Plan Review Details - Permit 02031521
| Plan Review Stops For Permit 02031521 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-04-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-04-19 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-04-19 |
Time |
14:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-04-15 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-04-15 |
Time |
07:13 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-04-15 |
Time |
06:38 |
Sent To |
|
|
| Notes |
| 2002-04-15 00:00:00 | ******************UNSAT!**************** | | | 1)NOTE: PLEASE NOTE THAT ALL PLANS | | | THAT ARE SIGNED AND SEALED BY ARCH/ OR | | | ENGINEER ARE REQ`D PER 61G15-23.002 FOR | | | ENGINEER AND 61G1-16.004 FOR ARCH. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-04-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-04-09 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-04-09 |
Time |
15:05 |
Sent To |
FIRE |
|
| Notes |
| 2002-04-09 00:00:00 | *****************UNSAT****************** | | | | | | PLEASE GIVE NAMEPLATE RATINGS OF | | | EQUIPMENT AND HOW BEING FED,ALSO LOW | | | VOLTAGE FEEDS TO BE SHOWN ON DRAWINGS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-05-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-10 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-10 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2002-05-10 00:00:00 | 1) PLEASE BE ADVISED THAT A MINIMUM OF | | | AT LEAST SEVEN AND HALF FEET CLEARANCE | | | IS REQUIRED TO THE FRONT AND SIDES OF A | | | FIRE HYDRANT. FOUR FEET IS REQUIRED TO | | | THE REAR OF THE HYDRANT. EQUIPMENT FOR | | | THE GATE CANNOT INTERFERE WITH THESE | | | REQUIREMENTS. | | | | | | 2) APPROPRIATE SIGNAGE IS REQUIRED FOR | | | THE GATE THAT FIRE RESCUE IS EXPECTED | | | TO USE ON THE NORTH SIDE. | | | | | | 3) ALL OPENINGS THAT FIRE RESCUE ARE | | | EXPECTED TO USE MUST BE AT LEAST | | | TWENTY FEET IN CLEAR WIDTH. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-04-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-04-10 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-04-10 |
Time |
12:28 |
Sent To |
|
|
| Notes |
| 2002-04-10 00:00:00 | A) WHAT PROVISIONS HAVE BEEN MADE FOR | | | FIRE AND PARAMEDICAL ACCESS. THE CUT | | | SHEET BOOKLET DOES CONTAIN KNOX-BOX | | | KEY SWITCH INFORMATION BUT IS IT | | | SPECIFIC FOR THIS JOB. | | | B) WHAT PROVISIONS HAVE BEEN MADE FOR | | | THE SECURITY DEVICES IF ELECTRICAL | | | POWER IS LOST. ARE THE SECURITY | | | EQUIPMENT FAIL SAFE OR FAIL SECURE. | | | C) THE NEW EQUIPMENT DOES NOT ALLOW | | | FOR 20 FEET IN CLEAR WIDTH. THE NEW | | | SECURITY FEATURES MUST BE PROPER IN | | | DESIGN AND FUNCTION AS THE EXISTING | | | EQUIPMENT DID NOT MEET NEEDS OF THE | | | FIRE RESCUE DEPARTMENT. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2002-04-09 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-04-09 |
Time |
11:45 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2002-04-04 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-04-04 |
Time |
08:21 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|