Plan Review Details - Permit 02040154
Plan Review Stops For Permit 02040154
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-04-07 Cont ID  
Sent By pkrauss Date 2005-06-28 Time 15:53 Rev Time 0.00
Received By rmcdouga Date 2005-04-07 Time 07:07 Sent To  
Notes
2005-04-07 00:00:00REVISION TO CHANGE STORM PANELS IS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-03-28 Cont ID  
Sent By rmcdouga Date 2003-03-28 Time 11:08 Rev Time 4.00
Received By rmcdouga Date 2003-03-28 Time 11:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-03-28 Cont ID  
Sent By dpalmer Date 2003-03-27 Time 06:31 Rev Time 3.00
Received By rmcdouga Date 2003-03-03 Time 13:48 Sent To  
Notes
2003-03-03 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE POOL AND CBS WALL. NOTE: FOOTING
 FOR WALL CAN NOT EXTEND OVER PROPERTY
 LINE.
  
 4) SOME OF THE DRAWINGS ARE NOT SIGNED
 AND SEALED BY THE ENGINEER.
  
 5) THE ENGINEER IS REQUIRED TO DATE THE
 PLANS AS WELL AS SIGN AND SEAL THEM.
  
 6) THE NEW PLANS DO NOT HAVE SHEETS G1
 AND G2.
  
 7) SHEET A1 IS INCORRECTLY DATE 3-18-03.
 THE OTHERS ARE DATED 3-18-02.
  
 8) PLEASE PUT TOGETHER TWO COMPLETE SETS
 OF PLANS WITH PRODUCT APPROVALS AND ALL
 OTHER REQUIRED SUBMITTALS. IF YOU ARE
 GOING TO SUBMIT THE OLD PLANS AS WELL,
 THEY NEED TO BE MARKED "OLD PLANS".
  
 9) THE ENERGY CALCULATIONS HAVE
 INCORRECT INFORMATION LISTED FOR THE
 EXTERIOR CONCRETE WALL. PLEASE CORRECT.
  
 10) THE DRAWINGS FOR THE OPAQUE STEEL
 DOORS DO NOT HAVE THE RENEWAL STAMP WITH
 THE NEW ACCEPTANCE NUMBER. PLEASE SUBMIT
 THE NEW DRAWINGS.
  
 11) PLEASE SUBMIT SBCCI OR METRO-DADE
 PRODUCT APPROVALS FOR THE STORM PANELS.
 THE INFORMATION SUBMITTED IS NOT
 ACCEPTABLE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-06-20 Cont ID  
Sent By kstevens Date 2003-03-01 Time 06:52 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-20 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL MULLIONS (THE ONES THAT
 WERE SUBMITTED WERE EXPIRED)
 - EXTERIOR SIDE SWING METAL DOOR AT THE
 GARAGE.
  
 4) INDICATE ON THE PLANS THAT THE GLASS
 BLOCK IN THE MASTER BATH IS ONE HOUR
 FIRE RATED.
  
 5) PROVIDE FIRE RATING INFORMATION FROM
 GLASS BLOCK MANUFACTURER.
  
 6) THE 24SH WINDOWS LABELED EGRESS AT
 THE MASTER BEDROOM SITTING AREA DO NOT
 COMPLY WITH THE MINIMUM NET CLEAR
 OPENING REQUIREMENTS OF THE FLORIDA
 BUILDING CODE SECTION 1005.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-09 Cont ID  
Sent By pkrauss Date 2002-04-15 Time 11:57 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-05-09 00:00:00BUILDING DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 4) STUCCO THICKNESS ON VERTICAL METAL
 LATHE IS REQUIRED TO BE 7/8" PER ASTM
 C 926 AND 2504.2.1 FBC. PLEASE CORRECT
 WALL SECTIONS B&C ON A10.
  
 5) A CLEARANCE OF 6" IS REQUIRED BETWEEN
 EXTERIOR WALL COVERINGS AND FINAL GRADE
 FOR INSPECTION FOR TERMITE INFESTION.
 1403.1.6 FBC PLEASE INDICATE ON WALL
 SECTIONS B&C ON A10.
  
 6) PROVIDE EMERGENCY EGRESS WINDOW IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24INCHES,NET CLEAR
 OPENING WIDTH OF 20 INCHES AND NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ.FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 INCHES ABOVE
 THE FLOOR. 1005.4 FBC & CITY AMENDMENTS
 THE 24SH WINDOWS IN BR #2 TYPICALLY DO
 NOT PROVIDE THE REQUIRED OPENING HEIGHT.
 THE EXISTING WINDOW IN BR #3 MUST COMPLY
 OR BE REPLACED WITH A WINDOW THAT DOES.
  
