Plan Review Details - Permit 02040117
Plan Review Stops For Permit 02040117
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-03 Cont ID  
Sent By btrobaug Date 2002-04-25 Time 14:32 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2002-05-03 00:00:00MUST PASS PLUMBING REVIEW BEFORE PERMIT
 CAN BE PRINT PERMITS WHEN PLUMBING HAS A
 PPROVED THE PLUMBING LS

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-04-29 Cont ID  
Sent By dpalmer Date 2002-04-29 Time 17:40 Rev Time 0.00
Received By dpalmer Date 2002-04-29 Time 17:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-25 Cont ID  
Sent By btrobaug Date 2002-04-25 Time 14:31 Rev Time 0.00
Received By btrobaug Date 2002-04-25 Time 14:31 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-23 Cont ID  
Sent By kstevens Date 2002-04-22 Time 19:48 Rev Time 0.00
Received By btrobaug Date 2002-04-23 Time 07:54 Sent To  
Notes
2002-04-23 00:00:00FAILED PENDING INFORMATION ON OUT OF
 STATE NOTARY,LEGALITY OF O.A.S SEAL IN
 FLORIDA.
 WRT.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-08 Cont ID  
Sent By kstevens Date 2002-05-08 Time 18:23 Rev Time 0.00
Received By kstevens Date 2002-05-08 Time 18:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-21 Cont ID  
Sent By kstevens Date 2002-04-21 Time 18:11 Rev Time 0.00
Received By kstevens Date 2002-04-21 Time 18:11 Sent To E
Notes
2002-04-21 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) ADJUST PLANS, NOTES, DETAILS, AND
 SUBMITTALS AS FOLLOWS.
 A)
 FBC-2001 SEC 424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MI8NIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL) SPA M.D'S ARE ONLY 2' APART.
 B)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 C)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 D)
 FBC-2001 SEC 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 E)
 FBC-2001 SEC 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 F)
 FBC-2001 SEC 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 G)
 FBC-2001 SEC 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-04 Cont ID  
Sent By sgraham Date 2002-04-04 Time 16:38 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***