Plan Review Details - Permit 02030851
Plan Review Stops For Permit 02030851
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-20 Cont ID  
Sent By dpalmer Date 2002-03-20 Time 19:26 Rev Time 0.00
Received By dpalmer Date 2002-03-20 Time 19:26 Sent To  
Notes
2002-03-20 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY,E-1 MENTIONS
 ELECTRICAL SITE PLAN? PLEASE NOTE THAT
 NO "ELECTRICAL SITE" WORK IS SHOWN?
 LANDSCAPE LIGHTING/LIGHTING FOR PARKING
 LOT(S) ETC. PLEASE CLARIFY.
  
 2)NOTE: PLEASE CLARIFY LOCATION OF TWO
 A/C COND UNITS SHOWN ON MDP?CU-1/CU-2
 PLEASE NOTE THAT THESE NEED TO BE SHOWN
 ON POWER PLAN AND NEED TO HAVE DISC`S
 PER 440-11.
  
 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 PER 220-3,220-11. PLEASE NOTE WATTS/PER
 SQ FT. ETC. PLEASE NOTE THAT ALL
 CONTINUOUS LOADS AT 125% PER 215-2,3/
 230-42 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REIVEW
 561-659-8096 EXT 8372
  
  
 PLEASE NOTE THAT NOTES FROM FIRST REVIEW
 ASKED FOR LOAD CALCULATIONS TO BE SHOWN.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-03-19 Cont ID  
Sent By mamini Date 2002-03-19 Time 14:32 Rev Time 1.00
Received By mamini Date 2002-03-19 Time 14:31 Sent To  
Notes
2002-03-19 00:00:00FAILED :
 1. SEE PERMIT # 01101303 FOR CIVIL
 ENGINEERING REVIEW COMMENTS DATED
 10/30/01.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-03-21 Cont ID  
Sent By mcarsill Date 2002-03-21 Time 12:41 Rev Time 0.00
Received By mcarsill Date 2002-03-21 Time 12:41 Sent To  
Notes
2002-03-21 00:00:00PREVIOUS PLAN REVIEW COMMENTS UNDER
 01101303 HAVE NOT BEEN ADDRESSED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved