Plan Review Details - Permit 02040076
Plan Review Stops For Permit 02040076
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-04-22 Cont ID  
Sent By jwitmer Date 2002-04-22 Time 16:19 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-22 Cont ID  
Sent By jwitmer Date 2002-04-22 Time 16:13 Rev Time 0.00
Received By jwitmer Date 2002-04-16 Time 08:46 Sent To  
Notes
2002-04-22 00:00:00D.V. PALMER SIGNED APPROVED PLANS
 SIGNATURE ON PLANS, OK 4/16/02

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-04-11 Cont ID  
Sent By mcarsill Date 2002-04-11 Time 10:18 Rev Time 0.00
Received By mcarsill Date 2002-04-11 Time 10:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-18 Cont ID  
Sent By pkrauss Date 2002-04-18 Time 11:58 Rev Time 0.40
Received By pkrauss Date 2002-04-18 Time 11:29 Sent To  
Notes
2002-04-18 00:00:002001 FLORIDA BUIDLING CODE, MECHANICAL
  
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS AS PER 2001 FBC(M) OR
 ASHRAE 62-89.
  
 2.PROVIDE MANUFACTURER INFORMATION FOR
 THE HVAC EQUIPMENT AS WELL AS ANY
 EXHAUST FANS.
  
 3.INDICATE DUCT MATERIAL, SIZE AND CFM
 DISTRIBUTION.
  
 4.INDICATE GRILLE SIZE.PLEASE NOTE
 AS PER 2001 FBC(M) 603.15, BALANCING
 DAMPERS OR OTHER MEANS OF SUPPLY AIR
 ADJUSTMENT SHALL BE PROVIDED IN THE
 BRANCH DUCTS OR AT EACH INDIVIDUAL
 DUCT REGISTER, GRILLE OR DIFFUSER.
  
 5.INDICATE CONDENSATE DRAIN SIZE AND
 TERMINATION.
  
 6.SHOULD CONDENSERS BE LOCATED ON THE
 ROOF, PROVIDE MANUFACTURER SUBMITTAL
 DATA FOR THE STAND.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-29 Cont ID  
Sent By jleech Date 2002-04-29 Time 19:42 Rev Time 2.00
Received By jleech Date 2002-04-29 Time 19:42 Sent To  
Notes
2002-04-29 00:00:00DENIED;
 1.MINIMUM PLUMBING FACILITIES TABLE
 403.1. SERVICE SINK IS REQUIRED.
 2.PAGE 3 WASTE RISER DIAGRAM. STERILIZER
 SHALL BE AN INDIRECT WASTE SEC 713.3.
 A.PROCESSOR SHOWN DISCHARGING INTO
 SANITARY SYSTEM BUT NOTE 11 STATES
 WASTE SHALL NOT DISCHARGE TO
 SANITARY, ALSO SHOW BACKFLOW
 PROTECTION. PROVIDE MANUFACTORS
 CUT SHEETS.
 B.VACUUM SYSTEM TO DISCHARGE TO
 SANITARY, NOT SHOWN ON PLAN.
 3.WATER HAMMER ARRESTORS ARE REQUIRED
 AND INSTALLED PER SEC 604.9 AND
 MANUFACTORS SPECIFACTIONS.
 4.SHOW LOCATION OF BACKFLOW PREVENTOR.
 IF INSIDE THE BUILDING A A DRAIN WILL
 BE REQUIED.
 5.MED. GAS (VAC. & AIR)
 SEPARATE PERMIT REQUIRED COTRACTOR
 TO BE A CERTIFIED MED GAS INSTALLER.
 6.EQUIPMENT SPECS. REQUIRED FOR
 COMPRESSOR AND VACUUM SYSTEMS SHOW
 PIPE SIZES, CLEANOUT. US NFPA 99A
 LEVEL 3 FOR INSTALLATION REQUIREMENTS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***