Plan Review Details - Permit 02040109
Plan Review Stops For Permit 02040109
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-12 Cont ID  
Sent By pkrauss Date 2002-04-12 Time 11:36 Rev Time 0.30
Received By pkrauss Date 2002-04-12 Time 11:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-03 Cont ID  
Sent By pkrauss Date 2002-04-03 Time 13:25 Rev Time 0.40
Received By pkrauss Date 2002-04-03 Time 13:25 Sent To  
Notes
2002-04-03 00:00:002001 FLORIDA BUILDING CODE, MECHANICAL
  
 1.INDICATE SIZE & LOCATION OF RETURN
 AIR GRILLE.
  
 2.BALANCED RETURN AIR - WHERE RETURN
 IS CENTERALLY LOCATED & TO AVOID
 PRESSURE DIFFERENTIALS ACROSS CLOSED
 DOORS, PROVIDE AIR DUCT PATHWAYS OR
 AIR TRANSFER FROM THE HIGH PRESSURE
 ZONES TO LOW ZONE.601.4
  
 3.BALANCING DAMPERS OR OTHER MEANS OF
 SUPPLY AIR ADJUSTMENT SHALL BE
 PROVIDED IN THE BRANCH DUCTS OR AT
 EACH INDIVIDUAL DUCT REGISTER,
 GRILLE OR DIFFUSER.603.15
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.