Plan Review Details - Permit 02031431
Plan Review Stops For Permit 02031431
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-25 Cont ID  
Sent By jwitmer Date 2002-04-25 Time 11:57 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-16 Cont ID  
Sent By jwitmer Date 2002-04-16 Time 09:57 Rev Time 2.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-16 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02031431
 8527 EGRET MEADOW LANE
 CONT: ODUM CONST
 TEL: 841-9877
  
 FL BLDG CODE= 2001 FLORIDA BUILDING CODE
  
 1)- PLANS SUBMITTED AFTER FEB. 28,2002
 SHALL COMPLY WITH THE 2001 FLORIDA
 BUILDING CODE.
 2)- FL BLDG CODE 1606.1.7 INFORMATION
 REQUIRED ON DRAWINGS RELATED TO WIND
 IS MISSING SEE CODE, NEW!
 3)- FL BLGD CODE 1606.2.5 COMPONENTS &
 CLADDING, 1606.1.4 PROTECTION OF
 OPENINGS, SLIDING GLASS DOOR REPORT IS
 FOR AN OX WITH A MAXIMUM WIDTH OF 96".
 WE ALSO ARE MISSING THE +/- PRESSURES
 ON THE OPENING.
 4)- FL BLDG CODE 1707.4.4.1 ANCHORING
 REQUIREMENT AS PER MANUFACTURES SPEC,
 NO BUCK ATTACHMENT?
 5)- FIXED WINDOWS ABOVE, FL BLDG CODE
 1707.4.5 MISSING MULLION REPORT.
 6)- DICREPANCY BETWEEN SHEET 1 &2.SEE
 OPENING 12'-6/14'-6? CHECK NEW PRODUCT
 TESTING REPORT FOR WIDTH & HEIGTH!!!
 7)- SHEET S-1 NO NOTATION AS TO HOW
 NEW LVLS ARE TO BE ANCHORED TO EXISTING
 STRUCTURE? OR IS THE THE BOLTS THROUGH
 THE TOP CORD OF DETAIL 1 GOING TO TRANS-
 FER THE LOADS? IF SO IN DETAIL 2 THE
 BOLTS ARE NOT INDICATED AS PENETRATING
 THE TOP CHORD OF THE TRUSS?
 8)- THERE IS NO LOADS TO BE REISTED?
 GRAVITY, HORIZONTAL NOR VERTICAL?
 9)- CLARIFICATION: S-1 DETAIL 7 THERE IS
 A NOTE "U" AT WOOD, AND BENEATH (2) 1/2"
 BOLTS, 1/2" DIA. X 4" LONG LAG, IS THIS
 LAG TO BE IN TENSION OR SHEAR? WHAT
 UPLIFT LOADS WILL BE IMPOSED ON THE
 LVL'S?
 10)- SSHEET S-1 A PROFESSIONAL ENGINEER
 (BOB BOTKIN) SHALL SIGN & AFFIX HIS SEAL
 TO ALL PLANS OR OTHER DOCUMENTS PREPARED
 OR ISSUED BY SAID REGISTRANT AND BEING
 SUBMITTED FOR PUBLIC RECORD.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-28 Cont ID  
Sent By btrobaug Date 2002-03-28 Time 18:20 Rev Time 0.00
Received By btrobaug Date 2002-03-28 Time 17:55 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-04-08 Cont ID  
Sent By btrobaug Date 2002-03-28 Time 18:20 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
2002-04-08 00:00:00PER CONTRACTOR: DO NOT THINK THERE WAS A
 ANY MECHANICAL WORK FOR THIS PERMIT>
 LS 4/8/02

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-27 Cont ID  
Sent By sgraham Date 2002-03-27 Time 10:23 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***