Plan Review Details - Permit 02031079
Plan Review Stops For Permit 02031079
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-09-03 Cont ID  
Sent By hpiskura Date 2002-09-03 Time 09:36 Rev Time 0.00
Received By hpiskura Date 2002-09-03 Time 08:31 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-08-21 Cont ID  
Sent By hpiskura Date 2002-08-21 Time 09:30 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-08-21 00:00:00THE VARCO-PRUDEN PLANS ARE REFERENCED TO
 THE "IBC" CODE AND A 120 MPH WIND
 SPEED.
  
 A PORTION OF THE V-P CALCULATIONS
 IDENTIFIED AS "BUILDING 1" CITE 120 MPH.
  
 THE CITY IS UNDER THE 2001 FLORIDA
 BUILDING CODE, (FBC) AND WHOLLY WITHIN
 A 140MPH WIND ZONE.THE PLANS MUST
 REFLECT WIND DESIGN TO EITHER FBC 1606
 OR ASCE 7-98.PLEASE REVISE AS
 NECESSARY WITH THE ENGINEER OF RECORD
 HAVING REVIEWED THE V-P PLANS FOR
 CONFIRMATION WITH DESIGN INTENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-06-18 Cont ID  
Sent By hpiskura Date 2002-06-18 Time 08:09 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-06-18 00:00:00COMMENTS ON 4/18/02 CHECKLIST ARE NOT
 ADDRESSED.
  
 PLEASE REVIEW THE 2001 FLORIDA BUILDING
 CODE.PROVIDE THE INFORMATION
 ENUMERATED IN FBC 104.3.1.1 AND
 1606.1.7 IN THE FORM OF PLANS, NOTES OR
 SPECIFICATIONS AS NECESSARY.
  
 IF THE EVALUATION OR TEST REPORTS FOR
 THE DOORS WINDOWS AND ROOF COVERING ARE
 NOT INCLUDED WITH THE PERMIT
 APPLICTION, ASEPARATE PERMIT AND
 ADDITIONAL FEES WILL BE NECESSARY.
  
 PLEASE REMOVE AND INSERT PAGES AS
 NECESSARY TO HAVE TWO CLEAR, CONCISE
 SETS OF PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-18 Cont ID  
Sent By hpiskura Date 2002-04-18 Time 13:55 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-18 00:00:00 
  
 THIS BUILDING WILL BE LOCATED IN AN A8
 FLOOD ZONE WITH A BFE OF 16.0'.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 THE CONSTRUCTION WILL BE SUBJECT TO THE
 2001 FLORIDA BUILDING CODE.THE DESIGN
 INFORMATION CALLED OUT ON THE PLANS IS
 NOT VALID.THE CITY OF WEST PALM BEACH
 IS LOCATED IN A 140 MPH WIND ZONE.
  
 MINIMUM PLAN REVIEW CRITERIA IS
 CONTAINED IN SECTIONS FBC 104 AND
 1606.1.7 OF THE CODE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-08-16 Cont ID  
Sent By dpalmer Date 2002-08-16 Time 06:11 Rev Time 0.00
Received By dpalmer Date 2002-08-16 Time 06:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-06-21 Cont ID  
Sent By dpalmer Date 2002-06-21 Time 06:43 Rev Time 0.00
Received By dpalmer Date 2002-06-21 Time 06:43 Sent To  
Notes
2002-06-21 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE PLANS NEED TO PUT
 INTO TWO COMPLETE SETS FOR REVIEW.
 PLEASE TAKE OUT OLD SHEETS AND INSERT
 NEW SHEETS. PUT OLD/VOIDED SHEETS IN
 ONE SET ONLY.
 PLEASE NOTE NEW SHEETS NOT PUT INTO
 SETS????
  
 2)NOTE: PLEASE NOTE SAME COMMENTS AS
 FIRST REVIEW FOR MDP. PLEASE NOTE STILL
 SHOWS AS "MLO" WITH 8 3-POLE SPACES??
 230-71A
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-01 Cont ID  
Sent By dpalmer Date 2002-04-01 Time 07:21 Rev Time 0.00
Received By dpalmer Date 2002-04-01 Time 07:02 Sent To  
Notes
2002-04-01 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT "MDP" SHOWS
 SIX MAINS AND SPACES FOR TWO MORE.
 PLEASE NOTE THAT MDP IS BEING SHOWN AS
 "MLO". 230-71A.
  
