| Plan Review Stops For Permit 02031088 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-05-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-22 |
Time |
10:22 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2002-05-15 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2002-05-15 00:00:00 | APPROVED WITH PROVISO. SEE COOMENTS ON | | | PERMIT #02031089. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-04-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2002-04-17 |
Time |
16:14 |
Rev Time |
1.50 |
| Received By |
jgomez |
Date |
2002-04-17 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2002-04-17 00:00:00 | SEE COMMENTS ON PERMIT #02031089. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-03-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-27 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-03-27 |
Time |
06:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-03-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-28 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-28 |
Time |
15:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-05-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-22 |
Time |
10:20 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-05-22 |
Time |
10:20 |
Sent To |
B |
|
| Notes |
| 2002-05-22 00:00:00 | MECHANICAL PERMIT 02031130 | | | SUBMITTAL LRT - DRYERS LESS THAN 200 CFM |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-05-17 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-05-17 |
Time |
09:52 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2002-05-17 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2002-05-17 00:00:00 | PROVISO: | | | DRYER CFM DATA SUBMITTAL REQUIRED BEFORE | | | FIRST ROUGH INSPECTION |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-05-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-13 |
Time |
16:27 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-05-13 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2002-05-13 00:00:00 | *******************DENIED*************** | | | | | | MECHANICAL PERMIT 02031130 | | | | | | SEER ON ENERGY CALCS OKAY. | | | | | | OTHER COMMENTS NOT ADDRESSED FROM | | | PREVIOUS REVIEW. | | | | | | 1. O.A. CALCS. SHALL PROVIDE COMPLIANCE | | | WITH 402.2 (4% OF THE FLOOR AREA BEING | | | VENTILATED) OR TABLE 403.3 (MECHANICAL | | | VENTILATION NOT INFILTRATION) | | | | | | 2. DRYER CFM NOT PROVIDED. | | | | | | 3. DRYER LENGTHS IN EXCESS OF CODE | | | MINIMUM OF 25' PER 504.6. SUBMIT | | | SPECIFIC MANUFACTURER SPECIFICATIONS OF | | | ALLOWABLE LENGTH OF DUCT. | | | | | | 4. SECONDARY DRAIN CONSPICUOUS POINT | | | SHALL NOT BE BEHIND AHU CLOSET DOOR. IF | | | NO SUITABLE CONSPICUOUS LOCATION IS | | | AVAILABLE, A PAN WITH A FLOAT SWITCH PER | | | 307.2.4 IS ACCEPTABLE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-04-02 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-04-02 |
Time |
14:31 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2002-04-02 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2002-04-02 00:00:00 | ***************DENIED******************* | | | 1. SEER ON EQUIPMENT SCHEDULE DOES NOT | | | MATCH SEER ON ENERGY CALCS | | | 2. PROVIDE CFM INFORMATION ON DRYER TO | | | DETERMINE COMPLIANCE WITH 2001 FBC(M) | | | 504.5 | | | 3. PROVIDE OUTSIDE AIR PER FBC(M) TABLE | | | 403.3 | | | | | | NOTE: DRYER AND BATH EXHAUST DUCT SHAL | | | NOT PENETRATE RATED PARTYWALL OR | | | ADJACENT ROOF |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-05-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-13 |
Time |
17:37 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-13 |
Time |
17:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-04-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-19 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-19 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2002-04-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FHA AMEND-98 DESIGN MANUAL | | | | | | 1) SEE COMMENTS FROM PLAN REVIEW PERMIT | | | #02031089 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-03-21 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-03-21 |
Time |
11:55 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|