Plan Review Details - Permit 02040076
| Plan Review Stops For Permit 02040076 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2002-04-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-04-22 |
Time |
16:19 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-04-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-04-22 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2002-04-16 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2002-04-22 00:00:00 | D.V. PALMER SIGNED APPROVED PLANS | | | SIGNATURE ON PLANS, OK 4/16/02 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-04-11 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-04-11 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-04-11 |
Time |
10:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-04-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-18 |
Time |
11:58 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-04-18 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2002-04-18 00:00:00 | 2001 FLORIDA BUIDLING CODE, MECHANICAL | | | | | | 1.PLEASE PROVIDE OUTSIDE AIR | | | CALCULATIONS AS PER 2001 FBC(M) OR | | | ASHRAE 62-89. | | | | | | 2.PROVIDE MANUFACTURER INFORMATION FOR | | | THE HVAC EQUIPMENT AS WELL AS ANY | | | EXHAUST FANS. | | | | | | 3.INDICATE DUCT MATERIAL, SIZE AND CFM | | | DISTRIBUTION. | | | | | | 4.INDICATE GRILLE SIZE.PLEASE NOTE | | | AS PER 2001 FBC(M) 603.15, BALANCING | | | DAMPERS OR OTHER MEANS OF SUPPLY AIR | | | ADJUSTMENT SHALL BE PROVIDED IN THE | | | BRANCH DUCTS OR AT EACH INDIVIDUAL | | | DUCT REGISTER, GRILLE OR DIFFUSER. | | | | | | 5.INDICATE CONDENSATE DRAIN SIZE AND | | | TERMINATION. | | | | | | 6.SHOULD CONDENSERS BE LOCATED ON THE | | | ROOF, PROVIDE MANUFACTURER SUBMITTAL | | | DATA FOR THE STAND. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-04-29 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2002-04-29 |
Time |
19:42 |
Rev Time |
2.00 |
| Received By |
jleech |
Date |
2002-04-29 |
Time |
19:42 |
Sent To |
|
|
| Notes |
| 2002-04-29 00:00:00 | DENIED; | | | 1.MINIMUM PLUMBING FACILITIES TABLE | | | 403.1. SERVICE SINK IS REQUIRED. | | | 2.PAGE 3 WASTE RISER DIAGRAM. STERILIZER | | | SHALL BE AN INDIRECT WASTE SEC 713.3. | | | A.PROCESSOR SHOWN DISCHARGING INTO | | | SANITARY SYSTEM BUT NOTE 11 STATES | | | WASTE SHALL NOT DISCHARGE TO | | | SANITARY, ALSO SHOW BACKFLOW | | | PROTECTION. PROVIDE MANUFACTORS | | | CUT SHEETS. | | | B.VACUUM SYSTEM TO DISCHARGE TO | | | SANITARY, NOT SHOWN ON PLAN. | | | 3.WATER HAMMER ARRESTORS ARE REQUIRED | | | AND INSTALLED PER SEC 604.9 AND | | | MANUFACTORS SPECIFACTIONS. | | | 4.SHOW LOCATION OF BACKFLOW PREVENTOR. | | | IF INSIDE THE BUILDING A A DRAIN WILL | | | BE REQUIED. | | | 5.MED. GAS (VAC. & AIR) | | | SEPARATE PERMIT REQUIRED COTRACTOR | | | TO BE A CERTIFIED MED GAS INSTALLER. | | | 6.EQUIPMENT SPECS. REQUIRED FOR | | | COMPRESSOR AND VACUUM SYSTEMS SHOW | | | PIPE SIZES, CLEANOUT. US NFPA 99A | | | LEVEL 3 FOR INSTALLATION REQUIREMENTS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT 8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|