Plan Review Details - Permit 02031914
| Plan Review Stops For Permit 02031914 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-06-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-06 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-06 |
Time |
16:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-05-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-29 |
Time |
17:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-29 |
Time |
17:45 |
Sent To |
|
|
| Notes |
| 2002-05-29 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT ON E-6 CHANGES | | | WERE MADE TO CLARIFY VOLTAGE FOR PUMPS. | | | PLEASE ALSO NOTE THAT TWO PUMPS ARE | | | STILL SHOWN AS 120VOLT. (MISPRINT) | | | PLEASE EITHER SHOW WHERE GFI PROTECTION | | | IS MET AND/OR IF INDEED LOW VOLTAGE. | | | 680-51 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-04-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-04-29 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-04-29 |
Time |
08:29 |
Sent To |
|
|
| Notes |
| 2002-04-29 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | | LOADS AND LARGEST MOTOR LOADS AT 125%. | | | PLEASE NOTE THAT LOAD CALCUALTIONS NEED | | | TO BE SHOWN. 215-2/3, 230-42, 430 ETC. | | | | | | 2)NOTE: PLEASE NOTE THAT GFI PROETCION | | | FOR ALL SUBMERSIBLE PUMPS. 680-51 | | | | | | 3)NOTE: PLEASE NOTE COLOR CODING OF 277V | | | /480V PER LOCAL AMENDMENTS.215-2 | | | BROWN/ PURPLE/ YELLOW. | | | | | | 4)NOTE: PLEASE NOTE THAT MEANS OF | | | CONTROLLING OF LIGHTS IN PUMP ROOM ALSO, | | | NOT JUST AT THE TOP OF THE STAIRS | | | OUTSIDE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | | | | PLEASE NOTE WRONG BLDG CODE REFERENCED, | | | SHOWS 1997 AND SHOULD BE 2001. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-05-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-07 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-07 |
Time |
14:25 |
Sent To |
|
|
| Notes |
|
|
|