 2)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 NEED TO BE SHOWN. PLEASE SHOW W-PER SQ
 FT./ REC LOADS/ ETC.
 220-3,220-10,220-11,220-13
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE SEE ANY FIRE REVIEW
 COMMENTS THAT MAY AFFECT ELECTRICAL
 SHEETS. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICALPLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2002-07-23 Cont ID  
Sent By mamini Date 2002-07-23 Time 11:34 Rev Time 1.00
Received By mamini Date 2002-07-23 Time 11:34 Sent To  
Notes
2002-07-23 00:00:00N/A:
 1. SEE PERMIT # 02071300 FOR CIVIL /SITE
 WORK REVIEW AND PERMITTING.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2002-06-21 Cont ID  
Sent By mamini Date 2002-06-21 Time 11:28 Rev Time 5.00
Received By mamini Date 2002-06-21 Time 11:28 Sent To  
Notes
2002-06-21 00:00:00FAILED :
 1. PLEASE PROVIDE A COPY OF THE NORTHERN
 PALM BEACH COUNTY IMPROVEMENT DIST.
 PERMIT.
 2. A SEPARATE PERMIT AND FEES FOR THE
 CIVIL/SITE WORKS IS REQUIRED.
 3. ITEMS INDICATED ABOVE WERE NOT
 ADDRESSED IN YOUR RESPONSES TO OUR
 PREVIOUS REVIEW COMMENTS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-03-19 Cont ID  
Sent By mamini Date 2002-03-19 Time 10:00 Rev Time 3.00
Received By mamini Date 2002-03-19 Time 10:00 Sent To  
Notes
2002-03-19 00:00:00FAILED:
 1. DRIVEWAY APPROACHES MUST BE
 CONSTRUCTED PER FDOT STANDARD, INDEX NO.
 515, PLEASE INDICATE.
 2. ALL OFF-STREET PARKING MUST BE
 PAINTED WITH DOUBLE 4" WHITE FOR REGULAR
 AND BLUE FOR H.C., PLEASE REVISE THE
 DETAILS AS SHOWN ON SHEET C3.
 3. ALL BACKFLOW PREVENTERS MUST BE
 INSPECTED AND APPROVED BY THE CITY,
 659-8005 EXT. 2008 ORVILLE POLK.
 4. PLEASE SHOW THE REQUIRED CLEARANCES
 AT ALL CONFLICTS.
 5. WATER AND SEWER SERVICES AS SHOWN
 ON CIVIL PLAN DO NOT MATCHED THE
 PLUMBING PLANS.OIL/WATER SEPARATOR
 AND ITS LOCATION MUST BE SHOWN ON CIVIL.
 A SAND INTERCEPTOR MUST BE PROVIDED IF
 HEAVY MACHINERY AND EQUIPMENT ARE BEING
 WASHED.ALL INTERCEPTORS MUST BE
 INSPECTED AND APPROVED BY THE CITY,
 837-4051 EXT. 4074 RODNEY COMPO.
 6. PLEASE PROVIDE STORM WATER CALC.
 FOR OUR REVIEW AND APPROVAL.
 7. A SEPARATE PERMIT FROM NORTHERN PALM
 BEACH COUNTY IMPROVEMENT DISTRICT WILL
 BE REQUIRED, PLEASE SUBMIT A COPY.
 8. PLEASE SHOW INVERT ELEV. AND END WALL
 FOR 18" RCP ON NORTHSIDE OF THE
 RETETION POND.
 9. IS THERE ANY DUMPSTER ENCLOSURE
 PROPOSED FOR THE SITE? PLEASE NOTE THAT
 IT SHOULD BE CONSTRUCTED PER CITY
 STANDARD AND REQUIREMENT, IF GARBAGE IS
 TO BE PICKED UP BY THE CITY.
 10. A SEPARATE PERMIT AND FEES FOR THE
 SITE/CIVIL WORKS WILL BE REQUIRED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-09-06 Cont ID  
Sent By mcarsill Date 2002-09-06 Time 14:36 Rev Time 0.00
Received By mcarsill Date 2002-09-06 Time 14:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2002-08-13 Cont ID  
Sent By hpiskura Date 2002-09-03 Time 09:37 Rev Time 0.00
Received By mcarsill Date 2002-08-13 Time 11:08 Sent To  
Notes
2002-08-13 00:00:001) THE FIRE HYDRANTS SHOWN ON THE SITE
 PLAN ARE LOCATED BEHIND A CHAIN-LINK
 FENCE AND PROVIDES NO PROTECTION FOR
 THE TOOL EQUIPMENT RENTAL.
  
