Plan Review Details - Permit 02040084
Plan Review Stops For Permit 02040084
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2003-01-29 Cont ID  
Sent By rbrown Date 2003-01-29 Time 16:13 Rev Time 0.00
Received By rbrown Date 2003-01-29 Time 16:12 Sent To  
Notes
2003-01-29 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 REVISION SUBMITTED 1-16-03 FOR EXTENDING
 THE GARAGE AND INSTALLING A 2ND FLOOR
 BATHROOM.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) PLEASE NOTE THAT THE PROVISOS DATED
 12-6-02 STILL STAND, AS THEY HAVE NOT
 YET BEEN ADDRESSED.
  
 2) THE ROOF PROFILE AND WEST ELEVATION
 WALL WOULD BE CHANGED BY THE PROPOSED
 PERMIT PLAN REVISION.SUBMIT A REVISED
 WEST ELEVATION TO SHOW THIS.
  
 3) NO NEW DOOR AND WINDOW SCHEDULE HAS
 BEEN SUBMITTED.THE GARAGE AND LAUNDRY
 WINDOWS W, Y AND Z ON SHEET A-2 DO NOT
 CORRELATE WITH THE PERMIT APPROVED
 SCHEDULE.ALSO, THE GUEST BATH WINDOW
 REFERENCE 'V' IS SHOWN ON THE SCHEDULE
 AS A GARAGE DOOR.SUBMIT A CORRECTED
 SCHEDULE
  
 4) THE SIZE OF THE GARAGE DOOR HAS BEEN
 INCREASED.SUBMIT A PRODUCT APPROVAL
 AND REVISE THE DOOR SCHEDULE TO SPECIFY
 THE NEW DOOR.
  
 5) THE EXTERIOR DOOR AT THE REAR OF THE
 GARAGE IS SHOWN AS 'X', WHICH THE
 SCHEDULE CALLS UP AS 'EXISTING'.WHICH
 EXISTING DOOR IS TO BE USED?IF A NEW
 DOOR IS REQUIRED, SUBMIT A PRODUCT
 APPROVAL.
  
 6) FBC 2405.2THE WINDOW ADJACENT THE
 PROPOSED 2ND FLOOR BATH TUB IS IN A
 'HAZARDOUS LOCATION' AND IS REQUIRED
 TO BE SAFETY GLASS SATISFYING THE
 REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 7) THERE ARE ARCHITECT'S AND ENGINEER'S
 HAND-WRITTEN REVISIONS, ON THE PERMIT
 APPROVED ARCHITECTURAL AND STRUCTURAL
 PLANS, THAT HAVE NOT BEEN ADDED TO THE
 REVISED PLAN SET. THE OMISSIONS INCLUDE,
 BUT ARE NOT LIMITED TO, THE HAND-WRITTEN
 REVISION TO NOTE 9 OF THE PERMIT
 APPROVED COPY OF SHEET A-2, THE BEAM
 SCHEDULE ON SHEET S-1, AND THE
 'CONSTRUCTION NOTES' AND HAND-DRAWN
 ATTIC ACCESS PANEL IN THE CLOSET ON THE
 PERMIT APPROVED COPY OF SHEET A-3. CHECK
 AGAINST THE PERMIT APPROVED PLANS AND
 AMEND THE REVISION PLAN SET TO SHOW THE
 REQUIRED INFORMATION.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-12-06 Cont ID  
Sent By kstevens Date 2003-01-28 Time 11:11 Rev Time 0.00
Received By rbrown Date 2002-12-06 Time 13:50 Sent To  
Notes
2002-12-06 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 THE FOLLOWING PRODUCT APPROVALS HAVE
 EXPIRED SINCE THE ORIGINAL PLAN REVIEW
 APPLICATION WAS SUBMITTED:
 NOA# 98-1110.10 (EXPIRED 4-15-02)
 NOA# 98-1110.12 (EXPIRED 4-15-02)
 NOA# 99-0223.07 (EXPIRED 5-1-02)
 SUBMIT VALID PRODUCT APPROVALS.
  
