Plan Review Details - Permit 02040096
Plan Review Stops For Permit 02040096
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-30 Cont ID  
Sent By dpalmer Date 2002-04-30 Time 19:47 Rev Time 0.00
Received By dpalmer Date 2002-04-30 Time 19:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-10 Cont ID  
Sent By btrobaug Date 2002-04-10 Time 08:47 Rev Time 0.00
Received By btrobaug Date 2002-04-10 Time 07:44 Sent To P
Notes
2002-04-10 00:00:00****************UNSAT!******************
 1} PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 2}PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 3}PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 4}CODE ARTICLES IN THE ELECTRICAL NOTES
 ARE INCORRECT.
  
 5}PLEASE NOTE AIC @ 22.00?
  
 PLEASE MAKE CORRECTIONS AND RESUBMIT FOR
 REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-11-26 Cont ID  
Sent By pkrauss Date 2002-11-25 Time 11:30 Rev Time 0.25
Received By pkrauss Date 2002-11-25 Time 11:30 Sent To  
Notes
2002-11-25 00:00:00MECHANICAL REVISION PERMIT 02040113
 REVISED ENERGY CALCS SUBMITTED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-09 Cont ID  
Sent By hmoser Date 2002-05-09 Time 18:08 Rev Time 0.50
Received By hmoser Date 2002-05-09 Time 18:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-13 Cont ID  
Sent By hmoser Date 2002-04-13 Time 09:46 Rev Time 0.33
Received By hmoser Date 2002-04-13 Time 09:46 Sent To  
Notes
2002-04-13 00:00:00PLAN DENIED
 PLANS DO NOT MATCH ENERGY CALCS OR
 MANUAL J [MODEL NUMBER AND SEER DO NOT
 MATCH]
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT 8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-13 Cont ID  
Sent By btrobaug Date 2002-04-10 Time 09:10 Rev Time 0.33
Received By jleech Date 2002-04-13 Time 06:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-05-09 Cont ID  
Sent By lhatten Date 2002-05-09 Time 19:30 Rev Time 0.50
Received By lhatten Date   Time   Sent To  
Notes
2002-05-09 00:00:00CALC. FEES & PRINT CARDS 05/09/2002

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-04-29 Cont ID  
Sent By lhatten Date 2002-04-29 Time 10:52 Rev Time 2.50
Received By lhatten Date 2002-04-28 Time 10:51 Sent To  
Notes
2002-04-30 00:00:00REVIEW & STAMPED PLANS 04/28/2002
 OKED PER LOU HATTEN

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-05 Cont ID  
Sent By sgraham Date 2002-04-05 Time 13:29 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***