Plan Review Details - Permit 02031234
Plan Review Stops For Permit 02031234
Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-12-04 Cont ID  
Sent By mcarsill Date 2002-12-04 Time 16:10 Rev Time 0.00
Received By mcarsill Date 2002-12-04 Time 16:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2002-08-14 Cont ID  
Sent By mcarsill Date 2002-08-14 Time 08:39 Rev Time 0.00
Received By mcarsill Date 2002-08-14 Time 08:39 Sent To  
Notes
2002-08-14 00:00:001) MORE DETAILS ARE NEEDED FOR THE
 AREA WHERE THE LP GAS TANK IS
 PROPOSED. PLEASE INDICATE WHO'S
 PROPERTY IS IT. ARE THERE ANY UTILITY
 EASEMENTS TO WORRY ABOUT. PLEASE
 ADVISE AND REVISE PLANS AS NECESSARY.
 IT APPEARS AT THIS POINT THAT A MEETING
 SHOULD BE SCHEDULED WITH ALL INTERESTED
 PARTIES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-06-07 Cont ID  
Sent By mcarsill Date 2002-06-07 Time 13:30 Rev Time 0.00
Received By mcarsill Date 2002-06-07 Time 13:30 Sent To  
Notes
2002-06-07 00:00:001) A SURVEY IS REQUIRED.
  
 2) MORE DETAILS REQUIRED FOR
 INSTALLATION.
  
 3) DOES THE CENTER OPPOSE THIS
 INSTALLATION FOR ANY REASON.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-04-12 Cont ID  
Sent By mcarsill Date 2002-04-12 Time 14:45 Rev Time 0.00
Received By mcarsill Date 2002-04-12 Time 14:45 Sent To  
Notes
2002-04-12 00:00:00A) PLEASE SHOW ALL EXIT DOORS AND
 WINDOWS OF BUILDING NEXT TO PROPANE
 TANK.
 B) PLEASE INDICATE DISTANCE FROM
 PROPERTY LINES, ETC. A SURVEY SHOULD
 BE PROVIDED.
 C) NO INDICATION OF WARNING LABELS THAT
 WILL BE PROVIDED.
 D) PLEASE PROVIDE DETAILS ON BOLLARDS.
 E) PLEASE PROVIDE DATA ON HEATING OR
 COOKING EQUIPMENT.
 F) GAS VALVE IS TO BE TESTED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-12 Cont ID  
Sent By kstevens Date 2002-06-12 Time 17:06 Rev Time 0.00
Received By kstevens Date 2002-06-12 Time 17:06 Sent To  
Notes
2002-06-12 00:00:00PASSED/PROVISO
  
 INSPECTOR SHALL CHECK OVEN/RANGE FOR
 LISTING, BTU RATING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-11 Cont ID  
Sent By kstevens Date 2002-04-11 Time 16:59 Rev Time 0.00
Received By kstevens Date 2002-04-11 Time 16:59 Sent To  
Notes
2002-04-11 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS - NFPA-58
  
 1) MORE INFORMATION REQUIRED. PLEASE
 SUBMIT A PLAN TO SHOW ALL DOORS AND
 WINDOWS.
  
 2) PLEASE SUBMIT MANUFACTURE INFORMATION
 FOR OVEN/RANGE. SHOW BTU'S AND SHOW
 LISTING BY AN APPROVED AGENCY.
  
 3) PLEASE SUBMIT MANUFACTURE INFORMATION
 FOR REGULATOR. SHOW RANGE FOR REGULATOR
 (INPUT - OUTPUT).
  
 4)EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377