Plan Review Details - Permit 02031213
Plan Review Stops For Permit 02031213
Review Stop P PLUMBING
Rev No 3 Status P Date 2002-05-19 Cont ID  
Sent By pschmitz Date 2002-05-19 Time 12:07 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-05-19 00:00:00REVISION APPR,PES.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-04-11 Cont ID  
Sent By kstevens Date 2002-04-11 Time 19:08 Rev Time 1.00
Received By pschmitz Date 2002-04-11 Time 19:08 Sent To  
Notes
2002-05-19 00:00:00REVISION,APPR.PES
2002-04-11 00:00:00PASSED - PROVISO
  
 SHUT OFF VALVES REQUIRED BEFORE EACH
 REGULATOR.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-03 Cont ID  
Sent By kstevens Date 2002-04-03 Time 14:25 Rev Time 0.00
Received By kstevens Date 2002-04-03 Time 14:25 Sent To  
Notes
2002-04-03 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH THE
 STANDARDS NFPA 54, NFPA 58 AND THE FBC
 FUEL GAS CHAPTER 6.
  
 2) SPECIFI MODEL ON WATER HEATER BEING
 INSTALLED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377