Plan Review Details - Permit 02031384
Plan Review Stops For Permit 02031384
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-03 Cont ID  
Sent By btrobaug Date 2002-05-03 Time 14:26 Rev Time 0.00
Received By btrobaug Date 2002-05-03 Time 13:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-22 Cont ID  
Sent By btrobaug Date 2002-03-22 Time 15:17 Rev Time 0.00
Received By btrobaug Date 2002-03-22 Time 13:31 Sent To  
Notes
2002-03-22 00:00:00*****************UNSAT!*****************
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUMBIT FOR REVIEW:
  
 1} A.I.C. RATING TO THE MAIN DISCONNECT.
  
 2} FEEDERS TO 60 AMP SUB PANEL TO COMPLY
 WITH 210-5 NEC & 215-8 CWPB
 AMMENDMENTS.
  
 3} INDICATE CONDUIT SIZE YO SUB PANEL.
  
 4} INDICATE LOCATION OF SERVICE
 EQUIPMENT.
  
 5} THE JOB VALUATION ON THE PERMIT
 APPLICATION DOESN'T SEEM CORRECT.
 PLEASE COMPLY WITH 104.6.5 CWPB
 AMMENDMENTS (ATTACHED).
  
 6} NOTE CODE ARTICLES 210-12 &
 210-11(C)(3).
  
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL:
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392