Plan Review Details - Permit 02030788
Plan Review Stops For Permit 02030788
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-24 Cont ID  
Sent By lmartine Date 2002-04-24 Time 16:46 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-02 Cont ID  
Sent By btrobaug Date 2002-03-29 Time 16:33 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2002-04-02 00:00:00FAILED BUILDING FOR THE FOLLOWING:
  
 1. FBC 2001 MUST BE THE CODE REFERENCE
 ON THE PLANS.ALL CALCULATIONS MUST BE
 TO THIS CODE.
  
 2. DETAILS FOR THE CONCRETE PAD FOR THE
 EQUIPMENT MUST BE SHOWN ON THE PLANS
 WITH THE ANCHORING DETAIL FOR THE
 EQUIPMENT
  
 3. DETAILS FOR COMPLIANCE TO FBC
 CHAPTER 4 MUST BE NOTED ON PLANS.THIS
 INCLUDES ALL THE REFERENCES TO POOL
 SAFETY THAT USED TO BE IN THE STATE
 STATUTES CHAPTER
 515.THIS SS 515 HAS BEEN DELETED.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-29 Cont ID  
Sent By kstevens Date 2002-03-29 Time 16:10 Rev Time 0.00
Received By btrobaug Date 2002-03-29 Time 16:29 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-05-01 Cont ID  
Sent By kstevens Date 2002-05-01 Time 10:29 Rev Time 0.00
Received By kstevens Date 2002-05-01 Time 10:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-04-24 Cont ID  
Sent By kstevens Date 2002-04-24 Time 11:43 Rev Time 0.00
Received By kstevens Date 2002-04-24 Time 11:52 Sent To  
Notes
2002-04-24 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 A) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 B)
 FBC-2001 SEC 424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 C)
 FBC-2001 SEC 424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MI8NIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)
 D)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 E)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 2) THIS INFORMATION WAS REQUESTED ON
 PREVIOUS REVIEW. SOME INFORMATION WAS
 SUPPLIED, SOME PARTIALLY SUPPLIED. IF
 FAX NOT RECIEVED I DID NOT KNOW. SEE
 ATTACHED SHEET.
 3) PLEASE PUT ALL PAGES TOGETHER TO FORM
 TWO COMPLETE SETS OF PLANS. LOOSE SHEETS
 CAN GET LOST.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-29 Cont ID  
Sent By kstevens Date 2002-03-29 Time 15:17 Rev Time 0.00
Received By kstevens Date 2002-03-29 Time 15:33 Sent To E
Notes
2002-03-29 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS.
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92.
 3) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 4)
 FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 5)
 FBC-2001 SEC 424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 6)
 FBC-2001 SEC 424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MI8NIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)
 7)
 FBC-2001 SEC 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 8)
 FBC-2001 SEC 424.2.8.1 VALVES SHALL BE
 MADE OF MATERIALS THAT ARE APPROVED IN
 THE FLA BLDG CODE, PLUMBING. THEY WILL
 BE READILY ACCESSIBLE FOR MAINT. AND RE-
 MOVAL. SEC 424.2.8.2 FULL WAY VALVES
 SHALL BE INSTALLED TO INSURE PROPER FUN-
 CTION OF THE FILTRATION AND PIPING SYS-
 TEM. SEC 424.2.8.3 WHERE CHECK VALVES
 ARE INSTALLED THEY SHALL BE OF THE SWING
 OR VERTICAL CHECK PATTERNS. SEC 424.2.8.
 4 COMBINATION VALVES SHALL REQUIRE APP-
 ROVAL OF THE ADMINISTRATIVE AUTHORITY
 PRIOR TO THEIR INSTALLATION.
 9)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 10)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 11)
 FBC-2001 SEC 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 )
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-19 Cont ID  
Sent By sgraham Date 2002-03-19 Time 08:56 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***