Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-04-18 Cont ID  
Sent By rbrown Date 2002-04-18 Time 08:23 Rev Time 0.00
Received By rbrown Date 2002-04-18 Time 08:23 Sent To  
Notes
2002-04-18 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) FBC* 104.2.1SUBMIT A FLOOR PLAN TO
 SHOW THE OCCUPATION/USE OF THE NEW
 ROOM(S) AND THE MEANS OF ACCESS/EGRESS.
 IF IT IS TO INCORPORATE A SLEEPING ROOM,
 THEN THAT ROOM SHALL HAVE A DOOR OR
 WINDOW WHICH COMPLIES WITH THE EMERGENCY
 EGRESS REQUIREMENTS (FBC 1005.4.1).THE
 PLAN SHALL STATE THE FLOOR AREA OF THE
 NEW ROOM.
  
 3) NO ELECTRICAL, MECHANICAL OR PLUMBING
 PLANS HAVE BEEN SUBMITTED.SEPARATE
 PERMIT APPLICATIONS WILL BE REQUIRED FOR
 WORK UNDER THESE TRADES.
  
 4) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE ENERGY CODE COMPLIANCE FORMS
  
 5) FBC* 104.2.1SUBMIT AN EAVES DETAIL
 SHOWING THE TYPE OF COVERING ON THE
 EXISTING ROOF, ROOF INSULATION, WALL
 INSULATION, CEILING AND WALL LININGS,
 AND EXTERIOR WALL SHEATHING AND WEATHER-
 PROOFING.
  
 6) FBC* 104.2.1STATE THE SIZE OF THE
 NEW WINDOWS.THE STATED DOOR HEIGHT OF
 6 FEET ROUGH IS INSUFFICIENT.
  
 7) FBC 1606.1.4WINDOW PRODUCT APPROVAL
 THE NOTICE OF ACCEPTANCE FOR THE 'SERIES
 PA-14 ALUMINUM SINGLE HUNG WINDOW' IS
 MISSING SHEET 2, WHICH SHOULD BE
 ENTITLED "....SPECIFIC CONDITIONS".
 ALSO, THE NOTICE OF ACCEPTANCE AND
 ASSOCIATED DRAWINGS ARE NOT FULLY
 LEGIBLE AS THEY HAVE BEEN REPEATEDLY
 FAXED/COPIED.SUBMIT COMPLETE AND
 LEGIBLE COPIES OF THE PRODUCT APPROVAL.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE
 REQUIRED HURRICANE MISSILE IMPACT
 PROTECTION SHUTTERS, OR A SEPARATE
 SHUTTER PERMIT APPLICATION WILL BE
 REQUIRED.
  
 9) FBC 2303.3WEATHER PROTECTION.THE
 STRUCTURAL FRAME AND INTERIOR WALL
 COVERING SHALL BE PROTECTED BY TYPE 15
 FELT OR KRAFT WATERPROOF BUILDING PAPER
 OR OTHER APPROVED WEATHER BARRIER.THE
 APPLICATION OF THE WEATHER PROTECTION
 BARRIER SHALL BE IN ACCORDANCE WITH THE
 CODE REQUIREMENT.
  
 10) FBC 2308.2.2.1THE EXTERIOR STUD
 WALLS SHALL INCORPORATE SHEATHING OF
 EXTERIOR GRADE PLYWOOD (MIN. 5/8" THICK)
 OR OTHER SHEATHING TYPE AS REFERENCED IN
 FBC TABLE 2308.2.2B
  
 11) FBC 2308.3.2 WINDOW AND DOOR HEADERS
 THE ENDS OF EACH HEADER SHALL BE
 SUPPORTED BY JACK STUDS AS SHOWN ON THE
 ATTACHED FIGURE.
  
 12) FBC* 104.2.1SPECIFY THE
 MANUFACTURER'S TYPE REFERENCE AND
 SPACING OF ANCHORS AND CONNECTORS FOR
 THE STUD WALLS.
  
 NOTE:
 AS PER LUIS MARTINEZ, THE ABOVE COMMENTS
 SUPERCEDE THE BUILDING PLAN REVIEW DATED
 4/4/02.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-04 Cont ID  
Sent By kstevens Date 2002-03-29 Time 09:37 Rev Time 0.00
Received By lsmith Date 2002-04-04 Time 07:50 Sent To  
Notes
2002-04-04 00:00:00*******************FAILED***************
  
  
 1. NEED PRODUCT APPROVALS FOR STORM
 PANELS OVER WINDOWS PER FBC 2001
  
 2. NEED TO SHOW TYPE OF USE OF ROOM.
 IFIT IS TO BE LIVING AREA THE PLANS
 MUST BE TAKEN TO PBC FOR PAYMENT OF
 IMPACT FEES.A COPY OF THE RECEIPT &
 STAMPED PLANS MUST BE RETURNED TO US TO
 ISSUE THE PERMIT.
  
 3. DRAWINGS MUST SHOW TYPE OF ANCHORS,
 HURRICANE CLIPS, ETC.
  
 4. ALL WOOD TOUCHING CONCRETE MUST BE PT
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT 8394

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-03-21 Cont ID  
Sent By btrobaug Date 2002-03-21 Time 15:10 Rev Time 0.00
Received By btrobaug Date 2002-03-21 Time 15:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-03-22 Cont ID  
Sent By pkrauss Date 2002-03-22 Time 09:05 Rev Time 0.25
Received By pkrauss Date 2002-03-22 Time 09:05 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-03-29 Cont ID  
Sent By pkrauss Date 2002-03-22 Time 09:05 Rev Time 0.00
Received By kstevens Date 2002-03-29 Time 09:36 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-20 Cont ID  
Sent By sgraham Date 2002-03-20 Time 12:37 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***