| 2002-03-29 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 |
| | |
| | 1) FBC-2001 SEC 424.2.6.6.2 PLEASE GIVE |
| | MANUFACTURE AND MODEL # FOR SELF CLOSING |
| | SAFTY COVER ON VACUUM LINE. |
| | 2) |
| | FBC-2001 SEC 424.2.6.4 SUBMIT MANUFACT- |
| | URES RECOMMENDATIONS. |
| | 3) |
| | FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL |
| | ORD. #2853-95, BACKFLOW REQUIRED ON |
| | WATER SERVICE. (ADD TO NOTES) |
| | 4) |
| | FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. |
| | PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| | TEST SHALL BE APPROVED FOR PVC PIPE AND |
| | FITTINGS. (ADD TO NOTES) |
| | 5) |
| | FBC-2001 SEC 424.2.13.2JOINTS AND CON- |
| | NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| | PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| | NOTES) |
| | 6) |
| | FBC-2001 SEC 424.2.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. MANUFACTURE |
| | SHEETS REQUIRED. (SUBMITTAL) |
| | 7) |
| | FBC-2001 SEC 424.2.14.2 WATER RETENTION, |
| | PROVIDE A POSITIVE MEANS OF RETAINING |
| | WATER IN THE HEATER WHEN PUMP IS SHUT |
| | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) |
| | 8) |
| | FBC-2001 SEC 424.2.14.4 CONNECTIONS, ALL |
| | WATER HEATING EQUIPMENT SHALL BE INSTAL- |
| | LED WITH FLANGES OR UNION CONNECTIONS |
| | ADJACENT TO THE HEATER. (ADD TO NOTES) |
| | 9) |
| | FBC-2001 SEC 424.2.15 GAS PIPING SHALL |
| | COMPLY WITH FBC FUEL GAS. SEPARATE PLANS |
| | AND PERMIT REQUIRED. (NOTES) |
| | |