 --PROVISO--
 THE ELEVATIONS SHOW WINDOW MULLIONS.
 SUBMIT MULTIPLE UNIT WINDOW PRODUCT
 APPROVALS OR SEPARATE MULLION PRODUCT
 APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-09-09 Cont ID  
Sent By rbrown Date 2002-09-09 Time 09:57 Rev Time 0.00
Received By rbrown Date 2002-09-09 Time 09:57 Sent To  
Notes
2002-09-09 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 --PROVISO--
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 --PROVISO--
 WINDOW ELEVATIONS AND PRODUCT APPROVALS.
 THE RESPONSE STATES THAT CASEMENT, FIXED
 AND SINGLE HUNG WINDOWS WILL BE USED.
 UNTIL A PRODUCT APPROVAL IS SUBMITTED
 THE SINGLE HUNG WINDOWS, ONLY THE FIXED
 AND CASEMENT WINDOWS CAN BE PERMITTED.
  
 --PROVISO--
 THE ELEVATIONS SHOW WINDOW MULLIONS.
 BEFORE A PERMIT CAN BE ISSUED, SEPERATE
 MULLION PRODUCT APPROVALS SHALL BE
 SUBMITTED AS PER THE NOTES ON THE FIXED
 WINDOW PRODUCT APPROVAL DRAWING SHEET
 6 OF 6 AND THE CASEMENT WINDOW PRODUCT
 APPROVAL DRAWING SHEET 1 OF 4.
  
 --PROVISO--
 FBC 13-103.1.2BEFORE A BUILDING PERMIT
 CAN BE ISSUED, THE SUBMITTED ENERGY CODE
 COMPLIANCE FORMS SHALL BE SIGNED BY THE
 BUILDING OWNER, THE OWNER'S ARCHITECT OR
 OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-07-31 Cont ID  
Sent By btrobaug Date 2002-08-30 Time 13:57 Rev Time 0.00
Received By rbrown Date 2002-07-31 Time 13:29 Sent To  
Notes
2002-07-31 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 5/15/02:
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4) & 5) CORRECTIONS. RESPONSE NOTED, BUT
 THE DESIGNER OF RECORD SHALL INITIAL AND
 DATE ALL ALTERATIONS ON THE DRAWINGS.
  
 8) WINDOW ELEVATIONS.RESPONSE NOTED
 BUT IF WINDOW TYPE CANNOT BE DETERMINED
 FROM THE ELEVATION DRAWINGS, THEN THE
 WINDOW SCHEDULE SHALL STATE THE WINDOW
 TYPE AS BEING FIXED, CASEMENT, SINGLE-
 HUNG OR SLIDING.THIS WILL ENABLE
 CORRELATION BETWEEN THE WINDOW LOCATION
 AND PRODUCT APPROVAL.
  
 9) SHUTTER PRODUCT EVALUATION (SBCCI)
 REPORT NO. 2127.THE NOTES AND
 DIMENSIONS ON DRG 01-265, SHEETS 1 TO 11
 CANNOT BE READ DUE TO FAXING AND/OR POOR
 COPYING.SUBMIT LEGIBLE COPIES.ALSO,
 THIS DRAWING NUMBER DOES NOT CORRESPOND
 TO THE ONE LISTED AS 'SUBSTANTIATING
 DATA' IN ITEM 5.1 OF THE PRODUCT
 EVALUATION REPORT.
  
 11) FBC 2309.6ATTIC ACCESS.RESPONSE
 NOTED, BUT NO ACCESS HAS BEEN PROVIDED
 FOR THE ATTIC SPACES ABOVE BED 1, BED 2,
 FAMILY ROOM AND GARAGE.IS ACCESS
 AVAILABLE THROUGH THE MASTER BEDROOM
 CLOSET WALL AND SITTING ROOM WALL?
  
 12) FBC 2405.2SAFETY GLASS.RESPONSE
 NOTED, BUT DOOR 2B IS NOT SCHEDULED AS
 HURRICANE IMPACT RESISTANT AND IS NOT
 ANNOTATED AS SAFETY GLASS.
  
