Plan Review Details - Permit 02030852
Plan Review Stops For Permit 02030852
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-08-02 Cont ID  
Sent By rbrown Date 2002-08-02 Time 14:37 Rev Time 0.00
Received By rbrown Date 2002-08-02 Time 14:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-07-02 Cont ID  
Sent By rbrown Date 2002-07-02 Time 15:30 Rev Time 0.00
Received By rbrown Date 2002-07-02 Time 15:26 Sent To  
Notes
2002-07-02 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 4/18/02:
  
 3) FBC* 104.2.1THIS COMMENT HAS NOT
 BEEN PROPERLY ADDRESSED.TITLE BLOCK ON
 SHEET PL1-W02 STILL SHOWS AN INCORRECT
 ADDRESS. AMEND TO READ '245 WALTON BLVD'
 FOR PUBLIC RECORD.
  
 4) FBC 13-103.0THE SUBMITTED ENERGY
 CODE COMPLIANCE FORMS ARE NOT COMPLETE.
 FBC 13-103.1.1 REQUIRES THE FORMS TO BE
 SIGNED BY THE PERSON PREPARING THE
 COMPLIANCE CALCULATION.ALSO THE
 PERMITTING OFFICE (WEST PALM BEACH),
 PERMIT NO. (02030852), CLIMATE ZONE (8)
 AND JURISDICTION NO. (604700) MUST ALL
 BE COMPLETED ON THE FORMS.
  
 5) FBC 1606.1.4THE SUBMITTED WINDOW
 PRODUCT APPROVAL NOTICE OF ACCEPTANCE
 NO. 01-0516.10 HAS COPIES OF DRAWING NO.
 2736, SHEETS 1 THRO' 7 OF 8 WHICH ARE
 MISSING DATA ON THE LEFT AND/OR RIGHT
 EDGES OF EACH SHEET.SUBMIT COMPLETE
 AND LEGIBLE COPIES.
  
 6) FBC 1804.6.3.1CRAWL SPACE
 VENTILATION.THE INFORMATION GIVEN IN
 ITEM (6) OF THE RESPONSE LETTER DATED
 5/28/02 SHALL BE ADDED TO THE PLANS, AND
 THE CHANGE SIGNED AND DATED.THE LETTER
 MAKES NO REFERENCE TO THE PURPOSE OF THE
 VENTILATION AND WILL NOT MAKE IT CLEAR
 TO THE CONTRACTOR AND FIELD INSPECTOR
 THAT THE VENT BLOCKS ARE TO BE LOCATED
 AT LOW LEVEL TO VENT THE UNDERFLOOR
 CRAWL SPACE.
  
 7) CMU BLOCKING AROUND THE NEW WINDOW IS
 DESCRIBED, IN THE RESPONSE LETTER, AS
 HAVING FILLED CELLS TIED TO THE SLAB
 BELOW AND BEAM ABOVE.THE FRONT CROSS
 SECTION (SHEET PL1-W02) STILL SHOWS A
 CONTINUOUS VERTICAL JOINT BETWEEN THE
 NEW CMU CONSTRUCTION AND THE EXISTING
 CMU WALL.ANNOTATE THE PLANS TO
 DESCRIBE HOW THE NEW CMU WILL BE TIED
 HORIZONTALLY TO THE EXISTING MASONRY AND
 SIGN AND DATE THE CHANGES.
  
 NOTE:
 IN ADDRESSING ITEMS 6 AND 7 PLEASE
 ANNOTATE THE PLANS.THE RESPONSE LETTER
 DOES NOT ADEQUATELY DESCRIBE THE
 LOCATION AND ORIENTATION, OF THE REVISED
 DETAILS, FOR THE CONTRACTOR AND FIELD
 INSPECTOR.ALL AMENDMENTS MADE TO THE
 PLANS, AFTER THE ORIGINAL SIGNING AND
 SEALING, SHALL BE SIGNED AND DATED BY
 THE DESIGNER WHO ORIGINALLY SIGNED AND
 SEALED THE PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-18 Cont ID  
Sent By rbrown Date 2002-04-18 Time 19:34 Rev Time 0.00
Received By rbrown Date 2002-04-18 Time 19:33 Sent To  
Notes
2002-04-18 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC* 104.2.1THE TITLE BLOCKS ON THE
 PLANS SHOW AN INCORRECT ADDRESS.AMEND
 TO READ '245 WALTON BLVD' FOR PUBLIC
 RECORD.
  
 4) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS.
  
 5) FBC 1606.1.4SUBMIT A PRODUCT
 APPROVAL FOR THE NEW WINDOWS.IF THE
 PROPOSED WINDOWS REQUIRE HURRICANE
 MISSILE IMPACT PROTECTION, THEN A
 SHUTTER PRODUCT APPROVAL WILL ALSO BE
 REQUIRED.
  
 6) FBC 1804.6.3.1CRAWL SPACE
 VENTILATION.A MINIMUM OF 2 SQFT OF
 CROSS VENTILATION SHALL BE PROVIDED.
 THE VENTILATION OPENINGS SHALL BE
 PROTECTED WITH CORROSION RESISTANT WIRE
 MESH WITH APERTURES OF NOT LESS THAN
 1/4" NOR MORE THAN 1/2" IN ANY DIMENSION
  
 7) FBC* 104.2.1ANNOTATE THE PLANS TO
 DESCRIBE HOW THE CONCRETE MASONRY UNIT
 BLOCKING AROUND THE NEW WINDOW WILL BE
 TIED TO THE EXISTING MASONRY AS A SECURE
 SUBSTRATE FOR THE NEW WINDOW/SHUTTERS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-13 Cont ID  
Sent By btrobaug Date 2002-03-13 Time 17:21 Rev Time 0.00
Received By btrobaug Date 2002-03-13 Time 17:01 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-08-02 Cont ID  
Sent By btrobaug Date 2002-03-13 Time 17:22 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-03-30 Cont ID  
Sent By jleech Date 2002-03-30 Time 10:48 Rev Time 0.25
Received By jleech Date   Time   Sent To  
Notes
2002-03-30 00:00:00NO PLUMBING SHOWN ON PLANS.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-19 Cont ID  
Sent By rbrown Date 2002-04-19 Time 08:31 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
2002-04-19 00:00:00PER SHIRLEY GRAHAM