Plan Review Details - Permit 02030644
Plan Review Stops For Permit 02030644
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-24 Cont ID  
Sent By btrobaug Date 2002-04-24 Time 11:14 Rev Time 0.00
Received By btrobaug Date 2002-04-24 Time 11:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-28 Cont ID  
Sent By kstevens Date 2002-04-23 Time 20:04 Rev Time 0.00
Received By btrobaug Date 2002-03-28 Time 16:36 Sent To M
Notes
2002-03-28 00:00:00*************** UNSAT ******************
  
 PLEASE PROVIDE A DRAWING OFTHE SERVICE
 AND HOW CONNECTED TO THE HOME.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/659-8096
 EXT 8392

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-28 Cont ID  
Sent By btrobaug Date 2002-03-28 Time 16:43 Rev Time 0.30
Received By pkrauss Date   Time   Sent To R
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-04-23 Cont ID  
Sent By kstevens Date 2002-04-23 Time 20:04 Rev Time 0.00
Received By kstevens Date 2002-04-23 Time 19:52 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-28 Cont ID  
Sent By kstevens Date 2002-03-28 Time 15:21 Rev Time 0.00
Received By kstevens Date 2002-03-28 Time 15:23 Sent To  
Notes
2002-03-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) PLEASE PROVIDE A FLOOR PLAN SHOWING
 HOW AND WHERE THE SEWER AND WATER WILL
 BE TYING INTO BLDG. SHOW WHERE UTILITIES
 ARE ENTERING THE PROPERTY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-04-23 Cont ID  
Sent By jwitmer Date 2002-04-23 Time 07:35 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-04-12 Cont ID  
Sent By pkrauss Date 2002-03-28 Time 16:58 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-15 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02030644
 932 21ST STREET
 CONT: MALCULM CONST. INC
 TEL: (561)741-8755
 CEL: (561)632-9000
  
 FL BLDG CODE= 2001 FLORIDA BUILDING CODE
  
 1) SOILS REPORT IS NOT FOR THIS LOCATION
  
 2) THE FOUNDATION DETAIL IS A GENERIC
 DETAIL, IT IS TO BE SITE SPECIFIC, MEET
 ALL THE CODE REQUIREMENTS WHICH WILL
 GIVE US AN EXACT MINIMUM STEM WALL
 HEIGTH:
 A)FL BLDG 1804.1.3 THE BOTTOM OF THE
 FOUNDATION SHALL EXTEND NO LESSS THAN
 12" BELOW FINISHED GRADE.
 B)FL BLDG 2304.3.3 WHEN WOOD JOIST OR
 THE BOTTOM OF WOOD STRUCTURAL FLOORS
 WITHOUT JOIST ARE CLOSER THAN 18" THEN
 APPROVED NATURALLY DURABLE WOOD OR
 PRESSURE TREATED WOOD IS TO BE USED.
 C) FL BLDG CODE 1012.1.5 LANDINGS:
 IN GROUP 3 OCCUPANCIES, LANDINGS MAY BE
 ONE STEP LOWER THAN INSIDE FLOOR, BUT
 NOT MORE THAN 7". LANDINGS SHALL NOT BE
 LESS THAN THE DOOR IT SERVES AND THE
 DEPTH SHALL BE NOT LESS THAN 36".
  
 3) THE STATE CERTIFIED PLANS INDICATE
 THAT THE INSTALLATION INSTRUCTIONS FOR
 ADDITIONAL SET UP INFORMATION HAS INFORM
 ATION ON GLAZING PROTECTION FOR WIND-
 BORNE DEBRIS REGIONS, FL BLDG CODE
 1606.1.4 REQUIRES PROTECTION OF ALL
 GLAZED OPENINGS, PLEASE PROVIDE INFORMA-
 TION, MISSING PAGES 1- 36.
 4) ALSO PROVIDETHE INFORMATION ON
 HINGED ROOFS, IN SAME INSTALLATION
 PACKAGE.
 5) FL ENERGY SHEET INDICATES THE SOUTH-
 ERN ZONE, ITEM # 5 IS THIS WORST CASE ?
 ANSWER : NO. CHECKING WITH DCA TO SEE
 WHY THIS IS NOT WORST CASE IF THIS IS
 MASTERED THROUGH STATE OR IF THIS SHOULD
 BE SITE SPECIFIC SINCE IT IS NOT WORST
 CASE SENARIO!!!!! THE STATE INDICATED BY
 RETURN PHONE CALL( ILLA JONES) THAT IF
 THE STATE CERTIFICATION WAS NOT WORST
 CASE FOREACH ZONE THEN SITE SPECIFIC
 ENERGY SHEETS SHALL BE REQUIRED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096X8412

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-28 Cont ID  
Sent By sgraham Date 2002-03-28 Time 15:40 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***