 13) FBC 1007.8.2CIRCULAR STAIRWAYS.
 AMEND NOTES 9 AND 10 ON SHEET A-2, TO
 STATE THAT DETAILS SHALL BE SUBMITTED TO
 CITY OF WEST PALM BEACH, BUILDING DEPT.
  
 14) FBC 1608.2.2THE GUARDRAILS CANNOT
 BE 'UNDER A SEPARATE PERMIT'.ANNOTATE
 EACH OF THE BALCONY GUARDRAILS, ON SHEET
 A-3, TO STATE THAT DETAILS SHALL BE
 SUBMITTED TO CITY OF WEST PALM BEACH TO
 DEMONSTRATE COMPLIANCE WITH FBC 1015 AND
 FBC 1608.2.2
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-05-15 Cont ID  
Sent By btrobaug Date 2002-07-16 Time 12:28 Rev Time 0.00
Received By rbrown Date 2002-05-15 Time 21:13 Sent To  
Notes
2002-05-15 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC* 104.2.1.3THE USE OF 'WITE-OUT'
 ON PLANS SUBMITTED FOR PERMITTING
 PURPOSES IS INAPPROPRIATE.THE
 RESUBMITTED PLANS MUST NOT INCLUDE
 ALTERATIONS MADE WITH CORRECTION FLUID.
  
 4) SHEET A-12, SPECIFICATIONS.
 2.02 MAKES REFERENCETO THE VILLAGE OF
 PALM BEACH.CORRECT THIS TO READ CITY
 OF WEST PALM BEACH.
 6.13, 6.15B & H, AND 7.01 ALL MAKE
 REFERENCE TO STANDARD BUILDING CODE.
 SHEETS S-1 AND S-2 MAKE REFERENCE TO
 SOUTH FLORIDA BUILDING CODE.CORRECT
 ALL BUILDING CODE REFERENCES TO 'FLORIDA
 BUILDING CODE 2001'.
  
 5) FBC 1606.1.6SHEET S-0 REFERS TO A
 WIND SPEED OF 110MPH.THAT WAS THE WIND
 SPEED UNDER THE STANDARD BUILDING CODE.
 THE CORRECT WIND SPEED, UNDER THE
 FLORIDA BUILDING CODE, IS 140MPH.
  
 6) PRODUCT APPROVAL NOTICE OF ACCEPTANCE
 NO. 99-0223.07 STATES THAT THE FIBER
 CEMENT SIDING SHALL BE INSTALLED OVER A
 5/8" PLYWOOD SUBSTRATE.DETAILS A-9/6,7
 AND 9 DO NOT REFLECT THIS.ANNOTATE THE
 PLANS TO ENSURE COMPLIANCE WITH THE
 REQUIREMENT OF THE PRODUCT APPROVAL AND
 TO CORRELATE WITH DETAIL S-4/1.
  
 7) PRODUCT APPROVAL NOTICE OF ACCEPTANCE
 NO. 02-0205.07 INDICATES THAT THE DOUBLE
 FRENCH DOOR ARRANGEMENT REQUIRES AN
 ASTRAGAL BETWEEN THE TWO DOOR LEAFS.
 THIS REQUIREMENT IS NOT REFLECTED ON THE
 FLOOR PLANS.AMEND THE PLANS OR SUBMIT
 A PRODUCT APPROVAL THAT CORRESPONDS TO
 THE PROPOSED ARRANGEMENT.
  
 8) ELEVATION SHEETS A-5 AND A-6 SHOW
 SINGLE HUNG WINDOWS.THE SUBMITTED
 PRODUCT APPROVALS ARE FOR FIXED WINDOWS
 AND CASEMENT WINDOWS.SUBMIT A PRODUCT
 APPROVAL TO COVER THE PROPOSED WINDOW
 TYPE.
  
 9) DOOR AND WINDOW SCHEDULE SHEET A-11
 REFERS TO HURRICANE MISSILE IMPACT
 PROTECTION SHUTTERS FOR SOME WINDOWS.
 SUBMIT A PRODUCT APPROVAL FOR THE
 PROPOSED SHUTTERS.
  
