Plan Review Details - Permit 02031486
Plan Review Stops For Permit 02031486
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-07-11 Cont ID  
Sent By btrobaug Date 2002-07-11 Time 08:12 Rev Time 0.00
Received By btrobaug Date 2002-07-11 Time 06:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-26 Cont ID  
Sent By btrobaug Date 2002-04-26 Time 12:40 Rev Time 0.00
Received By btrobaug Date 2002-04-26 Time 15:57 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-28 Cont ID  
Sent By btrobaug Date 2002-03-28 Time 14:40 Rev Time 0.00
Received By btrobaug Date 2002-03-28 Time 14:19 Sent To M
Notes
2002-03-28 00:00:00*************** PROVISO ****************
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 AND RESUBMIT FOR REVIEW.
  
  
 1} PROVIDE A CALCULATION FOR THE
 ADDITIONAL LOAD BEING ADDED TO THE
 SERVICE PER 220-31.
  
 2} PLEASE SHOW THE PATH OF THE REROUTED
 CONDUIT TO THE POOL EQUIPMENT,AND THE
 SIZE AND NUMBER OF THE CONDUCTOR IT
 CONTAINS.
  
 3} INDICATE HOW THE NEW BUILDING IS
 BEING FED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL:
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-05-21 Cont ID  
Sent By btrobaug Date 2002-03-28 Time 15:23 Rev Time 0.25
Received By hmoser Date 2002-03-29 Time 09:43 Sent To  
Notes
2002-05-21 00:00:00CALLED TO PICKUP PERMIT.PERMIT IN BOX E
 H.M.5/21/02
2002-03-29 00:00:00*************NO INFO INCLUDED***********
  
 MECHANICAL PERMIT REQUIRED FOR A/C WORK
 AHU IN ATIC TO HAVE SERVICE SIDE OF
 EQUIPMENT WITHIN 6' OF ATTIC ACCESS.
  
 MECHANICALBATHROOM EXHAUST REQUIRED

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-04-18 Cont ID  
Sent By kstevens Date 2002-04-18 Time 19:53 Rev Time 0.00
Received By kstevens Date 2002-04-18 Time 19:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-07-10 Cont ID  
Sent By jwitmer Date 2002-07-10 Time 16:10 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-07-10 00:00:00REVISION #2 MAY 2002

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-04-29 Cont ID  
Sent By btrobaug Date 2002-04-26 Time 16:01 Rev Time 0.00
Received By jwitmer Date 2002-07-08 Time 15:56 Sent To  
Notes
2002-04-29 00:00:00*******BUILDING PROVISO******
 PROVIDE PRODUCT APPROVAL (2) COPIES OF
 THE FOLLOWING:
 A) OVERHEAD GARAGE DOOR
 B) MULLION REPORT
 BEFORE FRAMING INSPECTION
 FL BLD CODE 424.17.1.9 POOL BARRIER ACT
 DEMONSTRATE CODE COMPLIANCE BEFORE
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-04-16 Cont ID  
Sent By btrobaug Date 2002-04-26 Time 13:06 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-16 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02031486
 200 FLAGLER LANE
 CONT: FRANK HADERCONST
 TEL: (561)735-3114
  
 FL BLDG CODE= 2001 FLORIDA BUILDING CODE
  
 1)- FL BLDG CODE 1606.1.7 INFORMATION ON
 DRAWINGS RELATED TO WIND IS MISSING, SEE
 CODE SECTION, NEW!
 2)- EXTERIOR WINDOWS & DOORS SHALL BE
 TESTEDD FOR WIND, TEST REPORTS SHALL
 INDICATE THE TEST PRESSURE & DESIGN
 PRESSURE. SBCCI OR DADE COUNTY REPORTS
 ARE ACCEPTED.FL BLDG CODE 1707.4.1.
 SEE NEW CODE SECTIONS 1707.4.2/1704.2.2
 3)- EXTERIOR DOOR ASSEMBLIES: SBCCI OR
 DADE COUNTY PRODUCT APPROVAL FOR EACH
 TYPE OF DOOR CONFIGURATION.
 4)- 1707.4.5 MULLIONS BETWEEN INDIVIDUAL
 WINDOWS AND DOOR ASSEMBLIES.
 5)- 1707.5 ROOF TILE PRODUCT TESTING
 REPORT, SBCCI OR DADE COUNTY REPORT.
 6)- FL BLDG CODE 1606.1.4 PROTECTION OF
 OPENINGS, GLAZED OPENINGS TO HAVE LARGE
 MISSLE IMPACT TESTING OR STORM SHUTTERS
 7)- FLORIDA ENERGY FORMS, OWNER OR AGENT
 TO SIGN FORMS.
 8)- FLOOD ZONE A-5: CITY BASE ELEVATION
 HABITABLE AREAS 7'-6", A ELEVATION
 CERTIFICATE SHALL BE REQUIRED BY THE
 SURVEYOR AFTER MONOLITHIC SLAB IS POURED
 NOTE: POOL EQUIPMENT, A/C COMPRESSOR
 PADS SHALL BE SET AT A MINIMUM OF 7'-6".
 9)- FL BLDG CODE 1707.3.1 TRUSS ANCHORS,
 MISSING INFORMATION ON TRUSS LAYOUT
 PLAN, TRUSS GIRDER LOADS, VERTICAL,
 HORIZONTAL & GRAVITY LOADS AND THE TYPE
 OF ANCHOR THAT SHALL BE USED TO RESIST
 THESE LOADS.
 10)- FL BLDG CODE 424.17.1.9. POOL
 BARRIERS, WHERE A WALL OF A DWELLING
 SERVES AS PART OF THE BARRIER, ONE OF
 THE FOLLOWING SHALL APPLY: SEE CODE!
 11) CONTRACTOR TO SUBMIT THE PLANS TO
 THE P. B. COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT.
 12)- CONT TO PAY ADDITIONAL FEES, FOR
 RADON.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412
 ******PRIVACY WALL NOT PART OF BLDG
 PERMIT, A SEPERATE PERMIT IS REQUIRED***

Review Stop Z ZONING
Rev No 2 Status P Date 2002-07-09 Cont ID  
Sent By sgraham Date 2002-07-09 Time 14:55 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-26 Cont ID  
Sent By sgraham Date 2002-03-26 Time 11:03 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***