| Plan Review Stops For Permit 02031204 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-03-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-20 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-03-20 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2002-03-20 00:00:00 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | ****************UNSAT!****************** | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW: | | | | | | 1} SIZE OF THE EXISTING SERVICE AND | | | ADDITIONAL LOAD BEING ADDED TO THE | | | SERVICE. | | | | | | 2} CIRCUIT NUMBERS AS THEY WILL APPEAR | | | ON THE PANEL SCHEDULE. | | | | | | 3} CIRCUITING OF RECEPTACLES.COMPLY | | | WITH210-52(B)(1),THROUGH 210-52(C)(5). | | | | | | 4} DRAWINGS TO COMPLY WITH 104.2 OF THE | | | CITY AMMENDMENTS. THE CABINET DETAILS | | | NEED TO BE DRAWN CLEARLY ENOUGH TO | | | DETERMI | | | NE CORRECT RECEPTACLE LOCATIONS. |
|
|
|