Plan Review Details - Permit 02031379
Plan Review Stops For Permit 02031379
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-23 Cont ID  
Sent By jwitmer Date 2002-04-23 Time 10:25 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-23 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02031379
 326 FERN ST/ 3RD FL
 CONT: INTEC CONST
 TEL: 649-1115
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)- COVER SHEET, CODE RESEARCH INDICATES
 1997 STANDARD BUILING CODE, SSHOULD READ
 2001 FLORIDA BUILDING CODE
  
 2)- COVER SHEET,GENERAL NOTES INDICATES
 THE 1994 FLORIDA ACCESSIBILITY CODE, THE
 FL ACCESSIBILITY CODE IS NOW CHAPTER11
 OF THE 2001 FL BLD CODE.
  
 3)- FL BLD CODE 903.8. MISSING FIRE
 SPRINKLER DRAWINGS.
  
 4)- OCCUPANT LOAD= 57 PEOPLE TABLE1003.1
  
 5)- FL BLD CODE 1012.1.2 EGRESS DOORS
 SHALL BE SIDE SWINGINGIN THE DIRECTION
 OF EGRESS WHEN SERVING AN OCCUPANT LOAD
 OF 50 OR MORE.
  
 6)- FL BLD CODE 1012.4 EGRESS DOORS DUR-
 ING ITS SWING SHALL LEAVE UNOBSTRUCTED
 AT LEAST ONE HALF THE REQUIRED WIDTH OF
 THE CORRIDOR, (22"). AT COLUMN LINE "E"
 THE DIMENSION IS NOT GIVEN, VERIFY!
  
 7)- THE 2 DOORS GAINING EGRESS INTO THE
 TENANT SPACE DO NOT GIVE THE RATING OF
 THE DOOR, FRAME OR CLOSER?
  
 8)- PROVIDE A FLOOR PLAN OF THE FURNI-
 TURE LAYOUT, INDICATE ACCESS CORRIDORS
  
 9)- DETAIL 8 OF 3.1 INDICATES A CUT
 SECTION OF A SOFFIT? WHERE IS IT TO BE
 USED? GIVE INFORMATION AS TO FASTENING
 SCHEDULE? TYPE OF FASTENER, FREQUENCY
 ETC? SPACING OF STUDS?
  
 10)- FL BLD CODE 1511.7 MECHANICAL UNITS
 ON THE ROOF, SEE TABLE 1511.7 CLEARENCES
 BELOW ROOF MOUNTED MECHANICAL UNITS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-04-03 Cont ID  
Sent By dpalmer Date 2002-04-03 Time 14:56 Rev Time 0.00
Received By dpalmer Date 2002-04-03 Time 14:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-04-12 Cont ID  
Sent By mcarsill Date 2002-04-12 Time 12:37 Rev Time 0.00
Received By mcarsill Date 2002-04-12 Time 12:37 Sent To  
Notes
2002-04-12 00:00:00A) GENERAL NOTES SECTION ON PAGE A1.1
 AND TITLE PAGE INDICATES EXITS TO COMPLY
 WITH CHAPTER 5 OF THE LIFE SAFETY CODE.
 THIS SHOULD READ CHAPTER 7 OF THE
 LIFE SAFETY CODE SINCE THE 2000 EDITION
 OF THE LIFE SAFETY CODE IS IN EFFECT.
 B) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE ALARM SYSTEM REMODEL.
 C) FIRE ALARM NOTES # 19 INDICATES FIRE
 ALARM CIRCUITS WILL BE CLASS B, STYLE C.
 ONLY CLASS A, STYLE D CIRCUITS WILL
 BE PERMITTED.
 D) PLEASE INDICATE RATINGS OF TENANT
 SPACE DOORS LEADING FROM THE SPACE TO
 CORRIDOR 312.
 E) NO FIRE SPRINKLER PLANS PROVIDED. THE
 FIRE SPRINKLER NOTES ARE INCORRECT.
 REFERENCES ARE MADE REGARDING THE SOUTH
 FLORIDA BUILDING CODE AND BROWARD
 COUNTY EDITION. THE FIRE SPRINKLER
 SYSTEM DESIGN IS TO COMPLY WITH NFPA 13,
 1999 EDITION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-09 Cont ID  
Sent By ndenmark Date 2002-04-09 Time 09:49 Rev Time 0.33
Received By ndenmark Date 2002-04-09 Time 09:49 Sent To  
Notes
2002-04-09 00:00:00PROVISO:
 ROOF STANDS FOR MECH EQUIPMENT SHALL BE
 PER FBC 1511.7 NOT SFBC

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-21 Cont ID  
Sent By kstevens Date 2002-04-21 Time 15:33 Rev Time 0.00
Received By kstevens Date 2002-04-21 Time 15:33 Sent To  
Notes
2002-04-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT M4.1 CONDENSATE SHALL NOT DRAIN
 INTO SANITARY. CONDENSATE SHALL DRAIN
 INTO A CONDENSATE LINE AND RUN SEPARATE
 OUTSIDE OF BLDG. CONDENSATE SHALL HAVE
 A RELIEF VENT AS THE LINE EXITS THE BLDG
 AND TIE INTO A CATCH BASIN, STORM DRAIN,
 OR DRYWELL IF APPROVED BY MECHANICAL
 CODE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377