Plan Review Details - Permit 02030620
Plan Review Stops For Permit 02030620
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-15 Cont ID  
Sent By lsmith Date 2002-05-15 Time 14:26 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-03 Cont ID  
Sent By btrobaug Date 2002-03-29 Time 13:34 Rev Time 1.00
Received By lsmith Date   Time   Sent To  
Notes
2002-04-03 00:00:00******************FAILED**************
  
 1. FBC2001 STATES SAFETY REQUIREMENTS
 FORMERLY SHOWN IN SS #515 SHOULD NOW BE
 INCLUDED ON THE PLANS AND REFERENCE
 FBC2001 CHAPTER 424: RESIDENTIAL
 PRIVATE POOL SAFETY FEATURES.
  
 2.DETAILS ON CONCRETE PAD FOR POOL
 EQUIPMENT MUST BE SHOWN ON THE PLANS
 INCLUDING ALL REQUIRED ANCHORING
 DETAILS FOR EQUIPMENT ANCHORING.
  
 3. NOTE 8: GENERAL NOTES:MUST STATE
 POOL IS CONSTRUCTED ACCORDING TO
 FBC2001 CHAPTER 4 SEC. 424 PRIVATE
 RESIDENTIAL POSWIMMING POOL.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-29 Cont ID  
Sent By btrobaug Date 2002-03-29 Time 13:34 Rev Time 0.00
Received By btrobaug Date 2002-03-29 Time 13:05 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-05-15 Cont ID  
Sent By kstevens Date 2002-05-15 Time 13:17 Rev Time 0.00
Received By kstevens Date 2002-05-15 Time 13:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-04 Cont ID  
Sent By kstevens Date 2002-05-04 Time 06:29 Rev Time 0.00
Received By kstevens Date 2002-05-04 Time 06:28 Sent To  
Notes
2002-05-04 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 2)
 FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 3)
 FBC-2001 SEC 424.2.7.1 POOL CIRCULATING
 PUMPS SHALL BE EQUIPPED ON THE INLET
 SIDE WITH AN APPROVED TYPE HAIR AND LINT
 STRAINER WHEN USED WITH A PRESSURE FIL-
 TER. (DETAIL)
 4)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 5)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 6)
 FBC-2001 SEC 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL) NOT SHOWN
 7)
 FBC-2001 SEC 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 8)
 FBC-2001 SEC 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 SHOW DETAIL FOR WATER RETENTION ON CUT
 SHEETS.
 9)
 FBC-2001 SEC 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-29 Cont ID  
Sent By pschmitz Date 2002-03-29 Time 10:16 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-03-29 00:00:00PLUMBING PLAN REVIEW,FBC 2001, DENIED.
 (1) COMPLY WITH FBC 2001 SEC 424.2
 PRIVATE SWIMMING POOLS.
 (2) SEC 424.2.6 ENGINEERING DESIGN,CONST
 RUCTION AND WORKMANSHIP,ANSI/NSPI-492
 (3) SEC 424.2.6.6 ENTRAPMENT PROTECTION
 FOR SUCTION INLETS(DETAIL)
 (4) SEC 424.2.6.6.3 (1,2,3) ENTRAPMENT
 AVOIDANCE.(DETAIL)
 (5) SEC 424.2.7.2 MOUNTING AND ANCHORING
 EQUIPMENT TO CONCRETE PAD.(DETAIL)
 (6) SEC 424.2.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW PREVENTER REQUIRED ON
 WATER SERVICE.
 (7)SEC 424.2.13.2 JOINTS AND CONNECTIONS
 FBC-P SEC 605.21, PURPLE PRIMER REQUIRED
 ON PVC PIPING.
 (8) SEC 424.2.14.1 WATER HEATING EQUIP-
 MENT: LABELS, MFG CUT SHTS.
 (9) SEC 424.2.14.2 WATER RETENTION:
 PROVIDE A POSITIVE MEANES OF RETANING
 WATER IN THE HEATER WHEN PUMP IS NOT
 (10)ADDRESS EACH COMMENT,PROVIDE DETAILS
 FOR CLARITY.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-19 Cont ID  
Sent By sgraham Date 2002-03-19 Time 09:44 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***