| 2002-04-26 00:00:00 | THE GENERAL NOTES ON SHEET A1 OF THE |
| | PLANS DECLARE TYPE V UNPROTECTED |
| | CONSTRUCTION AND A NFPA 13D FIRE |
| | SPRINKLER SYSTEM.FOOTNOTE (D) TO |
| | TABLE500 PROHIBITS A 13D OR 13R SYSTEM |
| | FOR HEIGHT MODIFICATIONS. |
| | |
| | THE BUILDINGS MUST BE EITHER 1 HOUR |
| | PROTECTED WITH A 13D SYSTEM OR A FULL |
| | 13 SYSTEM TO BE THREE STORIES.PLEASE |
| | REVISE AS NECESSARY. |
| | |
| | SECTIONS ON SHEET A6 SHOW AN EXISTING |
| | RETAINING WALL.THE PROPOSED PROBERTY |
| | LINES SHOW THE RETAINING WALL FOOTING |
| | TO BE ENCROACHING ON THE NEIGHBORING |
| | PROPERTY.PROVIDE A METHOD TO RESOLVE |
| | OWNERHIP AND RESPONSIBILITY. |
| | |
| | SAME.PROVIDE AN ENGINEERING ANALYSIS |
| | OF THE SUITABILITY OF THE EXISTING |
| | WALL TO ASSUME THE ADDED FOUNDATION |
| | LOADS OF THE BUILDINGS.INCLUDE THE |
| | WATER PROOFING AND/OR DAMP PROOFING |
| | REQUIRED BY SBC 1814.1 |
| | |
| | BUILDINGS NUMBERED 1,4,6, AND 7 HAVE |
| | EXTERIOR WALL OPENINGS EXCEEDING THE |
| | 40% ALLOWED BY SBC TABLE 600 ON UNITS |
| | LABELED "E".PLEASE REVISE AS |
| | NECESSARY. |
| | |
| | WITH AN ASSUMED PROPERTY, THERE IS NONE |
| | INDICATED ON THE PLANS, BETWEEN |
| | BUILDINGS PAIRED, 1&2 2&3 3&4 ETC. THE |
| | ALLOWABLE EXTERIOR WALL OPENINGS FOR |
| | TABLE 600 ARE EXCEEDED.PLEASE REVISE |
| | AS NECESSARY. |
| | |
| | PLEASE PROVIDE THE SOIL REPORTS FOR |
| | THESE BUILDINGS.SEE SBC 104.2. |
| | |
| | PROVIDE THE NOTICE OF ACCEPTANCE AND |
| | TEST REPORTS FOR THE WINDOWS, DOORS AND |
| | ROOF COVERING. |
| | |
| | SHOW THE SOIL TERMITE TREATMENT IN |
| | ACCORDANCE WITH SBC 2304 AS AMENDED BY |
| | THE CITY. |
| | |
| | SHEET S2 CITES ASCE 7-98, THE 1997 SBC |
| | INVOKES ASCE 7-95.PLEASE REVISE |
| | ACCORDINGLY AND DEMONSTRATE COMPLIANCE |
| | WITH 7-95.ALTERNATIVELY, REVISE THE |
| | BUILSDINGS TO COMPLY WITH THE 2001 FBC. |
| | |
| | THE EMERGENCY EGRESS FOR BUILDINGS 8 |
| | AND12 INTO THE ENCLOSED COURTYARD DOES |
| | NOT MEET THE RESCUE REQUIREMENTS OF SBC |
| | 1005.4.PLEASE REVISE AS NECESSARY. |
| | |
| | SEPARATE SURVEYS ARE REQUIRED FOR EACH |
| | TOWNHOUSE UNIT. |
| | |
| | GIVEN THE SIZE AND SCOPE OF THIS PROJECT |
| | A RESIDENT INSPECTOR WILL BE REQUIRED. |
| | CONTACT DON NEELY AT 561-659-8096 EXT |
| | 8333 FOR MORE INFORMATION. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY, THE PERMIT PLANS |
| | STAMPEDBY THAT OFFICE, AND A COPY OF |
| | THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. |