Plan Review Details - Permit 02031302
Plan Review Stops For Permit 02031302
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2002-03-25 Cont ID  
Sent By mamini Date 2002-03-25 Time 08:56 Rev Time 3.00
Received By mamini Date 2002-03-25 Time 08:56 Sent To  
Notes
2002-03-25 00:00:00PASSED WITH PROVISOS:
 1. ALL OFF STREET PARKING STALLS MUST BE
 PAINTED WITH DOUBLE 4" WIDE, WHITE FOR
 REGULAR AND BLUE FOR H.C.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-03-26 Cont ID  
Sent By mcarsill Date 2002-03-26 Time 08:56 Rev Time 0.00
Received By mcarsill Date 2002-03-26 Time 08:56 Sent To  
Notes
2002-03-26 00:00:00A) WET FIRE HYDRANTS REQUIRED PRIOR TO,
 DURING AND AFTER CONSTRUCTION.
 B) FIRE HYDRANTS ARE TO BE SPACED
 BETWEEN 300-500 FEET APART.
 C) CLEARANCES OF AT LEAST SEVEN FEET
 6 INCHES MUST BE PROVIDED TO THE FRONT
 AND SIDES OF EACH FIRE HYDRANT. AT
 LEAST FOUR FEET MUST BE PROVIDED TO THE
 REAR OF ALL FIRE HYDRANTS.
 D) NO ITEMS THAT WOULD OBSTRUCT THE
 USES OF THE FIRE HYDRANTS WILL BE
 ALLOWED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910