 2) NO DETAILS PROVIDED FOR THE PROPOSED
 LP GAS TANK SHOWN ON THE SITE PLAN. NO
 BARRIER PROTECTION SHOWN FOR THE LG
 GAS TANK OR PROPOSED 3000 GALLON FUEL
 TANK. SEPARATE PLANS AND PERMITS
 REQUIRED.
  
 3) GAS METER NOTED NEAR WELDING AREA.
  
 4) PLEASE ENSURE THAT ELECTRICAL
 DRAWINGS MATCH THE ARCHITECTURAL
 DRAWINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2002-06-28 Cont ID  
Sent By pkrauss Date 2002-06-24 Time 08:23 Rev Time 0.00
Received By mcarsill Date 2002-06-28 Time 10:31 Sent To  
Notes
2002-06-28 00:00:00PLEASE RESPOND TO PREVIOUS COMMENTS
 PROVIDED BY THIS OFFICE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-04-03 Cont ID  
Sent By mcarsill Date 2002-04-03 Time 15:49 Rev Time 0.00
Received By mcarsill Date 2002-04-03 Time 15:49 Sent To  
Notes
2002-04-03 00:00:00A) FIRE HYDRANTS ARE TO BE PROVIDED ON
 THE PROPERTY. NO FIRE HYDRANTS ARE
 SHOWN ON THE SITE PLAN.
 B) HOW DOES FIRE AND PARAMEDICAL
 EQUIPMENT ACCESS THE PROPERTY WHEN THE
 SLIDING GATES ARE CLOSED. WHAT
 PROVISIONS WILL BE MADE.
 C) BUILDING ADDRESS REQUIRED.
 D) MORE DETAILS REQUIRED ON LP GAS
 STORAGE AND AND ABOVE GROUND FUEL TANK
 SHOWN ON SITE PLAN.
 E) SEPARATE PLAN AND PERMITS REQUIRED
 ON SPRAY BOOTH AND EXTINGUISHING SYSTEM.
 F) PLEASE INDICATE WHAT BUILDING AND
 FIRE CODES THE BUILDING WAS DESIGNED
 TO.
 G) PLEASE INDICATE OCCUPANT LOADS FOR
 THE BUILDING.
 H) THE PAINT SPRAY BOOTH MUST HAVE AT
 LEAST THREE FEET ON ALL SIDES OF IT
 TO PROVIDE CLEANING CAPABILITIES.
 I) ARE ALL EXIT SIGNS SHOWN ON THE
 LIGHTING FLOOR PLAN.
 J) PLEASE PROVIDE MORE DETAILS ON WELDER
 50A.
 K) PLEASE INDICATE ALL FIRE EXTINGUISHER
 LOCATIONS.
 L) PLEASE EXPLAIN EXITING RATIONALE FROM
 DISPLAY AREA 101. IT APPEARS THAT
 EXITING ENTERS INTO A MORE HAZARDOUS
 AREA.
 M) THE PLANS INDICATE THAT THE BUILDING
 WILL BE CLASSIFIED AS BUSINESS. THE
 LIFE SAFETY CODE DEFINES BUSINESS AS
 "AS ONE USED FOR ACCOUNT AND RECORD
 KEEPING PURPOSES OR THE TRANSACTION
 OF BUSINESS OTHER THAN MERCANTILE" THIS
 OFFICE DOES NOT APPEAR TO BE CORRECTLY
 CATEGORIZED.
 N) PLEASE INDICATE USES FOR WAREHOUSE 1,
 PUMP AND POWER STORAGE, AND DISPLAY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-06 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 09:34 Rev Time 0.00
Received By btrobaug Date 2002-11-06 Time 09:34 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-11-15 Cont ID  
Sent By pkrauss Date 2002-11-15 Time 16:03 Rev Time 0.40
Received By pkrauss Date 2002-11-15 Time 16:03 Sent To  
Notes
2002-11-15 00:00:00CALLED CONTRACTOR - NEEDS TO COMPLETE A
 PERMIT APPLICATION FOR SPRAY BOOTH.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-08-15 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 09:34 Rev Time 0.50
Received By pkrauss Date 2002-08-15 Time 12:52 Sent To  
Notes
2002-08-15 00:00:00PROVISO:
  
 SEPARATE PERMITS REQUIRED FOR PAINT
 SPRAY BOOTH, GENERATOR & FUEL TANK, &
 GAS.PLEASE PROVIDE PLANS WITH PERMIT
 APPLICATION.
  
