Plan Review Details - Permit 02031587
Plan Review Stops For Permit 02031587
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-13 Cont ID  
Sent By jwitmer Date 2002-05-13 Time 15:26 Rev Time 1.75
Received By jwitmer Date   Time   Sent To  
Notes
2002-05-13 00:00:00*****BUILDING PROVISO******
 PERMIT # 02031587
 265 GRANADA RD
 CONT: BRANCH CONT
 TEL: 833-6206
  
 1) STORM SHUTTER PROTECTION FOR THE (3)
 OPENINGS SHALL REQUIRE A SEPERATE PERMIT
 WITH ASSOCIATED FEES, BEFORE THE CERTIFI
 CATE OF COMPLITION SHALL BE ISSUED.
  
 2) SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE DESIGN
 PROFESSIONAL OF RECORD.FOR FRENCH DOORS
 AND WINDOWS, BEFORE FRAMING INSPECTION,
 A SEPERATE PERMIT SHALL BE REQUIRED.
  
 3)1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS. ATTACHMENT SCHEDULE
 FROM THE DESIGN PROFESSIONAL BY TIME
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-25 Cont ID  
Sent By pkrauss Date 2002-04-15 Time 13:00 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-25 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02031587
 265 GRANADA ROAD
 CONT: BRANCH CONST
 TEL: 833-6206
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SHEET 2 OF 4 STRUCTURAL NOTES :
 SBC 1205 @ 140 MPH WIND NOT THE SOUTH
 FL CODE, 2001 FL BLD CODE
 2) SAME CODE DATA INDICATES THE 1997
 STANDARD BUILDING CODE WRONG, 2001
 FL BLD CODE
 3) THE PLANS INDICATE A 32"WX 20"H
 ACCESS FOR THE EXISTING CRAWL SPACE THAT
 WILL BE COVERED BY THE NEW ADDITION,
 HOW WILL ACCESS BE GAINED?
 4) SHEET 2 ALSO DETAILS A CONCRETE
 STAIR,FL BLD CODE 1012.1.5 REQUIRES A
 MINIMUM OF A 3'-0" LANDING BEFORE THE
 STAIRS BEGIN, THE LANDING MAY BE 7"
 LOWER THAN THE INSIDE FLOOR LEVEL.
 5)- THE SAME DETAIL, HANDRAILS FL BLD
 CODE1007.5.1 HANDRAILS ARE REQUIRED WHEN
 THERE IS 4 OR MORE RISERS ABOVE FLOOR OR
 FINISHED GRADE
 6) FL BLD CODE 1007.5.2 STAIRWAYS SHALL
 HAVE HANDRAILS ON BOTH SIDES, EXCEPTION
 IS WITHIN DWELLING UNIT.
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
 WOOD DOUBLE HUNG WINDOW
 WOOD FRENCH DOORS
 TRANSOM ABOVE
 MULLIONS
 8) SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE DESIGN
 PROFESSIONAL OF RECORD. IF PRODUCT
 TESTING ISN'T AVAILABLE. SEE ADDITIONAL
 INFORMATION.
 9) FLBLD CODE 1511.6.4.3 EMERGENCY OVER-
 FLOW FOR ROOF, SCUPPER ARE TO BE PLACED
 LEVEL WITH ROOF, OVERFLOW SHALL NOT BE
 PLACED LESS THAN 2" ABOVE ROOF LEVEL &
 NOT MORE THAN 4".
 10-PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 1997 FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION.
 11-IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-05 Cont ID  
Sent By dpalmer Date 2002-04-05 Time 06:12 Rev Time 0.00
Received By dpalmer Date 2002-04-05 Time 06:11 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-15 Cont ID  
Sent By pkrauss Date 2002-04-15 Time 12:04 Rev Time 0.45
Received By pkrauss Date 2002-04-15 Time 11:59 Sent To B
Notes
2002-04-15 00:00:00MECHANICAL PERMIT 02031592

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-12 Cont ID  
Sent By dpalmer Date 2002-04-05 Time 06:12 Rev Time 0.00
Received By kstevens Date 2002-04-12 Time 20:08 Sent To  
Notes
2002-04-12 00:00:00PASSED/PROVISO
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR
 GAS.SEPARATE PLUMBING PERMIT REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-03 Cont ID  
Sent By sgraham Date 2002-04-03 Time 14:55 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***