Plan Review Details - Permit 02031545
Plan Review Stops For Permit 02031545
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-09-20 Cont ID  
Sent By hpiskura Date 2002-09-20 Time 09:11 Rev Time 0.00
Received By hpiskura Date 2002-09-20 Time 09:11 Sent To  
Notes
2002-09-20 00:00:00REV 2 HORN STROBE LOCATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2002-07-30 Cont ID  
Sent By lmartine Date 2002-07-30 Time 13:54 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-07-12 Cont ID  
Sent By lmartine Date 2002-07-12 Time 09:47 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-07-12 00:00:00REVIEWED WITH HAROLD , OK TO APPROVE

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-06-13 Cont ID  
Sent By hpiskura Date 2002-06-13 Time 17:51 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-06-13 00:00:00PLEASE PROVIDE A SITE PLAN SO THAT
 COMPLIANCE WITH FBC TABLE 600 FOR THE
 NEW OPENINGS MAY BE DETERMINED.
  
 A SEPARATE PERMIT AND INFORMATION WILL
 BE REQUIRED TO INSTALL THE NEW WINDOWS
 AND DOORS IF THE TEST AND EVALUATION
 REPORTS ARE NOT INCLUDED WITH THIS
 PERMIT.
  
 A RECORDED COPY OF THE NOTICE
 COMMENCEMENT IS REQUIRED BEFORE A
 PERMIT TO CONSTRUCT MAY BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-18 Cont ID  
Sent By hpiskura Date 2002-04-18 Time 16:36 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-18 00:00:00WHAT IS THE NATURE OF THE PRODUCT AND/OR
 WORK PROCESSES THAT TAKE PLACE IN THE
 BUILDING?SEE FBC 303.1 EXCEPTIONS.
  
 IS THIS A SINGLE TENANT BUILDING?
  
 PLEASE PROVIDE A SITE PLAN WITH
 DIMENSIONS SO THAT COMPLIANCE WITH FBC
 TABLE 600MAY BE DETERMINED WITH REGARDS
 TO THE NEW OPENINGS IN THE EXTERIOR
 WALLS.
  
 IF PRODUCT APPROVALS AND/OR THE
 APPROPRIATE TEST REPORTS FOR THE DOORS
 AND WINDOWS ARE NOT INCLUDED WITH THE
 PERMIT APPLICATION, A SEPARATE PERMIT,
 WITH THE ATTENDANT FEES WILL BE
 REQUIRED.
  
 INCLUDE A BRIEF LIFE SAFETY PLAN SHOWING
 EGRESS FROM THE NEWLY DEMISED PORTION
 OF THE BUILDING.SEE FBC 1001.2.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-09-16 Cont ID  
Sent By btrobaug Date 2002-09-16 Time 15:04 Rev Time 1.00
Received By btrobaug Date 2002-09-16 Time 13:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-08-13 Cont ID  
Sent By btrobaug Date 2002-08-13 Time 17:17 Rev Time 0.00
Received By btrobaug Date 2002-08-13 Time 16:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-07-30 Cont ID  
Sent By dpalmer Date 2002-07-30 Time 11:25 Rev Time 0.00
Received By dpalmer Date 2002-07-30 Time 11:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-06-12 Cont ID  
Sent By dpalmer Date 2002-06-12 Time 06:22 Rev Time 0.00
Received By dpalmer Date 2002-06-12 Time 06:22 Sent To  
Notes
2002-06-12 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NOTHING WAS
 SUBMITTED TO ADDRESS COMMENTS FROM FIRST
 REVIEW. PLEASE NOTE COVER SHEET FOR "NEW
 SHEETS MENTION E-1,E-2,E-3 BUT NONE
 SUBMITTED.
  
 PLEASE SUBMIT FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-11 Cont ID  
Sent By dpalmer Date 2002-04-11 Time 13:40 Rev Time 0.00
Received By dpalmer Date 2002-04-11 Time 13:40 Sent To  
Notes
2002-04-11 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE CLARIFY ANY CIRCUITING
 REQ`D PER 600-5.
  
 2)NOTE: PLEASE CLARIFY ROOM USES. PLEASE
 LABEL ON PLANS. PLEASE CLARIFY IF ROOM
 WITH TRACK LIGHTING IS SOME SORT OF
 "SHOW WINDOW"?
 PLEASE NOTE 210-62 IF INDEED USED FOR
 SHOW/DISPLAYING OF ITEMS/GOODS. ART 100.
  
 3)NOTE: PLEASE CLARIFY AHU #1 AND #3 ??
 PLEASE NOTE THAT #1 SHOWS 11.5KW AND
 #3 IS SHOWN WITH THE SAME LOAD AS #1
 WITH LESS OCP AND SMALLER WIRE SIZES.??
  