 PERMITS FOR ABOVE WORK REQUIRED PRIOR
 TO WORK COMMENCING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-24 Cont ID  
Sent By pkrauss Date 2002-06-24 Time 08:11 Rev Time 0.35
Received By pkrauss Date 2002-06-24 Time 08:03 Sent To  
Notes
2002-06-24 00:00:00PROVISO COMMENTS BY NANCY DENMARK
 DATED 4/4/02:
  
 AIR BALANCE SCHEDULE PER 2001 FBC(M)
 601.4 SHALL BE REQUIRED.
  
 SEPARATE PERMITS & PLANS REQUIRED FOR
 PAINT SPRAY BOOTH, FUEL (FOR GENERATOR)
 & FOR GENERATOR.
  
 PERMITS FOR ABOVE WORK REQUIRED PRIOR
 TO WORK COMMENCING ON ANY OF THE
 AFORMENTIONED ITEMS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT NANCY DENMARK (CHIEF MECH
 INSPECTOR) (561) 659-8096 EXT 8221 OR
 PATTY KRAUSS (MECH PLAN REVIEW) EXT
 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-04 Cont ID  
Sent By ndenmark Date 2002-04-04 Time 11:04 Rev Time 0.33
Received By ndenmark Date 2002-04-04 Time 11:04 Sent To  
Notes
2002-04-04 00:00:00PROVISO:
  
 AIR BALANCE PER 2001 FBC(M) 601.4 SHALL
 BE REQUIRED.
 SEPARATE PERMITS AND PLANS REQUIRED FOR
 PAINT SPRAY BOOTH, SUPPRESSION SYSTEM
 FOR PAINT SPRAY BOOTH, FUEL (FOR
 GENERATOR) AND FOR GENERATOR.
 PERMITS FOR ABOVE WORK REQUIRED PRIOR TO
 WORK COMMENCING ON ITEMS.
  
 ANY QUESTIONS PLEASE CAL:
 NANCY DENMARK,
 CHIEF MECHANICAL INSPECTOR
 (561) 659-8096 EXT. 8221

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-01-10 Cont ID  
Sent By kstevens Date 2003-01-10 Time 10:27 Rev Time 0.20
Received By kstevens Date 2003-01-10 Time 10:26 Sent To  
Notes
2003-01-10 00:00:00SUBMITTAL APPROVED (12-18-02) - RETURNED
 TO GAS CONTRACTOR - APPROVAL FOR GAS
 APPLIANCE

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-10-31 Cont ID  
Sent By kstevens Date 2002-10-31 Time 13:21 Rev Time 0.50
Received By kstevens Date 2002-10-31 Time 13:21 Sent To  
Notes
2002-10-31 00:00:00SUBMITTAL OK - GREASE TRAP DRAWING

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-08-17 Cont ID  
Sent By kstevens Date 2002-08-17 Time 16:37 Rev Time 0.00
Received By kstevens Date 2002-08-17 Time 16:37 Sent To  
Notes
2002-08-17 00:00:00PASSED - NO GAS REVIEW,INFORMATION
 REQUIRED AT TIME OF GAS PERMIT APPLICAT-
 ION. SEPARATE PERMIT REQUIRED FOR GAS.
 A) NEED MANUFACTURE SHEETS FOR GAS EQUIP
 B) SHOW LOCATION AND CAPACITY OF L-P
 TANK (SEE PREVIOUS REVIEW (D))
 C) UNDERGROUND OR ABOVE GROUND TANK??
 (SEE PREVIOUS REVIEW (E))

