Plan Review Details - Permit 02040049
Plan Review Stops For Permit 02040049
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-22 Cont ID  
Sent By dpalmer Date 2002-05-22 Time 17:18 Rev Time 0.00
Received By dpalmer Date 2002-05-22 Time 17:18 Sent To  
Notes
2002-05-22 00:00:00************ NOTE ************
  
 1 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
  
 REVISE BEFORE INSPECTION

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-25 Cont ID  
Sent By dpalmer Date 2002-04-25 Time 13:33 Rev Time 0.00
Received By dpalmer Date 2002-04-25 Time 13:33 Sent To P
Notes
2002-04-25 00:00:00***************** UNSAT ****************
  
  
 1)NOTE: PLEASE NOTE THAT THE CODE ARTS
 REF ARE STILL FROM 96 NEC. PLEASE
 MAKE CHANGES TO REFLECT 99 NEC.
  
 2 )NOTE: PLEASE CLARIFY EQUIPMENT
 GROUNDING METHOD BETWEEN FIRST MEANS
 OF DISCONNECT AND PANELS. PLEASE SIZE
 CONDUCTORS PER 250-122.
  
 3)NOTE: PLEASE NOTE MISSING OUTLET FOR
 A/C EQUIPMENT. PER 210-63 AND/OR SECTION
 306 OF THE MECHANICAL CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-11-21 Cont ID  
Sent By hmoser Date 2002-11-21 Time 15:58 Rev Time 0.50
Received By hmoser Date 2002-11-21 Time 15:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-08-12 Cont ID  
Sent By hmoser Date 2002-08-12 Time 17:55 Rev Time 0.50
Received By hmoser Date 2002-08-12 Time 17:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-24 Cont ID  
Sent By hmoser Date 2002-04-24 Time 18:19 Rev Time 0.50
Received By hmoser Date 2002-04-24 Time 18:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-27 Cont ID  
Sent By dpalmer Date 2002-04-25 Time 13:37 Rev Time 0.33
Received By jleech Date 2002-04-27 Time 11:17 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-05-06 Cont ID  
Sent By lhatten Date 2002-05-06 Time 13:54 Rev Time 2.50
Received By lhatten Date 2002-05-01 Time 13:40 Sent To  
Notes
2002-05-06 00:00:00REVIEW & STAMPED PLANS 05/01/2002
 CALC. FEES05/06/2002

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-08 Cont ID  
Sent By sgraham Date 2002-04-08 Time 07:55 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***