Plan Review Details - Permit 02031159
Plan Review Stops For Permit 02031159
Review Stop P PLUMBING
Rev No 2 Status P Date 2002-04-03 Cont ID  
Sent By kstevens Date 2002-04-03 Time 13:07 Rev Time 0.00
Received By kstevens Date 2002-04-03 Time 13:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-02 Cont ID  
Sent By kstevens Date 2002-04-02 Time 15:39 Rev Time 0.00
Received By kstevens Date 2002-04-02 Time 15:39 Sent To  
Notes
2002-04-02 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. TYPE OF GAS, (LP OR NATURAL)
  
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
  
 3). EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377