| Plan Review Stops For Permit 02031841 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-04-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-04-03 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-04-03 |
Time |
17:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-04-01 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-04-01 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-04-01 |
Time |
13:07 |
Sent To |
|
|
| Notes |
| 2002-04-01 00:00:00 | ****************** UNSAT *************** | | | NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|
|
|