Plan Review Details - Permit 02031030
Plan Review Stops For Permit 02031030
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-17 Cont ID  
Sent By hpiskura Date 2002-04-17 Time 10:08 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-17 00:00:00THIS BUILDING IS LOCATED IN AN A5 FLOOD
 ZONE WITH A BFE OF 7.0' NGVD.THE
 LOWEST OCCUPIABLE FLOOR MUST BE AT OR
 ABOVE 7.5'NGVD.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY FOR THE CITY, THE
 PERMIT PLANSSTAMPED BY THAT OFFICE AND
 A COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.CALL
 561-233-5025 FOR MORE INFORMATION.
  
 AT TIME OF PERMIT APPLICATION PROVIDE A
 RECENT, SIGNED, SEALED AND DATED
 PROPERTY SURVEY INCLUDING ELEVATIONS.
  
 THE HC RAMP AS SHOWN DOES NOT COMPLY
 WITH FBC 11-4.8.
  
 ALL OF THE REMODELED PORTIONS OF THE
 BUILDING MUST COMPLY WITH 11-4.1
 THROUGH 11-4.35.THE PLANS AS SHOWN DO
 NOT COMPLY.
  
 THE EXTERIOR DOORS AT THE PRIVATE
 OFFICEAND LOBBY MUST COMPLY WITH FBC
 1012.1.3 FOR LANDINGS.
  
 THE PERMIT PLANS SHOULD INDICATE THE
 OVERFLOW SCUPPERS IN THE PARAPET WALLS
 AS PROVIDED FOR IN FBC 1511.6.4.3.
  
 PROVIDE A STRUCTURAL ANALYSIS OF THE
 EXISTING ROOF TRUSSES DEMONSTRATING
 THEIR SUITABILILTY TO ASSUME THE NEW
 LOADS THAT WILL BE IMPOSED.
  
 ADDITIONAL CONSTRUCTION DETAILS FOR THE
 DECORATIVE CAST COLUMNS AND GABLE END
 TRUSSES WILL BE NECESSARY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-01 Cont ID  
Sent By dpalmer Date 2002-04-01 Time 10:11 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2002-04-01 00:00:00************* NOTE ******************
  
 1)NOTE: PLEASE SHOW LOAD CALCUALTION
 IN MORE DETAIL. PLEASE SHOW WATSS PER
 SQ FT/ REC LOADS/ ETC.
 220-3,220-10,220-11,220-13.
  
 2)NOTE: PLEASE CLARIFY SIGN CIRCUIT PER
 600-5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-04-04 Cont ID  
Sent By mcarsill Date 2002-04-04 Time 15:37 Rev Time 0.00
Received By mcarsill Date 2002-04-04 Time 15:37 Sent To  
Notes
2002-04-04 00:00:00A) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS
 REQUIRED.
 B) ALL STORAGE AND MECHANICAL ROOMS
 ARE TO BE FIRE RATED AND BE EQUIPPED
 WITH AT C LABELED FIRE DOORS SINCE
 NO FIRE SPRINKLERS ARE PRESENT.
 C) EXITING NOTED THRU PRIVATE OFFICE.
 THE DOOR LEADING INTO THE PRIVATE
 OFFICE CANNOT BE SUBJECT TO LOCKING
 AND ALSO NO FURNITURE IS TO BE PLACED
 IN FRONT OF THE EXIT DOORS.
 D) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFOMATION FOR WALLS
 AND CEILINGS.
 E) PLEASE INDICATE OCCUPANT LOAD FOR
 BUILDING, SINCE SOME CORRIDORS ARE LESS
 THAN 44" WIDE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-04-11 Cont ID  
Sent By pkrauss Date 2002-04-11 Time 12:30 Rev Time 1.15
Received By pkrauss Date 2002-04-11 Time 12:30 Sent To  
Notes
2002-04-11 00:00:00 
  
 1.2001 FBC, MECHANICAL 401.5, OUTSIDE
 AIR EXHAUST & INTAKE OPENINGS SHALL
 BE A MINIMUM OF 10 FT FROM LOT LINES
 OR BUILDINGS ON THE SAME LOT.
  
 2.AS PER 2001 FBC, MECHANICAL 401.5.2,
 EXHAUST AIR SHALL NOT BE DIRECTED ON
 TO WALKWAYS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-20 Cont ID  
Sent By kstevens Date 2002-04-20 Time 07:54 Rev Time 0.00
Received By kstevens Date 2002-04-20 Time 07:54 Sent To  
Notes
2002-04-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11 FACBC
  
 1) ACCORDING TO TABLE 403.1 FBC PLUMBING
 1 DRINKING FOUNTAIN AND 1 SERVICE SINK
 SHALL BE REQUIRED.
 2) SHT P-1 BUSINESS OFFICE LOUNGE, SHOW
 COMPLIANCE WITH SECTION 4.24 FACBC FOR
 SINK.
 3) SHT P-1 CONDENSATE LINE TO DRYWELL
 SHALL HAVE A RELIEF VENT AS PIPING EXITS
 BLDG. SHOW DETAIL.
 4) SHT P-1 GENERAL NOTES #16 CHANGE TO
 WATER HAMMER ARRESTORS - AIR CHAMBERS
 NOT APPROVED.
 5) SHT P-2 ITEM #10 WATER FILTER, PLEASE
 SUBMIT MANUFACTURE INFORMATION. FILTER
 TO BE NSF APPROVED.
 6) SHT P-2 ITEM #11 WATER HEATER, RELIEF
 VALVE DISCHARGE PIPE SHALL NOT HAVE ANY
 TRAPPED SECTIONS AND SHAL HAVE A VISIBLE
 AIR GAP OR AIR GAP FITTING LOCATED IN
 THE SAME ROOM AS THE WATER HEATER. FBC-
 PLMG SEC. 504.7
 7) SHT P-2 ITEM #12 AND ALL DENTAL EQUIP
 MENT SHALL HAVE BACKFLOW PROTECTION.
 PLEASE SUBMIT INFORMATION SHOWING HOW
 THIS WILL BE COMPLIED WITH.
 8) SHT P-4 WATER ISOMETRIC, NOTE #9
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 IN AN "EFFICTIVE RANGE" CLOSE TO FIXTUR-
 ES NOT AT TOP OF DROP AS SHOWN. PER MAN-
 UFACTURES INSTALLATION INSTRUCTIONS AND
 PDI-WH 201.
 9) PLEASE SUBMIT MANUFACTURE INFORMATION
 ON THE DENTISTS CHAIRS TO SEE HOW WATER,
 WASTE, VACUUM, AND AIR ARE CONNECTED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status F Date 2002-03-28 Cont ID  
Sent By sgraham Date 2002-03-28 Time 15:49 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-03-28 00:00:001. PLANS DOES NOT MEET PARKING REQUIRE-
 MENTS OF RESIDENTIAL CONVERSION TO
 COMMERICAL IN THE POR DISTRICT
 2. NO LANDSCAPE PLAN, ANY CONVERSION
 MUST PROVIDE LANDSCAPE BUFFERS AROUND
 PARKING
 3. PLAN SHOULD BE 1301 S FLAGLER,NOT N
 FLAGLER