 7) INDICATE ATTIC ACCESS IN HOUSE AND
 DETACHED GARAGE TO COMPLY WITH 2309.6FBC
  
 8) INDICATE THE SIZE OF THE ATTIC VENTS
 ON A10 AND PROVIDE CALCULATIONS WHICH
 INDICATE THE TOTAL NET FREE VENTILATING
 AREA TO CEILING AREA AS REQUIRED BY
 2309.7 FBC.
  
 9) INDICATE ON THE PLANS THAT THE WELDED
 WIRE MESH LISTED IN THE FOUNDATION NOTES
 ON G1 SHALL BE SUPPORTED IN A MANNER
 THAT COMPLIES WITH 1909.3 FBC.
  
 10) THE ROOF SHEATHING NAILING DIAGRAM
 ON A7 SHOULD INDICATE 5'(INCLUDING OVER-
 HANG) AT THE GABLE END (ZONE 3). CITY
 AMENDMENTS 2306.1
  
 11) INDICATE THE POSITIVE AND NEGATIVE
 PRESSURES ON THE ELEVATIONS FOR ALL NEW
 WINDOW AND DOOR OPENINGS.
  
 12) THE REAR ELEVATION EXCEEDS TABLE 600
 FBC FOR THE PERCENTAGE OF OPENINGS
 ALLOWED. WALLS WITHIN 3'-10' OF THE
 PROPERTY LINE ARE ALLOWED TO HAVE 20 %
 OF THE WALL AREA AS OPENINGS, WHICH IS
 52 SQFT. IN THIS CASE. WITH 1 HOUR FIRE
 RATED GLASS BLOCK IN THE BATHROOM THE
 REMAINING WINDOW AREA IS 55.3 SQFT.
  
 13) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALCULATION FORM.
  
 14) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL MULLIONS
 - GLASS BLOCK
  
 15) SECTION 1707.4.4.2 OF FBC REQUIRES
 THAT TAPERED BUCKS EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME. WHERE BUCK THICKNESS IS LESS THAN
 1-1/2" THE WINDOW AND DOOR ASSEMBLIES
 ARE REQUIRED TO TO BE ANCHORED THROUGH
 THE BUCKS TO THE STRUCTURAL SUBSTRATE.
 PLEASE REVIEW THE BUCK DETAILS ON G2
 AND REVISE AS NECESSARY.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-07-12 Cont ID  
Sent By dpalmer Date 2005-07-12 Time 18:21 Rev Time 0.30
Received By dpalmer Date 2005-07-12 Time 18:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-06-21 Cont ID  
Sent By dpalmer Date 2005-06-21 Time 07:44 Rev Time 0.50
Received By dpalmer Date 2005-06-21 Time 07:41 Sent To M
Notes
2005-06-21 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE INCLUDE ALL LICENSE
 INFORMATION ON TITLE BLOCK AS REQUIRED
 UNDER FAC 61G15-23.002 AND FS 471.023
 THIS IS REQUIRED ON ALL SHEETS AND ALL
 TRADES WEATHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE COPY OF SURVEY
 ATTACHED. THIS IS SUBMITTED FOR A
 PROPOSED POOL AND DECK. THIS IS REQUIRED
 TO BE UNDER A SEPARATE PERMIT. PLEASE
 ALSO SEE ELECTRICAL OVERHEAD LLINES
 SHOWN SHALL BE INSTALL A MIN OF 10' FROM
 WATERS EDGE INCLUDING OVERHEAD
 UTILITIES.680.8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-03-27 Cont ID  
Sent By dpalmer Date 2003-03-27 Time 06:30 Rev Time 0.33
Received By dpalmer Date 2003-03-27 Time 06:30 Sent To B
Notes
2003-03-27 00:00:00*** PLANS NOTEDAND REDLINED *****
 PLANS DO NOT NEED TO BE REVISED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-02-19 Cont ID  
Sent By sthyng Date 2003-03-25 Time 13:57 Rev Time 1.00
Received By dpalmer Date 2003-02-19 Time 11:06 Sent To P
Notes
2003-02-19 00:00:00************* UNSAT *******************
  
 1)NOTE: PLEASE SEE RISER DIAGRAM, NOW
 A NEW 300A MAIN DISC HAS BEEN ADDED?
 PLEASE SEE 310-15FOR SIZING OF
 CONDUCTORS, SHOWN AS 2/0'S WHICH ARE
 ONLY RATED FOR 200A'S.
  