 4))NOTE: PLEASE NOTE THAT THE LOAD
 CALCULATIONS NEED TO BE SHOWN. SQ FT/
 RECEPT LOADS ETC. PER 220-3,220-10,
 220-11, 220-13. (215-5)
  
 5)NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
 215-2,215-3,230-42
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-09-19 Cont ID  
Sent By mcarsill Date 2002-09-19 Time 16:46 Rev Time 0.00
Received By mcarsill Date 2002-09-19 Time 16:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-07-11 Cont ID  
Sent By mcarsill Date 2002-07-11 Time 15:53 Rev Time 0.00
Received By mcarsill Date 2002-07-11 Time 15:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-06-19 Cont ID  
Sent By mcarsill Date 2002-06-19 Time 14:31 Rev Time 0.00
Received By mcarsill Date 2002-06-19 Time 14:31 Sent To  
Notes
2002-06-19 00:00:00REQUIRED INFORMATION TO PERFORM PLAN
 REVIEW STILL MISSING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-04-11 Cont ID  
Sent By mcarsill Date 2002-04-11 Time 08:33 Rev Time 0.00
Received By mcarsill Date 2002-04-11 Time 08:33 Sent To  
Notes
2002-04-11 00:00:00A) PLEASE INDICATE WHAT WILL BE STORED
 WITHIN THE BUILDING. THE PLANS INDICATE
 S-2 OCCUPANCY.
 B) PLEASE INDICATE ALL EXIT DOOR
 LOCATIONS FOR THE BUILDING. THE KEY PLAN
 COULD REFLECT MULTIPLE TENANT
 ARRANGEMENT OR A SINGLE TENANT, PLEASE
 EXPLAIN.
 C) BUILDING ADDRESS REQUIRED ON
 BUILDING.
 D) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFORMATION.
 E) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL.
 F) NO FIRE ALARM EQUIPMENT SHOWN. ARE
 ANY DEVICES PLANNED FOR THE SPACE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-08-19 Cont ID  
Sent By pkrauss Date 2002-08-19 Time 09:34 Rev Time 0.40
Received By pkrauss Date 2002-08-19 Time 09:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-11 Cont ID  
Sent By pkrauss Date 2002-06-11 Time 13:42 Rev Time 0.40
Received By pkrauss Date 2002-06-11 Time 13:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-12 Cont ID  
Sent By pkrauss Date 2002-04-12 Time 13:56 Rev Time 0.50
Received By pkrauss Date 2002-04-12 Time 11:03 Sent To  
Notes
2002-04-12 00:00:00 
 1.AS PER 2001 FMC, OUTSIDE AIR EXHAUST
 AND INTAKE OPENINGS SHALL BE LOCATED
 A MINIMUM OF 10 FT FROM LOT LINES OR
 BUILDINGS ON THE SAME LOT. FBC 401.5
  
 2.FMC 401.5.2, EXHAUST AIR SHALL NOT
 BE DIRECTED ONTO WALKWAYS.
  
 3.SEE FIRE DEPARTMENTS COMMENTS AS TO
 STORAGE WITHIN THE BUILDING.
  
 4.CLARIFY LOCATION AND SEPARATION OF
 THE OUTSIDE AIR IN REFERENCE TO THE
 EHXAUST OF CONDENSERS.
  
 PROVISO:
  
 AS PER 2001 FBC 1503.4.4, CONDENSATE
 SHALL DISCHARGE A MINIMUM OF 12 INCHES
 FROM THE BUILDING STRUCTURE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-07-30 Cont ID  
Sent By kstevens Date 2002-07-30 Time 13:13 Rev Time 0.00
Received By kstevens Date 2002-07-30 Time 13:13 Sent To  
Notes
2002-07-30 00:00:00PASSED/PROVISO
  
 EXISTING DRINKING FOUNTAIN/SERVICE SINK
 IN WAREHOUSE - MIN 5'3" IN HDCP TOILET
 ROOM WIDTH.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-06-27 Cont ID  
Sent By kstevens Date 2002-06-27 Time 19:43 Rev Time 0.00
Received By kstevens Date 2002-06-27 Time 19:43 Sent To  
Notes
2002-06-27 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) FROM PREVIOUS REVIEW: SHT P-2 WATER
 HAMMER ARRESTORS SHALL BE REQUIRED FOR
 QUICK CLOSING VALVES AND LOCTED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE" NOT AT
 TOP OF DROP AS SHOWN. SEC 604.9
 2) SHT P-2 PLUMBING NOTES #13 AIR
 CHAMBERS NOT APPROVED. DELETE REFERENCE
 3) FROM PREVIOUS REVIEW: TOILET ROOMS
 ARE NOT WIDE ENOUGH. MINIMUM WITH IS
 5'3". SEE SHT A-4 DETAILS ALSO
 4) SHT A-2 SNACK ROOM SINK TO COMPLY
 WITH 11-4.24.1 THRU 11-4.24.7 PLEASE
 PROVIDE DETAILS. FROM PREVIOUS REVIEW.
 ------NEW COMMENTS------
 5) PER TABLE 403.1, A DRINKING FOUNTAIN
 AND A SERVICE SINK IS REQUIRED. PLEASE
 SHOW FIXTURES ON RESUBMITTED PLANS.
 6) PLEASE REMOVE ALL VOIDED/SUPERSEDED
 SHEETS AND PLACE NEW SHEETS IN PLAN FOR
 REVIEW. RESUBMIT ONE SET OF OLD SHEETS
 FOR COMPARISON SEPARATE FROM NEW COMPLE-
 TE SET.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-30 Cont ID  
Sent By jleech Date 2002-04-30 Time 13:56 Rev Time 1.00
Received By jleech Date 2002-04-30 Time 13:56 Sent To  
Notes
2002-04-30 00:00:00DENIED;
 1.PAGE P-2 NOTE 13. APPROVED ENGINEERED
 SHOCK ARRESTORS ARE REQUIRED. SEE SEC.
 604.9.
 2.PAGE A-2 BATHROOM WIDTHS ARE TOO SMALL
 SIZE PER HANDICAP TOILET ROOM DETAILS
 ON PAGE A-4.
 3.SNACK ROOM SINK TO COMPLYWITH FACBC
 SEC. 11-424.1 THRU 11-24.7. SHOW
 DETAIL.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369


Account Summary | Usage Policy | Privacy Policy