Plan Review Details - Permit 02030624
| Plan Review Stops For Permit 02030624 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-05-15 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2002-05-15 |
Time |
14:24 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-04-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-21 |
Time |
06:53 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-03 00:00:00 | FAILED: | | | | | | 1. FBC 2001 STATES SAFETY REQUIREMENTS | | | FORMERLY SHOWN IN SS515 SHOULD NOW BE | | | INCLUDED ON THE PLANS AND REFERENCE | | | FBC2001THERE IS NO LONGER A REFERENCE | | | AT SS515 FOR POOL SAFETY FEATURES. | | | | | | 2. CONCRETE PAD FOR POOL EQUIPMENT MUST | | | BE SHOWN ON PLANS AND METHOD OF | | | ANCHORING OF EQUIPMENT MUST BE SHOWN. | | | | | | 3. NOTE 8: GENERAL NOTES: MUST STATE | | | POOL IS CONSTRUCTED ACCORDING TO | | | FBC2001 CHAPTER 4 SEC. 424 PRIVATE | | | RESIDENTIAL SWIMMING POOL. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 561-659-8096 EXT. 8394 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-03-21 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-21 |
Time |
06:53 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-03-21 |
Time |
06:52 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-05-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-15 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-15 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-05-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-04 |
Time |
06:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-04 |
Time |
06:50 |
Sent To |
|
|
| Notes |
| 2002-05-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | | | 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | | FORMATION REQUIRED FOR PLAN REVIEW | | | 2) | | | FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE | | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | | NUMBER AND MANUF INFO FOR VAC LOCK. | | | (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) | | | 3) | | | FBC-2001 SEC 424.2.7.1 POOL CIRCULATING | | | PUMPS SHALL BE EQUIPPED ON THE INLET | | | SIDE WITH AN APPROVED TYPE HAIR AND LINT | | | STRAINER WHEN USED WITH A PRESSURE FIL- | | | TER. (DETAIL) | | | 4) | | | FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL | | | ORD. #2853-95, BACKFLOW REQUIRED ON | | | WATER SERVICE. (ADD TO NOTES) | | | 5) | | | FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. | | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. (ADD TO NOTES) | | | 6) | | | FBC-2001 SEC 424.2.13.2JOINTS AND CON- | | | NECTIONS, FBC PLMG SEC 605.21, PURPLE | | | PRIMER REQUIRED ON PVC PIPING. (ADD TO | | | NOTES) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-03-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-21 |
Time |
06:54 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-29 00:00:00 | PLUMBING PLAN REVIEW, FBC 2001,DENIED | | | (1) COMPLY WITH FBC 2001 SEC 424.2 | | | PRIVATE SWIMMING POOLS. | | | (2)SEC 424.2.6 ENGINEERING DESIGN,CONST- | | | RUCTION AND WORKMANSHIP, ANSI/NSPI-492 | | | (3)SEC 424.2.6.6 ENTRAPMENT PROTECTION | | | FOR SUCTION INLETS. (DETAIL) | | | (4) SEC 424.2.6.6.3 (1,2,3) ENTRAPMENT | | | AVOIDANCE.(DETAIL) | | | (5) SEC 424.2.7.2 MOUNTING EQIPMENT TO | | | CONCRETE PAD.(DETAIL) | | | (6) SEC 424.2.9 WATER SUPPLY, LOCAL ORD. | | | #2853-95, BACKFLOW PREVENTER REQUIRED ON | | | WATER SERVICE. | | | (7) SEC 424.2.13.2 PURPLE CLEANER FOR | | | PVC PIPEING. | | | (8) ADDRESS EACH COMMENT PROVIDE DETAILS | | | END OF COMMENTS, PAUL SCHMITZ | | | QUESTIONS 561-659-8096X8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-03-19 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-03-19 |
Time |
09:54 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|