 2)NOTE: PLEASE SEE 250-66 FOR SIZING OF
 GROUNDING ELECTRODE PER SEC.
  
 3)NOTE: PLEASE CLARIFY SIZE OF METERCAN
 IF SERVICE IS GOING TO BE 400A AS SHOWN.
  
  
 4)NOTE: PLEASE SHOW LOCATIONS OF MAIN
 DISC'S. MAINS ARE TO BE GROUPED PER
 230-72.SHOW ON PLAN.
  
 5)NOTE: RISER ON A-11 SHOWS AN EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC
 AND METER. PLEASE SEE 250-24, AND REMOVE
 , ONLY AFTER THE FIRST MEANS OF DISC
 IS AN EQUIPMENT GROUND INSTALLED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 07:17 Rev Time 0.33
Received By dpalmer Date 2003-02-06 Time 07:17 Sent To  
Notes
2003-02-06 00:00:00PLANS/PERMITS HAVE EXPIRED, OVER 7
 MONTH-S W/ NO ACTIVITY. PLANS SENT BACK
 OUT FRONT. SHOULD NOT HAVE COME BACK IN.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-06-11 Cont ID  
Sent By dpalmer Date 2003-01-29 Time 13:50 Rev Time 0.00
Received By dpalmer Date 2002-06-11 Time 05:52 Sent To P
Notes
2002-06-11 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE NOW A RISER DIAGRAM
 IS BEING SUBMITTED INCLUDING A PANEL
 FOR GARAGE.
 PLEASE NOTE PER 230-72 GROUPING OF MAINS
 AT MAIN SERVICE. MAIN DISC REQ`D AT
 METER LOCATION TO FEED GARAGE PANEL.
 PLEASE ALSO NOTE NO CONDUIT/WIRE SIZES
 AND GROUNDING SHOWN TO OR AT GARAGE
 PANEL. GARAGE ALSO NEEDS A MAIN DISC IF
 PANEL HAS MORETHAN 6 SPACES.
 RECEPT IN GARAGE TO BE GFI 210-8
  
 2)NOTE: PLEASE NOTE THAT ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO GFI
 /GFI PROTECTED. PER 210-8-A-6. INCLUDING
 PENINSULAR.
  
 3)NOTE: PLEASE NOTE BATHROOM STILL
 MISSING EGRESS LIGHTING PER 210-70
 EXIST BATH.
  
 4)NOTE: PLEASE NOTE OUTLET SPACING IN
 EXISTING BEDROOM AND LIV RM WILL BE REQ`
 D TO BE BROUGHT UP TO CODE IF EXIST DOES
 NOT MEET 210-52. ??
  
 5)NOTE: PLEASE NOTE, JUST AS A NOTE,
 SEEMS KITCHEN COUNTER AT END MAY BE 12"
 OR MORE WHICH WOULD REQ` AN OUTLET.
 210-52-C-1
  
 PLEASE NOTE THAT MOST NOTES ARE FROM
 FIRST REVIEW. PLEASE SUBMIT THE ABOVE
 AND IF THERE ARE ANY QUESTIONS,PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 6)NOTE: PLEASE NOTE ON FIRST SET OF PLAN
 -S, A RECEPT WAS SHOWN WITHIN 5' OF POOL
 WHICH IS NOT ALLOWED, THAT WAS REMOVED,
 HOWEVER ONE IS REQ`D WITHIN 20`. PLEASE
 SEE 680-6(A).

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-12 Cont ID  
Sent By dpalmer Date 2002-04-12 Time 08:54 Rev Time 0.00
Received By dpalmer Date 2002-04-12 Time 08:54 Sent To  
Notes
2002-04-12 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT UNLESS THE
 FEED FROM METER TO PANEL IS UNDERGROUND
 (SLAB). MORE THAN 8' OF UNPROTECTED
 CONDUCTORS IS NOT ALLOWED IN BLDG.
 PLEASE NOTE THAT A MAIN DISC WILL BE
 REQ`D WITH OCP.
  