 10) FBC 1606.3.2SUBMIT A PRODUCT
 APPROVAL FOR THE ROOF COVERING.
  
 11) FBC 2309.6EACH OF THE ATTIC SPACES
 SHALL BE PROVIDED WITH ACCESS OPENINGS
 NOT LESS THAN 20"X36".
  
 12) FBC 2405.2THE GLAZING IN THE DOORS
 AND GLAZED PANELS WITHIN 24" OF A DOOR
 IS IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 13) FBC 1007.8.2DETAILS OF THE
 CIRCULAR STAIRWAYS SHALL BE SUBMITTED
 BEFORE CONSTRUCTION.
  
 14) FBC 1608.2.2GUARDRAILS.SUBMIT
 GUARDRAIL ATTACHMENT DETAILS, FOR EACH
 OF THE BALCONIES, TO DEMONSTRATE
 COMPLIANCE WITH THE LOADING REQUIREMENTS
  
 15) FBC* 104.2.1.2SHEET S-2, HIGH ROOF
 FRAMING PLAN.THE CORNER COLUMN C-4 AND
 ASSOCIATED BEAM B-8 WILL RECEIVE LOAD
 FROM THE REAR JACUZZI, VIA THE PRE-
 MANUFACTURED ROOF TRUSSES, IN ADDITION
 TO GENERAL ROOF/TERRACE LOAD. STRUCTURAL
 CALCULATION SHEET 17 DOES NOT ACCOUNT
 FOR THIS.SUBMIT ADDITIONAL DETAILS TO
 DESCRIBE THE LOAD PATH DOWN TO FIRST
 FLOOR.ALSO, WHAT SUPPORTS BEAM B-3?
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 07:57 Rev Time 0.50
Received By dpalmer Date 2003-01-24 Time 07:56 Sent To Z
Notes
2003-01-24 00:00:00**************** UNSAT ***************
  
 1)PLEASE SEE RISER DIAGRAM AND PLANS,
 THERE ARE MANY ITMES THAT DO NOT
 CORRELATE.
 SHOWS 250A SERVICE AND 225 DISC,225A
 PANEL W/ 250A BRKRS, 50A SUB PANEL W/
 68.75A LOAD W/ 75A OCP AND ONLY #6 WIRE
 ON RISER BUT SHOW #4 ON PANEL SCHEDULE.
  
 2)NOTE: MISSING EQUIPMENT GROUNDING
 CONDUCTORS BETWEEN MAIN AND PANELS,
 SIZE PER 250-122
  
 3)NOTE: PLEASE NOTE, PLANS CAME IN FOR
 AN ADDITION ON GARAGE AND NO ELECTRICAL
 SHOWN. PLEASE REVISE ON E-SHEET FOR
 LAYOUT OF ADD.
  
 PLEASE NOTE PLANS HAVE HAD THE SAME NOTE
 S ON PREVIOUS REVIEW. PLEASE ADDRESS
 COMMENTS.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED. MAINS
 PANELS, BRKRS ARE ALL TO BE RATED FOR
 THE AVAILABLE FAULT CURRENT. 110-9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-08-30 Cont ID  
Sent By btrobaug Date 2003-01-16 Time 17:03 Rev Time 1.00
Received By btrobaug Date 2002-08-30 Time 11:13 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-07-16 Cont ID  
Sent By btrobaug Date 2002-07-16 Time 12:27 Rev Time 0.00
Received By btrobaug Date 2002-07-16 Time 10:33 Sent To B
Notes
2002-07-16 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE THE FOLLOWING DISCREPANCIES
 ON PLANS,MAKE ANY NECESSARY CHANGES AND
 RESUBMIT FOR REVIEW.
  
 1} THE EQUIPMENT GROUND BETWEEN THE
 METER AND THE MAIN DISCONNECT NEEDS TO
 BE REMOVED. SEE NOTE #2 LAST REVIEW.
  
 2} PLEASE NOTE THE SINGLE POLE 50 AMP
 BREAKER SHOWN FEEDING PANEL "B",CIRCUIT
 38 IN PANEL "A".
  
