Plan Review Details - Permit 02031030
| Plan Review Stops For Permit 02031030 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-04-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-04-17 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-17 00:00:00 | THIS BUILDING IS LOCATED IN AN A5 FLOOD | | | ZONE WITH A BFE OF 7.0' NGVD.THE | | | LOWEST OCCUPIABLE FLOOR MUST BE AT OR | | | ABOVE 7.5'NGVD. | | | | | | BEFORE A PERMIT TO CONSTRUCT MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY FOR THE CITY, THE | | | PERMIT PLANSSTAMPED BY THAT OFFICE AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO | | | THE PERMIT APPLICATION.CALL | | | 561-233-5025 FOR MORE INFORMATION. | | | | | | AT TIME OF PERMIT APPLICATION PROVIDE A | | | RECENT, SIGNED, SEALED AND DATED | | | PROPERTY SURVEY INCLUDING ELEVATIONS. | | | | | | THE HC RAMP AS SHOWN DOES NOT COMPLY | | | WITH FBC 11-4.8. | | | | | | ALL OF THE REMODELED PORTIONS OF THE | | | BUILDING MUST COMPLY WITH 11-4.1 | | | THROUGH 11-4.35.THE PLANS AS SHOWN DO | | | NOT COMPLY. | | | | | | THE EXTERIOR DOORS AT THE PRIVATE | | | OFFICEAND LOBBY MUST COMPLY WITH FBC | | | 1012.1.3 FOR LANDINGS. | | | | | | THE PERMIT PLANS SHOULD INDICATE THE | | | OVERFLOW SCUPPERS IN THE PARAPET WALLS | | | AS PROVIDED FOR IN FBC 1511.6.4.3. | | | | | | PROVIDE A STRUCTURAL ANALYSIS OF THE | | | EXISTING ROOF TRUSSES DEMONSTRATING | | | THEIR SUITABILILTY TO ASSUME THE NEW | | | LOADS THAT WILL BE IMPOSED. | | | | | | ADDITIONAL CONSTRUCTION DETAILS FOR THE | | | DECORATIVE CAST COLUMNS AND GABLE END | | | TRUSSES WILL BE NECESSARY. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-04-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-04-01 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-01 00:00:00 | ************* NOTE ****************** | | | | | | 1)NOTE: PLEASE SHOW LOAD CALCUALTION | | | IN MORE DETAIL. PLEASE SHOW WATSS PER | | | SQ FT/ REC LOADS/ ETC. | | | 220-3,220-10,220-11,220-13. | | | | | | 2)NOTE: PLEASE CLARIFY SIGN CIRCUIT PER | | | 600-5. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-04-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-04-04 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-04-04 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2002-04-04 00:00:00 | A) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS | | | REQUIRED. | | | B) ALL STORAGE AND MECHANICAL ROOMS | | | ARE TO BE FIRE RATED AND BE EQUIPPED | | | WITH AT C LABELED FIRE DOORS SINCE | | | NO FIRE SPRINKLERS ARE PRESENT. | | | C) EXITING NOTED THRU PRIVATE OFFICE. | | | THE DOOR LEADING INTO THE PRIVATE | | | OFFICE CANNOT BE SUBJECT TO LOCKING | | | AND ALSO NO FURNITURE IS TO BE PLACED | | | IN FRONT OF THE EXIT DOORS. | | | D) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION INFOMATION FOR WALLS | | | AND CEILINGS. | | | E) PLEASE INDICATE OCCUPANT LOAD FOR | | | BUILDING, SINCE SOME CORRIDORS ARE LESS | | | THAN 44" WIDE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-04-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-11 |
Time |
12:30 |
Rev Time |
1.15 |
| Received By |
pkrauss |
Date |
2002-04-11 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2002-04-11 00:00:00 | | | | | | | 1.2001 FBC, MECHANICAL 401.5, OUTSIDE | | | AIR EXHAUST & INTAKE OPENINGS SHALL | | | BE A MINIMUM OF 10 FT FROM LOT LINES | | | OR BUILDINGS ON THE SAME LOT. | | | | | | 2.AS PER 2001 FBC, MECHANICAL 401.5.2, | | | EXHAUST AIR SHALL NOT BE DIRECTED ON | | | TO WALKWAYS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-04-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-20 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-20 |
Time |
07:54 |
Sent To |
|
|
| Notes |
| 2002-04-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 FACBC | | | | | | 1) ACCORDING TO TABLE 403.1 FBC PLUMBING | | | 1 DRINKING FOUNTAIN AND 1 SERVICE SINK | | | SHALL BE REQUIRED. | | | 2) SHT P-1 BUSINESS OFFICE LOUNGE, SHOW | | | COMPLIANCE WITH SECTION 4.24 FACBC FOR | | | SINK. | | | 3) SHT P-1 CONDENSATE LINE TO DRYWELL | | | SHALL HAVE A RELIEF VENT AS PIPING EXITS | | | BLDG. SHOW DETAIL. | | | 4) SHT P-1 GENERAL NOTES #16 CHANGE TO | | | WATER HAMMER ARRESTORS - AIR CHAMBERS | | | NOT APPROVED. | | | 5) SHT P-2 ITEM #10 WATER FILTER, PLEASE | | | SUBMIT MANUFACTURE INFORMATION. FILTER | | | TO BE NSF APPROVED. | | | 6) SHT P-2 ITEM #11 WATER HEATER, RELIEF | | | VALVE DISCHARGE PIPE SHALL NOT HAVE ANY | | | TRAPPED SECTIONS AND SHAL HAVE A VISIBLE | | | AIR GAP OR AIR GAP FITTING LOCATED IN | | | THE SAME ROOM AS THE WATER HEATER. FBC- | | | PLMG SEC. 504.7 | | | 7) SHT P-2 ITEM #12 AND ALL DENTAL EQUIP | | | MENT SHALL HAVE BACKFLOW PROTECTION. | | | PLEASE SUBMIT INFORMATION SHOWING HOW | | | THIS WILL BE COMPLIED WITH. | | | 8) SHT P-4 WATER ISOMETRIC, NOTE #9 | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | IN AN "EFFICTIVE RANGE" CLOSE TO FIXTUR- | | | ES NOT AT TOP OF DROP AS SHOWN. PER MAN- | | | UFACTURES INSTALLATION INSTRUCTIONS AND | | | PDI-WH 201. | | | 9) PLEASE SUBMIT MANUFACTURE INFORMATION | | | ON THE DENTISTS CHAIRS TO SEE HOW WATER, | | | WASTE, VACUUM, AND AIR ARE CONNECTED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2002-03-28 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-03-28 |
Time |
15:49 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-28 00:00:00 | 1. PLANS DOES NOT MEET PARKING REQUIRE- | | | MENTS OF RESIDENTIAL CONVERSION TO | | | COMMERICAL IN THE POR DISTRICT | | | 2. NO LANDSCAPE PLAN, ANY CONVERSION | | | MUST PROVIDE LANDSCAPE BUFFERS AROUND | | | PARKING | | | 3. PLAN SHOULD BE 1301 S FLAGLER,NOT N | | | FLAGLER |
|
|
|