE BUCK THICKNESS IS LESS THAN | | | 1-1/2" THE WINDOW AND DOOR ASSEMBLIES | | | ARE REQUIRED TO TO BE ANCHORED THROUGH | | | THE BUCKS TO THE STRUCTURAL SUBSTRATE. | | | PLEASE REVIEW THE BUCK DETAILS ON G2 | | | AND REVISE AS NECESSARY. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2005-07-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-12 |
Time |
18:21 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-07-12 |
Time |
18:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2005-06-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-06-21 |
Time |
07:44 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-06-21 |
Time |
07:41 |
Sent To |
M |
|
| Notes |
| 2005-06-21 00:00:00 | ************ UNSAT ************ | | | | | | 1)NOTE: PLEASE INCLUDE ALL LICENSE | | | INFORMATION ON TITLE BLOCK AS REQUIRED | | | UNDER FAC 61G15-23.002 AND FS 471.023 | | | THIS IS REQUIRED ON ALL SHEETS AND ALL | | | TRADES WEATHER OR NOT COMMENT IS MADE BY | | | OTHER REVIEWER(S). | | | | | | 2)NOTE: PLEASE SEE COPY OF SURVEY | | | ATTACHED. THIS IS SUBMITTED FOR A | | | PROPOSED POOL AND DECK. THIS IS REQUIRED | | | TO BE UNDER A SEPARATE PERMIT. PLEASE | | | ALSO SEE ELECTRICAL OVERHEAD LLINES | | | SHOWN SHALL BE INSTALL A MIN OF 10' FROM | | | WATERS EDGE INCLUDING OVERHEAD | | | UTILITIES.680.8 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2003-03-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-03-27 |
Time |
06:30 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-03-27 |
Time |
06:30 |
Sent To |
B |
|
| Notes |
| 2003-03-27 00:00:00 | *** PLANS NOTEDAND REDLINED ***** | | | PLANS DO NOT NEED TO BE REVISED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2003-02-19 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-25 |
Time |
13:57 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-02-19 |
Time |
11:06 |
Sent To |
P |
|
| Notes |
| 2003-02-19 00:00:00 | ************* UNSAT ******************* | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM, NOW | | | A NEW 300A MAIN DISC HAS BEEN ADDED? | | | PLEASE SEE 310-15FOR SIZING OF | | | CONDUCTORS, SHOWN AS 2/0'S WHICH ARE | | | ONLY RATED FOR 200A'S. | | | | | | 2)NOTE: PLEASE SEE 250-66 FOR SIZING OF | | | GROUNDING ELECTRODE PER SEC. | | | | | | 3)NOTE: PLEASE CLARIFY SIZE OF METERCAN | | | IF SERVICE IS GOING TO BE 400A AS SHOWN. | | | | | | | | | 4)NOTE: PLEASE SHOW LOCATIONS OF MAIN | | | DISC'S. MAINS ARE TO BE GROUPED PER | | | 230-72.SHOW ON PLAN. | | | | | | 5)NOTE: RISER ON A-11 SHOWS AN EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN DISC | | | AND METER. PLEASE SEE 250-24, AND REMOVE | | | , ONLY AFTER THE FIRST MEANS OF DISC | | | IS AN EQUIPMENT GROUND INSTALLED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2003-02-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-06 |
Time |
07:17 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-02-06 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2003-02-06 00:00:00 | PLANS/PERMITS HAVE EXPIRED, OVER 7 | | | MONTH-S W/ NO ACTIVITY. PLANS SENT BACK | | | OUT FRONT. SHOULD NOT HAVE COME BACK IN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-06-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-29 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-11 |
Time |
05:52 |
Sent To |
P |
|
| Notes |
| 2002-06-11 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE NOW A RISER DIAGRAM | | | IS BEING SUBMITTED INCLUDING A PANEL | | | FOR GARAGE. | | | PLEASE NOTE PER 230-72 GROUPING OF MAINS | | | AT MAIN SERVICE. MAIN DISC REQ`D AT | | | METER LOCATION TO FEED GARAGE PANEL. | | | PLEASE ALSO NOTE NO CONDUIT/WIRE SIZES | | | AND GROUNDING SHOWN TO OR AT GARAGE | | | PANEL. GARAGE ALSO NEEDS A MAIN DISC IF | | | PANEL HAS MORETHAN 6 SPACES. | | | RECEPT IN GARAGE TO BE GFI 210-8 | | | | | | 2)NOTE: PLEASE NOTE THAT ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO GFI | | | /GFI PROTECTED. PER 210-8-A-6. INCLUDING | | | PENINSULAR. | | | | | | 3)NOTE: PLEASE NOTE BATHROOM STILL | | | MISSING EGRESS LIGHTING PER 210-70 | | | EXIST BATH. | | | | | | 4)NOTE: PLEASE NOTE OUTLET SPACING IN | | | EXISTING BEDROOM AND LIV RM WILL BE REQ` | | | D TO BE BROUGHT UP TO CODE IF EXIST DOES | | | NOT MEET 210-52. ?? | | | | | | 5)NOTE: PLEASE NOTE, JUST AS A NOTE, | | | SEEMS KITCHEN COUNTER AT END MAY BE 12" | | | OR MORE WHICH WOULD REQ` AN OUTLET. | | | 210-52-C-1 | | | | | | PLEASE NOTE THAT MOST NOTES ARE FROM | | | FIRST REVIEW. PLEASE SUBMIT THE ABOVE | | | AND IF THERE ARE ANY QUESTIONS,PLEASE | | | CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | 6)NOTE: PLEASE NOTE ON FIRST SET OF PLAN | | | -S, A RECEPT WAS SHOWN WITHIN 5' OF POOL | | | WHICH IS NOT ALLOWED, THAT WAS REMOVED, | | | HOWEVER ONE IS REQ`D WITHIN 20`. PLEASE | | | SEE 