Plan Review Details - Permit 02040047
Plan Review Stops For Permit 02040047
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-04-29 Cont ID  
Sent By rmcdouga Date 2002-04-29 Time 16:01 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-04-29 00:00:00OK PER L.SMITH 4-29-02

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-22 Cont ID  
Sent By kstevens Date 2002-05-07 Time 08:29 Rev Time 0.00
Received By btrobaug Date 2002-04-22 Time 16:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-08 Cont ID  
Sent By kstevens Date 2002-05-08 Time 11:48 Rev Time 0.00
Received By kstevens Date 2002-05-08 Time 11:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-21 Cont ID  
Sent By kstevens Date 2002-04-21 Time 17:21 Rev Time 0.00
Received By kstevens Date 2002-04-21 Time 17:21 Sent To E
Notes
2002-04-21 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 PRIVATE POOLS
  
 1) PLEASE ADJUST GENERAL NOTES AND DE-
 TAILS AS FOLLOWS.
 A) PLEASE SHOW SLAB TO BE NOMINAL 4 INCH
 THICK.
 B)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 C)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 D)
 FBC-2001 SEC 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 E)
 FBC-2001 SEC 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
 2) FOR FUTURE REFERENCE THE FOLLOWING
 INFORMATION REQUIRED ON PLANS WHEN A
 POOL HEATER IS INSTALLED.
 A)
 FBC-2001 SEC 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 B)
 FBC-2001 SEC 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 C)
 FBC-2001 SEC 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 D)
 FBC-2001 SEC 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-09 Cont ID  
Sent By sgraham Date 2002-04-09 Time 08:05 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***