 3} PLEASE SHOW METER ON THE PLANS.
  
 4} PLEASE NOTE CIRCUIT # 21 INDICATES A
 SMALL APPLIANCE CIRCUIT AND LAUNDRY
 CIRCUIT,THESE MUST BE SEPERATED PER
 210-11(C)(2).
  
 5} THE LOAD CALCULATIONS FOR PANEL "B"
 IS SHOWN AT 7.5 KW PER PHASE EQUALLING
 15KW,WHICH DIVIDED BY 240 VOLTS=62.5
 AMPS,EXCEEDING THE PANEL RATING,AND THE
 OCP FEEDING SAME.
  
 6} PLEASE NOTE THE SWITCH LOCATED ON THE
 ROOF FOR THE STAIRWELL SHOULD BE A
 3-WAY.
  
 7} NOTE CIRCUIT # 41 FOR BR#1 IS SHOWN
 AS A GFI,NOT AFCI AS REQUIRED BY 210-12.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392
  
  
  
  
  
  
  
  
  
  
  
  
 ]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-12 Cont ID  
Sent By dpalmer Date 2002-04-12 Time 13:42 Rev Time 0.00
Received By dpalmer Date 2002-04-12 Time 13:42 Sent To  
Notes
2002-04-12 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT SERVICE
 ENTRANCE CONDUCTORS ARE SHOWN AS 2/0`S
 ON RISER DIAGRAM AND NEED TO MEET MIN
 PER 310-15.
  
 2)NOTE: PLEASE NOTE THAT THERE IS AN
 EQUIPMENT GROUNDING BETWEENMETER AND
 MAIN. THIS IS PARALLELING THE NEUTRAL
 WHICH IS NOT PERMITTED.
 PLEASE NOTE THAT THE EQUIPMENT GROUNDING
 CONDUCTOR IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 3)NOTE: PLEASE NOTE THAT SUB PANEL IS
 SHOWN AS 25AMP? PLEASE CLARIFY?
  
 4)NOTE: PLEASE NOTE THAT PANEL "A" IS
 SHOWING #12 1-POLE 50 FEEDING SUB PANEL.
 PLEASE CORRECT.
  
 5)NOTE: PLEASE CLARIFY 220V OUTLET SHOWN
 IN THE MIDDLE OF THE YARD?
  
 6)NOTE: PLEASE NOTE THAT LOCATION OF
 PANEL "A" DOES NOT MEET 110-26.
 PLEASE CHANGE LOCATION TO MEET 110-26.
  
 7)NOTE: PLEASE SHOW LOCATION OF PANEL
 "B".
  
 8)NOTE: PLEASE NOTE MISSING EGRESS
 LIGHTING IN CLOSET (FUTURE BATH) UPSTAIR
 -S. 210-70.
  
 9 ) NOTE: PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
 MISSING.
  
 10NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 11)NOTE: PLEASE NOTE THAT OUTLET
 SPACING NEEDS TO MEET 210-52C -1.
  
 12)NOTE: PLEASE NOTE OUTLET(S) IN GARAGE
 NEEDS TO BE GFI/GFI PROTECTED.
  
 13)NOTE: PLEASE NOTE MISSING OUTLET IN
 BEDROOM. PER 210-52.
  
 14)NOTE: PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 15)NOTE: PLEASE NOTE THAT PANEL IS SHOWN
 AS MLO? PLEASE CLARFIY WHERE MAIN DISC
 IS. PER 225-31
  
 16)NOTE: PLEASE CLARFIY HOW THERE ARE
 CIRCUITS SHOWN AS SMALL APPL AND DINING
 AND SM APPL AND LAUNDRY. PLEASE NOTE
 THESE CIRCUITS CAN NOT BE COMBINED,
 PER 210-52,210-11
  
 17)NOTE: PLEASE NOTE THAT LOADS SHOWN
 FOR AHU`S ARE SHOWN AT 16KW AND 17KW
 ONCALCS? PLEASE CLARIFY.
  
 18)NOTE: PLEASE NOTE THAT LOAD CALCS
 FOR PANEL "B" ARE SHOWING LOAD FOR "B"
 AT 206A`S??? PLEASE CORRECT.
  
