| Plan Review Stops For Permit 02030835 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-06-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-06-18 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-06-18 |
Time |
15:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-03-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-13 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-03-13 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2002-03-13 00:00:00 | ****************UNSAT!!***************** | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW: | | | | | | 1}PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} NUMBER AND SIZE OF CONDUCTORS IN: | | | A)1-1/4"PVC | | | B)3" PVC. | | | | | | 3} OVERCURRENT PROTECTION OF THESE | | | CONDUCTORS. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT.8392 |
|
|
|