Plan Review Details - Permit 02030850
Plan Review Stops For Permit 02030850
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-20 Cont ID  
Sent By dpalmer Date 2002-03-20 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2002-03-20 Time 18:50 Sent To  
Notes
2002-03-20 00:00:00****************** UNSAT ***************
  
 PLEASE NOTE THAT NOW COMPLETE PLANS ARE
 BEING SUBMITTED FOR REVIEW FROM 10/30/01
  
 PLEASE NOTE THAT PLANS STILL HAVE NOTES
 FROM FIRST REVIEW TO BE ADDRESSED.
  
 1)NOTE: PLEASE NOTE THAT PLANS MUST BE
 SIGNED DATED AND SEALED BY THE ARCH`S/
 ENGINEER OF RECORD. PER FAC/FS 471.025
 481.221.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER 220-11/220-10 PLEASE SHOW AS PER
 W=SQ FT ETC.PLEASE NOTE ALL CONTINUOUS
 LOADS AT 125%. 215-2,3/230-42,,,,,,
  
 3)NOTE: PLEASE NOTE THAT DSB-7 AND DSB-8
 ARE MISSING FROM DISC SW SCHEDULE.
  
 4)NOTE: PLEASE NOTE THAT COND UNITS 1&2
 LOCATIONS ARE NOT SHOWN ON E-3.
 PLEASE SHOW, SHOW DISC`S PER 440-11
  
 5)NOTE: PLEASE NOTE THAT SHEET E-1 SAYS
 "ELECTRICAL SITE PLAN" PLEASE CALRIFY
 THERE IS NO ELECTRICAL SITE ELECTRICAL
 SHOWN? LIGHTING/LANDSCAPE LTS ETC??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-03-19 Cont ID  
Sent By mamini Date 2002-03-19 Time 14:43 Rev Time 1.00
Received By mamini Date 2002-03-19 Time 14:42 Sent To  
Notes
2002-03-19 00:00:00FAILED :
 1. SEE PERMIT # 01101295 FOR CIVIL
 ENGINEERING REVIEW COMMENTS DATED
 10/30/01.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-03-21 Cont ID  
Sent By mcarsill Date 2002-03-21 Time 11:26 Rev Time 0.00
Received By mcarsill Date 2002-03-21 Time 11:26 Sent To  
Notes
2002-03-21 00:00:00PREVIOUS PLAN REVIEW COMMENTS UNDER
 # 01101295 HAVE NOT BEEN ADDRESSED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-21 Cont ID  
Sent By pkrauss Date 2002-03-21 Time 16:37 Rev Time 0.35
Received By pkrauss Date 2002-03-21 Time 16:35 Sent To  
Notes
2002-03-21 00:00:00 
 REFERENCE PERMIT 01101295
  
 PLEASE SEE COMMENTS DATED 11-05-01.
  
 TO HELP EXPEDITE PLAN REVIEW PROCESS
 PLEASE PROVIDE WRITTEN RESPOSE TO
 COMMENTS.
  
 PLANS ARE NOT SIGNED, SEALED & DATED BY
 THE ENGINEER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***