Plan Review Details - Permit 02031565
| Plan Review Stops For Permit 02031565 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-06-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-27 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-06-27 |
Time |
10:28 |
Sent To |
FIRE |
|
| Notes |
| 2002-03-27 00:00:00 | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | AND RESUBMIT FOR REVIEW: | | | | | | 1} INDICATE THE LOCATION OF THE MAIN | | | DISCONNECTS FOR THE BUILDING,AND THE | | | NUMBER OF SAME. | | | | | | 2} DIAGRAM SHOWS THE GENERATOR FEEDING | | | A SINGLE PHASE TRANSFER SWITCH, PLEASE | | | CLARIFY THE TYPE OF GENERATOR BEING | | | USED. | | | | | | 3} THE DRAWING INDICATES THE TWO EXISTIN | | | G TENENT SPACE PANELS TO BE "MLO",PLEASE | | | CLARIFY. | | | | | | 4} INDICATE IF THE GENERATOR IS TO BE | | | USED AS A SEPERATELY DERIVED SYSTEM AS | | | PER250-20(D). | | | | | | 5} THE DISCONNECT FOR THE LOAD OF THE | | | GENERATOR IS INDICATED AS BEING "IN | | | UNIT".THIS WOULD TYPICALLY BE LOCKED.IS | | | THIS THE ONLY MEANS BEING PROPOSED? | | | IS THIS GROUPED WITH THE OTHER MEANS OF | | | DISCONNECTS PER 230-72? | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT.8392 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
N |
Date |
2002-06-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-06-27 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-06-07 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2002-06-07 00:00:00 | CONTRACTOR WAS CALLED TO COME PICK | | | UP PLANS. NO FOLLOW-UP INFORMATION | | | WAS EVER PROVIDED BY CONTRACTOR. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-03-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-27 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-28 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2002-03-28 00:00:00 | A) WHAT IS THE GENERATOR TO BE USED FOR. | | | B) MORE DETAILS REQUIRED ON PROPANE | | | TANK. WHAT SIZE, WHAT PROTECTION, WHAT | | | DISTANCE, WHAT PIPING, ARE TO BE | | | PROVIDED FOR THE PROPANE TANK. | | | C) WHERE ARE THE PROPERTY LINES | | | LOCATED. | | | D) ANY OPENINGS FOR THE BUILDING LOCATED | | | NEAR THE PROPANE TANK. | | | E) PLEASE INDICATE ANY PROPERTY LINES | | | NEAR THE CONCRETE PAD PLANNED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|