Plan Review Details - Permit 02031690
Plan Review Stops For Permit 02031690
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-04-15 Cont ID  
Sent By hpiskura Date 2002-04-15 Time 14:04 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-21 Cont ID  
Sent By dpalmer Date 2002-05-21 Time 19:58 Rev Time 0.00
Received By dpalmer Date 2002-05-21 Time 19:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-11 Cont ID  
Sent By dpalmer Date 2002-04-11 Time 06:49 Rev Time 0.00
Received By dpalmer Date 2002-04-11 Time 06:49 Sent To  
Notes
2002-04-11 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT TWO DIFFERENT
 E-SHEETS WERE SUBMITTED? PLEASE NOTE
 THAT BOTH HAVE THE SAME DATE AND ARE
 NOT DATED BY ARCH? PLEASE ONLY SUBMIT
 THE LATEST ONE TO BE REVIEWED.
  
 2)NOTE: PLEASE NOTE THAT ALL BRANCH
 CIRCUITING #`S ARE TO BE SHOWN ON PLANS
 AND CORRELATE WITH A SUBMITTED PANEL
 SCHEDULE.
  
 3)NOTE: PLEASE SHOW SIZE OF EXISTING
 PANEL IN ORDER TO VERIFY LOAD TO SERVICE
 SIZE.
  
 4)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 OUTLETS PER 210-62
  
 5)NOTE: PLEASE CLARIFY REQ`D SIGN
 CIRCUIT PER 600-5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-05-13 Cont ID  
Sent By lsmith Date 2002-05-13 Time 08:43 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-05-17 Cont ID  
Sent By mcarsill Date 2002-05-17 Time 13:11 Rev Time 0.00
Received By mcarsill Date 2002-05-17 Time 13:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-04-04 Cont ID  
Sent By mcarsill Date 2002-04-04 Time 17:04 Rev Time 0.00
Received By mcarsill Date 2002-04-04 Time 17:04 Sent To  
Notes
2002-04-04 00:00:00A) FIRE SPRINKLER HEADS REQUIRED IN
 REFRIGERATOR AND FREEZER.
 B) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 C) PLEASE PROVIDE INFORMATION ON
 DUKE OVEN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-28 Cont ID  
Sent By pkrauss Date 2002-05-28 Time 16:20 Rev Time 0.45
Received By pkrauss Date 2002-05-28 Time 16:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-10 Cont ID  
Sent By pkrauss Date 2002-04-10 Time 12:00 Rev Time 0.45
Received By pkrauss Date 2002-04-10 Time 12:00 Sent To  
Notes
2002-04-10 00:00:00 
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC, MECHANICAL TABLE
 403.3 OR ASHRAE 62-89.
  
 2.PROVIDE MANUFACTURER SUBMITTAL DATA
 OVEN.
  
 3.PROVIDE MANUFACTURER INFORMATION
 FOR THE NEW 4 TON RTU. (MAKE, MODEL
 BTU, SEER).
  
 4.INDICATE CFM DISTRIBUTION ON PLAN.
  
 3.ADDITIONAL PERMITS REQUIRED FOR WALK
 IN FREEZER/COOLER, HOOD AND FIRE
 SUPRESSION.PLEASE PROVIDE PLANS &
 MANUFACTURER SUBMITTAL DATA WITH
 PERMIT APPLILCATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-01 Cont ID  
Sent By jleech Date 2002-06-01 Time 13:31 Rev Time 0.75
Received By jleech Date 2002-06-01 Time 13:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-30 Cont ID  
Sent By jleech Date 2002-04-30 Time 17:33 Rev Time 2.00
Received By jleech Date 2002-04-30 Time 17:33 Sent To  
Notes
2002-04-30 00:00:00DENIED;
 1.WOMENS TOILET ROOM DOES NOT MEET
 MINIMUM INSIDE WIDTH.
 2.URINAL TO MEET FACBC REQUREMENTS SEE
 SEC 11-4.18.1 THRU11-4.18.4. SHOW
 DETAIL ON DRAWING.
 3.GREASE TRAP TO BE SIZED AND LOCATED BY
 RODNEY COMPO UTILITY DEPARTMENT PHONE
 837-4074 SPECIFICATIONS WILL BE
 REQUIRED, SIZE MANUFACTOR, CERTIFIED
 BY ETC.
 4.ALL INDIRECT WASTE TO FLOOR SINKS ICE
 MAKER, SODA DISPENSOR ETC.
 5.HOT WATER TO HAND SINKS AND LAVITORIES
 TO BE 110 DEG. IF HOTTER WATER IS
 REQUIRED FOR 3 COMPARTMENT SINK SHOW
 TEMPORING VALVE.
 6.SHOCK ARRESTORS REQUIRED WITH SEC.
 604.9.
 7.PAGE M2.0 RISER DIAGRAM. SHOW CLEAR
 SEPORATION OF GREASY WASTE AND
 SANITARY PIPING. W/C AND URINAL CANNOT
 GO THRU GREASE TRAP.
 8.WHAT TYPE FIXTURE IS ABOVE URINAL. NOT
 MARKED.
 9.FLOOR DRAINS REQUIRED WITH TRAP PRIMER
 IN REST ROOMS.
  
 10.RISER DIAGRAM SHOWS 3 LAVS AND 3 W/C
 AND MISSING SERVICE SINK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop Z ZONING
Rev No 1 Status N Date 2002-05-13 Cont ID  
Sent By lsmith Date 2002-05-13 Time 08:44 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***