Plan Review Details - Permit 02031316
Plan Review Stops For Permit 02031316
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-24 Cont ID  
Sent By lmartine Date 2002-04-24 Time 15:48 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-04-04 Cont ID  
Sent By btrobaug Date 2002-03-29 Time 06:48 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-04-04 00:00:00 
 PROVISO
 -------
  
 SUBMIT STRUCTURAL DETAIL FOR CUT THRU
 EXTERIOR BLOCK WALL.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-29 Cont ID  
Sent By pkrauss Date 2002-03-28 Time 16:58 Rev Time 0.00
Received By btrobaug Date 2002-03-29 Time 06:30 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-04-24 Cont ID  
Sent By mcarsill Date 2002-04-24 Time 15:40 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-03-28 Cont ID  
Sent By mcarsill Date 2002-03-28 Time 12:38 Rev Time 0.00
Received By mcarsill Date 2002-03-28 Time 12:38 Sent To  
Notes
2002-03-28 00:00:00A) IT WAS NOTED FROM THE PLANS THAT THE
 SPRAY BOOTH IS LOCATED DIRECTLY NEXT
 TO A WALL. THIS ARRANGEMENT CAN ONLY
 BE ALLOWED IF THE ALL PARTS OF THE
 SPRAY BOOTH CAN BE CLEANED. PLEASE
 ADVISE.
 B) PLEASE INDICATE HOW THE SPRAY BOOTH
 IS TO BE GROUNDED AND BONDED TO PREVENT
 STATIC ELECTRICITY.
 C) PLEASE PROVIDE A FLOOR PLAN OF THE
 SPACE WHERE THE SPRAY BOOTH IS PLANNED
 AND PLEASE LOCATE EXIT DOOR LOCATIONS.
 D) GLASS USED FOR THE LIGHT FIXTURES
 MUST BE EITHER WIRED GLASS, HEAT
 TREATED GLASS, OR HAMMERED WIRE GLASS.
 E) NO PANELS PROVIDED IN EXHAUST DUCT
 FOR INSPECTION OR CLEANING.
 F) HOW IS THE FLAMMABLE OR COMBUSTIBLE
 LIQUIDS PLANNED FOR USE TO BE STORED.
 G) THE EXHAUST DUCT FOR THE BOOTH
 TERMINATES ON THE SAME PROPERTY, ANY
 RIGHT OF WAYS, OR SOMEONE ELSE'S
 PROPERTY. PLEASE EXPLAIN.
 H) ELECTRIC TO COMPLY WITH NFPA 33.
 I) PLEASE PROVIDE DATA FOR FILTERS
 PLANNED FOR USE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-24 Cont ID  
Sent By pkrauss Date 2002-04-24 Time 15:42 Rev Time 0.40
Received By pkrauss Date 2002-04-24 Time 15:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-28 Cont ID  
Sent By pkrauss Date 2002-03-28 Time 16:01 Rev Time 0.45
Received By pkrauss Date 2002-03-28 Time 16:00 Sent To E
Notes
2002-03-28 00:00:00*******************DENIED***************
  
  
 1.AIR EXHAUSTED FROM SPRAY OPERATIONS
 SHALL BE CONDUCTED BY DUCTS DIRECTLY
 TO THE OUTSIDE OF THE BUILDING.
 EXHAUST DUCTS SHALL FOLLOW THE MOST
 DIRECT ROUTE TO THE POINT OF DIS-
 CHARGE, BUT SHALL NOT PENETRATE A
 FIRE WALL.
  
 2.EXHAUST DISCHARGE SHALL BE DIRECTED
 AWAY FROM ANY FRESH AIR INTAKES AND
 A MINIMUM OF 6 FT FROM ANY EXTERIOR
 WALL OR ROOF.
  
 3.EXHAUST SHALL NOT BE LOCATED LESS
 THAN 10 FT HORIZONTALLY FROM PARTS
 OF THE SAME OR CONTIGUOUS BUILDINGS
 AND ADJACENT PROPERTY LINE.
  
 SEE ALSO FIRE DEPT COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.