 2)NOTE: PLEASE NOTE THAT IF INSTALLING A
 NEW MAIN DISCONNECT THEN, PLEASE SUBMIT
 THE AIC RATING FOR NEW MAIN. 110-9
  
 3)NOTE: PLEASE CLARIFY OUTLETS SHOWN
 AROUND THE OUTSIDE OF HOUSE. NOT SHOWN
 ON ELECTRICAL DETAIL ON LEFT? PLEASE
 SHOW ALL AS GFI/GFI PROTECTED PER 210-8.
  
  
 4)NOTE: PLEASE NOTE THAT OUTLETS SHOWN
 AROUND POOL ARE SHOWN CLOSER THAN THE
 5' PERMITTED PER 680-6A.
  
 5)NOTE: PLEASE NOTE THAT THERE BATHROOMS
 THAT DO NOT SHOW GFI OUTLETS REQ`D PER
 210-52D PLEASE NOTE THAT 210-8
 PLEASE CLARIFY IF EXISITNG?
  
 6) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 7 )NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 8) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 9)NOTE: PLEASE NOTE CIRCUIT SHOWN FOR
 WALL OVEN IS SHOWN AT 4500W WITH #12?
 PLEASE CORRECT.
  
 10)NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSINGONE INMASTER BEDROOM.
  
 11)NOTE: PLEASE CLARIFY CIRCUIT WATTAGE
 FOR COND UNIT. SHOWN W/2P-50 AND ONLY
 1200WATTS.
  
 12)NOTE: PLEASE NOTE THAT DISCONNECTING
 MEANS SHALL BE PROVIDED FOR ALL
 UNGROUNDED CONDUCTORS THAT SUPPLY OR
 PASS THROUGH A BLDG/STRUCTURE.
 PER 225-31. PLEASE ALSO NOTE GROUNDING
 PER 250-50/250-32
 PLEASE NOTE THAT THERE IS NOTHING ON
 PANEL SCHEDULE ABOUT GARAGE, PLEASE
 CLARIFY.
  
 PLEASE SUBMIT THE ABOVEINFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 13:57 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 13:57 Sent To E
Notes
2005-07-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 16:57 Rev Time 0.00
Received By shill Date 2005-06-10 Time 16:57 Sent To E
Notes
2005-06-10 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-01 Cont ID  
Sent By adarroug Date 2005-04-01 Time 15:23 Rev Time 0.00
Received By adarroug Date 2005-04-01 Time 15:23 Sent To B
Notes
2005-04-01 00:00:00TO "RMCDOUGAL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-25 Cont ID  
Sent By sthyng Date 2003-03-25 Time 13:57 Rev Time 0.00
Received By sthyng Date 2003-03-25 Time 13:57 Sent To E
Notes
2003-03-25 00:00:00TO DP DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-28 Cont ID  
Sent By pkrauss Date 2005-06-28 Time 15:52 Rev Time 0.30
Received By pkrauss Date 2005-06-28 Time 15:52 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-15 Cont ID  
Sent By pkrauss Date 2002-04-15 Time 11:55 Rev Time 0.40
Received By pkrauss Date 2002-04-15 Time 11:46 Sent To B
Notes
2002-04-15 00:00:00O.A. NOT REQUIRED FOR ADDITION.AIR
 BALANCE OKAY. ADDITION FOR MASTER BEDRM,
 BATH & GUEST BEDRM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-03-01 Cont ID  
Sent By pkrauss Date 2005-06-28 Time 15:53 Rev Time 0.50
Received By kstevens Date 2003-03-01 Time 06:52 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-06-19 Cont ID  
Sent By dpalmer Date 2003-02-19 Time 11:07 Rev Time 0.00
Received By kstevens Date 2002-06-19 Time 18:18 Sent To  
Notes
2002-06-19 00:00:00DENIED
 RFEFERENCE: FBC-2001 PLUMBING
  
 1) SHT A-6, SANITARY RISER DIAGRAM.
 BIDET MISSING IN BATHROOM. BATHROOMS NOT
 VENTED PROPERLY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-05-02 Cont ID  
Sent By dpalmer Date 2002-06-11 Time 06:06 Rev Time 0.33
Received By jleech Date 2002-05-02 Time 09:08 Sent To  
Notes
2002-05-02 00:00:00PAGE A-6 RISER DIAGRAM, W/C NOT VENTED,
 BIDET IS MISSING AND TUB REQUIRES 3"
 PIPE TO BE VENTED PROPERLY. SEE TABLE
 909.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-08 Cont ID  
Sent By sgraham Date 2002-04-08 Time 12:31 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***