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-06-25 Cont ID  
Sent By kstevens Date 2002-06-25 Time 13:19 Rev Time 0.00
Received By kstevens Date 2002-06-25 Time 13:19 Sent To  
Notes
2002-06-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) FROM PREVIOUS REVIEW: DIMENTIONS FOR
 TOILET ROOMS NOT SHOWN. MINIMUM TOILET
 SIZE FOR TOILET ROOMS WITH DOOR IN FRONT
 IS 7'5" X 5'3". 5' TURNING RADIUS SHALL
 NOT INCLUDE SPACE OCCUPIED BY THE WATER
 CLOSET.
 2) FROM PREVIOUS REVIEW: WATER CLOSETS
 SHALL BE LOCATED 1'6" OFF THE WALL TO
 THE CENTER OF FIXTURE.
 3) ALL GAS INFORMATION REQUESTED SHALL
 BE SUBMITTED AT TIME OF GAS PERMIT
 APPLICATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-19 Cont ID  
Sent By kstevens Date 2002-04-19 Time 19:35 Rev Time 0.00
Received By kstevens Date 2002-04-19 Time 19:35 Sent To  
Notes
2002-04-19 00:00:00DENIED
 REFERENCE: FBC-2002 PLUMBING - FACBC-97
 FBC-2001 FUEL GAS - NFPA-58
  
 1) SHT A-1 PLEASE SUBMIT TOILET ROOM
 DETAILS. SHOW COMPLIANCE WITH FACBC SEC
 4.16 AND SEC 4.19 AND ALL SUBSECTIONS.
 PLEASE SUBMIT IN A 1/8" OR 1/4" SCALE,
 SHOW W/C'S TO BE 1'6" OFF WALL TO CENTER
 2) SHT A-1 PLEASE SHOW COMPLIANCE WITH
 FACBC SEC 4.15.2, AND SEC 4.1.3(10) FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 3) SHT P-1, WILL THE EYEWASH ALSO HAVE
 AN EMEMRGENCY SHOWER?
 4) SHTS P-2/P-3 FUNNEL FLOOR DRAIN NOT
 APPROVED. ALL INDIRECT WASTE AND DRIPS
 SHALL DRAIN INTO A FLOOR SINK. 802.2 &
 802.3
 5) SHT P-3 SANITARY RISER DIAGRAM, 2-WAY
 CLEAN OUTS ARE REQUIRED ON PIPES ENTER-
 ING AND EXITING THE GREASE TRAP. SEE
 ATTACHED SHEET FOR APPROVED GREASE TRAP
 DETAIL.
 6) SHT P-3 GEN PLMG NOTES #1 NFPA 58 IS
 FOR L.P. GAS NOT NFPA 54. #3 SIZE TO BE
 BASED ON FBC-2001 FUEL GAS TABLE APPROI-
 ATE FOR LP AND INDICATED PRESSURE.
 7) GREASE TRAP TO BE SIZED BY RODNEY
 COMPO ENVIRONMENTAL COMPLIANCE PER UTIL-
 ITY ORD #2938-96. PLEASE CALL (561)-
 837-4074.
 8) SHT P-4 WATER HEATER DETAIL, DIELECT-
 RIC UNIONS NOT APPROVED.
 9) SEPARATE GAS PERMIT REQUIRED. FOLLOW-
 ING IS LIST OF GAS PERMIT APPLICATION
 REQUIREMENTS NEEDED FOR PERMIT.
 A. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 GAS CODE SEC. 402.4.
 B. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAG CODE
 501.13 AND 501.14
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE CHAPTER 6.
 D. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 E. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 10) SHT C1 INDICATES A LP GAS TANK IN
 THE S.W. CORNER, AND SHT P-2 SHOWS LP
 TANKS NEAR THE S.E END OF THE BLDG.
 PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2002-09-09 Cont ID  
Sent By sgraham Date 2002-08-07 Time 07:52 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-08-07 00:00:00ZONING HAS ISSUE WITH THE FENCE, MATTER
 WILL BE DECIDED AT A LATER DATE.

Review Stop Z ZONING
Rev No 1 Status F Date 2002-06-05 Cont ID  
Sent By sgraham Date 2002-06-05 Time 09:26 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-06-05 00:00:00DENIED BY ZONING, EQUIP DISPLAY AREA
 MUST BE OF WASHED OR SIFTED ROCK NOT
 CRUSHED CONCRETE AS PER ENG DEPT .
 FENCE MUST BE CONCRETE WALL OR WOOD
 CONSTRUCTION