Plan Review Details - Permit 02030835
Plan Review Stops For Permit 02030835
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-18 Cont ID  
Sent By btrobaug Date 2002-06-18 Time 16:21 Rev Time 0.00
Received By btrobaug Date 2002-06-18 Time 15:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-13 Cont ID  
Sent By btrobaug Date 2002-03-13 Time 12:53 Rev Time 0.00
Received By btrobaug Date 2002-03-13 Time 12:42 Sent To  
Notes
2002-03-13 00:00:00****************UNSAT!!*****************
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW:
  
 1}PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} NUMBER AND SIZE OF CONDUCTORS IN:
 A)1-1/4"PVC
 B)3" PVC.
  
 3} OVERCURRENT PROTECTION OF THESE
 CONDUCTORS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392