 19)NOTE: PLEASE NOTE THAT IF THERE IS
 GOING TO BE ANY LOW VOLTAGE CATV, OR
 TELEPHONE, THEN THIS NEEDS TO BE SHOWN
 ON PLANS.
  
 20)NOTE: PLEASE VERFIY LOCATION SHOWN
 FOR BOTH AHU`S. PLEASE VERIFY FOR
 CLEARENCES, AND LOCATION OF RETURNS.
 110-26
 21)NOTE: PLEASE SHOW WHERE/WHAT EGRESS
 LIGHTING MEANS WILL BE FOR STAIRS UP TO
 ROOF.210-70
  
 22)NOTE: PLEASE NOTE THAT DISC`S AHU`S
 AND CU`S NEED TO MEET 110-26.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-04-21 Cont ID  
Sent By lmartine Date 2002-04-21 Time 12:22 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2002-04-21 Cont ID  
Sent By lmartine Date 2002-04-21 Time 12:23 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-27 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 12:34 Rev Time 0.00
Received By dpalmer Date 2003-01-27 Time 12:34 Sent To P
Notes
2003-01-27 00:00:00TO PLUMB INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-16 Cont ID  
Sent By btrobaug Date 2003-01-16 Time 17:03 Rev Time 0.00
Received By btrobaug Date 2003-01-16 Time 17:03 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-07-30 Cont ID  
Sent By pkrauss Date 2002-07-30 Time 11:33 Rev Time 0.35
Received By pkrauss Date 2002-07-30 Time 11:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-15 Cont ID  
Sent By pkrauss Date 2002-04-15 Time 09:19 Rev Time 0.45
Received By pkrauss Date 2002-04-15 Time 09:19 Sent To  
Notes
2002-04-15 00:00:00PLEASE PROVIDE THE FOLLOWING INFORMATION
  
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC, MECHANICAL 403.3. &
 TABLE 403.3.PLEASE NOTE OUTSIDE
 AIR SHALL NOT BE TAKEN FROM ROOF,
 ATTIC, OR CRAWLSPACE AS PER 2001 FBC
 CHAPTER 13 609.1ABC.1.
  
 2.PRESSURE DIFFERENTIALS ACROSS CLOSED
 DOORS WHERE RETURNS ARE CENTRALLY
 LOCATED SHALL BE LIMITED TO .001
 INCH WC OR LESS.PROVIDE AIR DUCT
 PATHWAYS OR AIR TRANSFER PATHWAYS
 FROM THE HIGH PRESSURE ZONE TO THE
 LOW ZONE.
  
 3.PLEASE CLARIFY RETURN IN THE LAUNDRY
 ROOM.PLAN DOES NOT REFLECT THE
 RETURNS BEING DUCTED TO THE AHU.
  
 4.CONDENSATE TERMINATION NOT INDICATED
 ON PLAN AS PER 2001 FBC 1503.4.4,
 CONDENSATE SHALL DISCHARGE A MINIMUM
 OF 12" FROM THE BUILDING STRUCTURE.
  
 5.SEE ALSO ELECTRICAL PLANS REVIEW
 NOTES #10 & 22.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-01-28 Cont ID  
Sent By kstevens Date 2003-01-28 Time 11:02 Rev Time 1.33
Received By kstevens Date 2003-01-28 Time 11:01 Sent To B
Notes
2003-01-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT FLOOR PLAN. 2 WATER CLOSETS
 SHOWN AND NO TUB.
 2) SHT A-4 ROOF PLAN PLEASE SUBMIT CAL-
 CULATIONS FOR PRIMARY AND SECONDARY ROOF
 DRAINS.SHOW 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPET WALLS PER SEC
 1106 & 1107. SHOW SIZES OF ROOF DRAINS
 AND SCUPPER DRAINS. INDICATE WHERE THE
 ROOF DRAINS WILL TERMINATE.
 3) SEPARATE PLUMBING PERMIT REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-04-29 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 12:34 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-09 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 07:59 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***