680-6(A). |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-04-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-04-12 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-04-12 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2002-04-12 00:00:00 | **************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT UNLESS THE | | | FEED FROM METER TO PANEL IS UNDERGROUND | | | (SLAB). MORE THAN 8' OF UNPROTECTED | | | CONDUCTORS IS NOT ALLOWED IN BLDG. | | | PLEASE NOTE THAT A MAIN DISC WILL BE | | | REQ`D WITH OCP. | | | | | | 2)NOTE: PLEASE NOTE THAT IF INSTALLING A | | | NEW MAIN DISCONNECT THEN, PLEASE SUBMIT | | | THE AIC RATING FOR NEW MAIN. 110-9 | | | | | | 3)NOTE: PLEASE CLARIFY OUTLETS SHOWN | | | AROUND THE OUTSIDE OF HOUSE. NOT SHOWN | | | ON ELECTRICAL DETAIL ON LEFT? PLEASE | | | SHOW ALL AS GFI/GFI PROTECTED PER 210-8. | | | | | | | | | 4)NOTE: PLEASE NOTE THAT OUTLETS SHOWN | | | AROUND POOL ARE SHOWN CLOSER THAN THE | | | 5' PERMITTED PER 680-6A. | | | | | | 5)NOTE: PLEASE NOTE THAT THERE BATHROOMS | | | THAT DO NOT SHOW GFI OUTLETS REQ`D PER | | | 210-52D PLEASE NOTE THAT 210-8 | | | PLEASE CLARIFY IF EXISITNG? | | | | | | 6) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 7 )NOTE: PLEASE LIST THE REQ`D ARC | | | FAULT PROECTED CIRCUITS ON PANEL | | | SCHEDULE. PER 210-12 | | | | | | 8) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | INCLUDES KITCHEN ISLANDS. | | | | | | 9)NOTE: PLEASE NOTE CIRCUIT SHOWN FOR | | | WALL OVEN IS SHOWN AT 4500W WITH #12? | | | PLEASE CORRECT. | | | | | | 10)NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | MISSINGONE INMASTER BEDROOM. | | | | | | 11)NOTE: PLEASE CLARIFY CIRCUIT WATTAGE | | | FOR COND UNIT. SHOWN W/2P-50 AND ONLY | | | 1200WATTS. | | | | | | 12)NOTE: PLEASE NOTE THAT DISCONNECTING | | | MEANS SHALL BE PROVIDED FOR ALL | | | UNGROUNDED CONDUCTORS THAT SUPPLY OR | | | PASS THROUGH A BLDG/STRUCTURE. | | | PER 225-31. PLEASE ALSO NOTE GROUNDING | | | PER 250-50/250-32 | | | PLEASE NOTE THAT THERE IS NOTHING ON | | | PANEL SCHEDULE ABOUT GARAGE, PLEASE | | | CLARIFY. | | | | | | PLEASE SUBMIT THE ABOVEINFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-07-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-12 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-12 |
Time |
13:57 |
Sent To |
E |
|
| Notes |
| 2005-07-12 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-06-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-10 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-10 |
Time |
16:57 |
Sent To |
E |
|
| Notes |
| 2005-06-10 00:00:00 | TO DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-04-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-01 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-01 |
Time |
15:23 |
Sent To |
B |
|
| Notes |
| 2005-04-01 00:00:00 | TO "RMCDOUGAL" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-03-25 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-25 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-25 |
Time |
13:57 |
Sent To |
E |
|
| Notes |
| 2003-03-25 00:00:00 | TO DP DESK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-06-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-06-28 |
Time |
15:52 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2005-06-28 |
Time |
15:52 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-04-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-15 |
Time |
11:55 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-04-15 |
Time |
11:46 |
Sent To |
B |
|
| Notes |
| 2002-04-15 00:00:00 | O.A. NOT REQUIRED FOR ADDITION.AIR | | | BALANCE OKAY. ADDITION FOR MASTER BEDRM, | | | BATH & GUEST BEDRM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-03-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-06-28 |
Time |
15:53 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-03-01 |
Time |
06:52 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-06-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-19 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-19 |
Time |
18:18 |
Sent To |
|
|
| Notes |
| 2002-06-19 00:00:00 | DENIED | | | RFEFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT A-6, SANITARY RISER DIAGRAM. | | | BIDET MISSING IN BATHROOM. BATHROOMS NOT | | | VENTED PROPERLY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-05-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-11 |
Time |
06:06 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2002-05-02 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2002-05-02 00:00:00 | PAGE A-6 RISER DIAGRAM, W/C NOT VENTED, | | | BIDET IS MISSING AND TUB REQUIRES 3" | | | PIPE TO BE VENTED PROPERLY. SEE TABLE | | | 909.3. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-04-08 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-04-08 |
Time |
12:31 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|