Plan Review Details - Permit 02030624
Plan Review Stops For Permit 02030624
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-15 Cont ID  
Sent By lsmith Date 2002-05-15 Time 14:24 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-03 Cont ID  
Sent By btrobaug Date 2002-03-21 Time 06:53 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2002-04-03 00:00:00FAILED:
  
 1. FBC 2001 STATES SAFETY REQUIREMENTS
 FORMERLY SHOWN IN SS515 SHOULD NOW BE
 INCLUDED ON THE PLANS AND REFERENCE
 FBC2001THERE IS NO LONGER A REFERENCE
 AT SS515 FOR POOL SAFETY FEATURES.
  
 2. CONCRETE PAD FOR POOL EQUIPMENT MUST
 BE SHOWN ON PLANS AND METHOD OF
 ANCHORING OF EQUIPMENT MUST BE SHOWN.
  
 3. NOTE 8: GENERAL NOTES: MUST STATE
 POOL IS CONSTRUCTED ACCORDING TO
 FBC2001 CHAPTER 4 SEC. 424 PRIVATE
 RESIDENTIAL SWIMMING POOL.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 561-659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-21 Cont ID  
Sent By btrobaug Date 2002-03-21 Time 06:53 Rev Time 0.00
Received By btrobaug Date 2002-03-21 Time 06:52 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-05-15 Cont ID  
Sent By kstevens Date 2002-05-15 Time 14:57 Rev Time 0.00
Received By kstevens Date 2002-05-15 Time 14:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-04 Cont ID  
Sent By kstevens Date 2002-05-04 Time 06:50 Rev Time 0.00
Received By kstevens Date 2002-05-04 Time 06:50 Sent To  
Notes
2002-05-04 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 2)
 FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 3)
 FBC-2001 SEC 424.2.7.1 POOL CIRCULATING
 PUMPS SHALL BE EQUIPPED ON THE INLET
 SIDE WITH AN APPROVED TYPE HAIR AND LINT
 STRAINER WHEN USED WITH A PRESSURE FIL-
 TER. (DETAIL)
 4)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 5)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 6)
 FBC-2001 SEC 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-29 Cont ID  
Sent By btrobaug Date 2002-03-21 Time 06:54 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-03-29 00:00:00PLUMBING PLAN REVIEW, FBC 2001,DENIED
 (1) COMPLY WITH FBC 2001 SEC 424.2
 PRIVATE SWIMMING POOLS.
 (2)SEC 424.2.6 ENGINEERING DESIGN,CONST-
 RUCTION AND WORKMANSHIP, ANSI/NSPI-492
 (3)SEC 424.2.6.6 ENTRAPMENT PROTECTION
 FOR SUCTION INLETS. (DETAIL)
 (4) SEC 424.2.6.6.3 (1,2,3) ENTRAPMENT
 AVOIDANCE.(DETAIL)
 (5) SEC 424.2.7.2 MOUNTING EQIPMENT TO
 CONCRETE PAD.(DETAIL)
 (6) SEC 424.2.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW PREVENTER REQUIRED ON
 WATER SERVICE.
 (7) SEC 424.2.13.2 PURPLE CLEANER FOR
 PVC PIPEING.
 (8) ADDRESS EACH COMMENT PROVIDE DETAILS
 END OF COMMENTS, PAUL SCHMITZ
 QUESTIONS 561-659-8096X8233

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-19 Cont ID  
Sent By sgraham Date 2002-03-19 Time 09:54 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***